HIGH BAY DUAL SENSE SENSOR HIM34
Installation and Instruction Manual

1. Technical Specifications

Product type Operating voltage Switched power Power consumption Detection angle Detection area (Max.)*
Detection range Hold time Stand-by time Stand-by dimming level Daylight threshold Warmming-up time Operating temperature IP rating Sensor mode

High bay dual sense DALI sensor (Daylight harvest) 220-240VAC 50/60Hz Maximum 20pcs DALI devices Maximum 40mA < 1W 360o Installation Height : 15m Detection Range (Ø) :18m 10% / 50% / 75% / 100% 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min 0s / 10s / 1min / 5min / 10min / 30min / 1h / +  10% / 20% / 30% / 50% 50 ~ 500Lux , Disable 30s -35oC ~ +50oC IP65 HF, PIR, HF+PIR, HF / PIR

2. Installation
Warnings: 1. Installation of the sensor involves connecting it to the mains supply. This work must be
carried out by a specialist in accordance with electrotechnical regulations. 2. Disconnect power supply before installing.
A. Ceiling mount

91.5 80.7
75 4.1

LED indicator Photocell
PIR

Infrared receiver Rotary switch for programing

Sensor module

Cable entry

4.1
66.6 81.5

47.5

57.3

59.3

73.5

Installation rack

64 24.5

3. Rotary Switch Settings

B. Screw to the Luminaire by conduit

LED indicator Photocell
PIR

Infrared receiver Rotary switch for programing

75

43.8

59.6 43

0.825"

A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels available:

Rotary switch preset (Please see the location in 2. Installation)

Channel
0 1 2 3 4 5 6 7 8 9 A B C D E F

Detection range
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

Hold time
5s 1min 5min 5min 5min 5min 10min 10min 10min 10min 20min 20min 30min 30min 30min 5s

Stand-by time
10s 5min 10min + + + 30min + + + 1h + + + + 10s

Stand-by dimming level
10% 10% 10% 10% 10% 30% 10% 10% 10% 30% 10% 30% 10% 30% 50% 10%

Daylight threshold
Disable 50Lux 50Lux 75Lux 100Lux 200Lux 50Lux 75Lux 100Lux 200Lux 100Lux 200Lux 100Lux 200Lux 400Lux 100Lux

Note: settings can also be changed by remote control HRC-11. The last action controls.

4. Functions
4.1 Daylight Harvest (Daylight Regulating) Daylight sensor measures the available natural light of the surrounding, calculates how much electrical light is needed to reach the total lux expected. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light.
Light level

Sensor module

Cable entry

66.6 89.9

73.5 59.3 57.3 47.5 33.7 35.2

C. Attach to the shade by clamp

LED indicator Photocell
PIR

Infrared receiver Rotary switch for programing
Angle adjustment Luminaire clamp

Sensor module

66.6 96.8 163.2

4.5 15
4.5 28.5
29

93.8 84.5 59.3

Note:We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.
4.2 Lux Off Function The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is not required (natural light lux level exceeds daylight threshold). Note: if the stand-by time is preset at "+", the fixture never switches off even when natural light
is sufficient.
4.3 Load Indication The light will flash ONCE rapidly after receiving the command from the remote controller. Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100% or POWER 80% is pressed.
5. Wiring Diagram L N

Hold time Energy Saving Zone

Stand-by time

Normal Electric Light
Daylight controlled light Natural light

Brown Blue
Red Black

L LED N Driver
DALI +
DALI -

0

24 Time (hrs)

HIM34

HIM34-20190104-A1

6. Three Options for PIR Lens and Detection Patterns (End user can choose the suitable lens in real application for various requirements)
* For single person walking across, the detection range is reduced by 1/3.

1

2

3

PIR

15m

HF

HFPIwR atalknignegnatiacrlomssov1e4mment 18m
PIR detection: H x D:15 x 18m (max.) HF detection: H x D:15 x 14m (max.)
7. Descriptions of the Button Functions (remote control HRC-11)

4

1

2

5

3

6 7

8

9

10

11

12

& A

4h

h

4h

13

14 15

HRC-11

PIR

15m

HF

5m

PIR

15m

HF

18m

14m 18m
PIR detection: L x W x H:18 x 5 x 15m (max.) HF detection: H x D:15 x 14m (max. )

5m 14m
PIR detection: L x W x H:5 x 18 x 15m (max.) HF detection: H x D:15 x 14m (max. )

Permanent ON/OFF [ button 1 ] Press button 1 ,to select permanent ON or permanent OFF mode. * Press button 2 / 4 to resume automatic operation The mode will change to AUTO Mode after power failure. .RESET[ button 2 ] Press button 2 , all settings go back to the rotary switch settings.
Shift [ button 3 ] Press button 3 , the LED on the top left corner is on for indication. All values / settings in RED are valid for 20 seconds.
Auto Mode [ button 4 ]
Press button 4 to initiate automatic mode.The sensor starts working and all settings remain as before the light was switched ON/OFF. Note: the function of Semi-auto is disabled.
Power output [ button 5 ] Press button 5 , the light output shifts between 80% and 100%. Note: the function of "Sensor off" and "Twilight" are disabled.
Brightness +/- [ button 6 ] Press button 6 to adjust the light brightness to reset the target lux level.
Scene prog. [ zone 7 ] (One-key-commissioning)
1. Press button "Start" to program. 2. Select the buttons in 8 "Detection range", 9 / 10 "Daylight threshold",
11 "Hold time", 12 "Stand-by time", 13 "Stand-by dimming level" to set all parameters. 3. Press button "Memory" to save all the settings programmed in the remote control. 4. Press button "Apply" to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, the steps should be as follows: Press button 7 Start, button 8 100%, 10 Disable, 3 Shift, 11 5min, 3 Shift, 12 +, 13 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
Detection range [ zone 8 ] Press buttons in zone 8 to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold [ zone 9 ]
Press buttons in zone 9 to set the daylight sensor at 50Lux / 100Lux / 300Lux / 500Lux or Disable as threshold / target Lux level. Note: 2Lux / 10Lux are disabled.
To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button 3 Shift at first.

Ambient daylight threshold [ button 10 ] 1. Press button 3 Shift, the red LED is on for indication. 2. Press button 10, the ambient lux level is sampled and set as
daylight threshold / target Lux level.
Hold time [ zone 11 ]
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button
3 Shift at first. 2. 2s is for testing purpose only, stand-by period and daylight
sensor settings are disabled in this mode. * To exit from Test mode, press button 2 or any button in zone 11 .
Stand-by time [ zone 12 ]
Press buttons in zone 12 to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +. Note: "0s" means on/off control; "+" means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence is detected after hold-time.
Stand-by dimming level [ zone 13 ] Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30% / 50%.
Daylight harvest auto-configuration function
1. Press button "Shift", the red LED is on for indication. 2. Select a time period and the sensor will do light level measurement
and determine/save the lowest light level (commission line) with 100% light on, so as to set the target lux level automatically. Note: 1. Make sure the light level measurement covers the night time.
2. The fixture will go into sensor mode after the measurement, all sensor settings remain unchanged.
Dual tech [ zone 14 ]
Press buttons in zone 14 to select sensor technology. HF+PIR: Light is on when both HF and PIR sensors are activated. HF/PIR: Light is on when HF or PIR sensors are activated.
RF mode [ zone 15 ] All buttons in zone 15 are disabled.

Hytronik Industrial Ltd. | www.hytronik.com 3rd Floor, block C, complex building, 155#, Bai'gang road south, Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023 Tel: 86-752-2772020 Fax: 86-752-2777877