User Manual for global sources models including: TZ-CT01 CO Transmitter, TZ-CT01, CO Transmitter, Transmitter

SHT3X485

雨林木风

TZ-CT01 CO₂ Transmitter User Manual V1.0 - Global Sources

User Manual V1.0 ... TZ-CT01 adds a display screen and indicator lights, users can see the current carbon ... about 1200 meters (depending on the use.

Suggest to connect the common ground of each transmitter together, and then connect it to the ground wire of the RS-232/RS-485 transverter, you can use the ...

prieš 17 valandų — Suggest to connect the common ground of each transmitter together, and then connect it to the ground wire of the RS-232/RS-485 transverter, you can use the ...

PDF preview unavailable. Download the PDF instead.

K1195695729
TZ-CT01 CO Transmitter User Manual V1.0
-1-

1. Overview
TZ-CT01 is a transmitter independently developed by our company to measure CO concentration. The sensing element adopts NDIR dual beam infrared carbon dioxide sensor, which has a fast and sensitive response, avoiding the life and long-term drift problems of traditional electrochemical sensors, and is widely used in agricultural greenhouses, flower cultivation, edible mushroom cultivation and other occasions that require CO monitoring.
TZ-CT01 CO transmitter is designed based on RS485 communication interface, compatible with standard Modbus-RTU protocol, and can be connected to Modbus network to realize the measurement and monitoring of carbon dioxide concentration.
TZ-CT01 adopts the DIP switch to set the address, which avoids the need to use the host computer to set the address in advance, simple, convenient and easy to maintain and replace.
TZ-CT01 adds a display screen and indicator lights, users can see the current carbon dioxide concentration more intuitively.
2. Features
 High long-term stability using dual-beam NDIR sensor  High sensitivity and strong anti-interference ability  High precision and good consistency  Long life and low drift  Gas sampling compatible with diffusion and vented  Standard Modbus-RTU protocol
 Strong interface defense capability and stable communication
3. Application areas
Generally used in indoor clean environment, such as:  Indoor air quality monitoring  Greenhouse farms, agricultural greenhouses  Flower cultivation, edible mushroom cultivation
-2-

 HVACHeating, ventilation and air conditioning  DCVFresh Air Energy Saving System

4. Technical data
4.1 Specifications
Supply voltage Sensing element Measuring range Measurement period Measurement accuracy Display screen Resolution Indicator light Transfer protocol Transmission rate Transmission distance
Number of theoretical nodes Operating temperature range Storage temperature Operating humidity range Storage humidity Dimensions

DC 536V NDIR
010000ppm 2s
±50ppm+3% reading value Keep the power on and the screen will turn on 1ppm Keep power on, it will be solid red RS485 serial port, standard modbus RTU 4800bps / 9600bps The standard maximum transmission distance is about 1200 meters (depending on the use environment, transmission material and transmission rate) 32
0~50
-20~60 0~95% 0~95% 109mm x 67mm x 40mm

4.2 PC electrical connection

Lead Green Yellow Black

Label BA+ GND

Red

V+

Function description RS485 interface BRS485 interface A+ Public ground (connect to the negative end of the power supply when DC power is supplied) Power supply positive (connect to the positive end of the power supply when DC power is supplied)
-3-

4.3 Schematic diagram of connection with PC
Note: When setting up a RS485 network, pay attention to the RS485 grounding treatment to eliminate the common mode voltage. Suggest to connect the common ground of each transmitter together, and then connect it to the ground wire of the RS-232/RS-485 transverter, you can use the shielding layer of the shielded wire as the ground wire.
5. DIP switch and address code
Note: The above picture is a schematic diagram of the DIP switch. The DIP switch has 8 DIP positions. The corresponding numbers from 1 to 8 are 128, 64, 32, 16, 8, 4, 2, 1, and these values are added together as the address code. As shown in the figure above, bits 1, 3, and 4 are in the ON position, so the address code is 128+32+16=176, that is, the address code is 176.
-4-

First Step

Second Step

The above picture is a schematic diagram of the correct steps to turn on the DIP switch Step 1: Use a screwdriver to unscrew the screws in the four corners of the picture, as shown in the first step above. Step 2: Turn on the DIP switch to set the address, as shown in the second step above. The part circled on the left is the power communication interface. The connection method has been explained in the electrical connection in 4.3, please read it carefully.
Note: You can specify when ordering, we will preset it for you.
6. Protocol
For the Modbus-RTU protocol, please refer to the relevant information, here is only a brief introduction.

6.1 Data frame format

Start bit 1

Data bit 8

Parity bit 0

Stop bit 1

Note: The above is the default format of the transmitter. If you need other formats, please specify when ordering.

-5-

6.2 RTU information format
TZ-CT01 follows the RTU information frame protocol. In order to ensure the integrity of the information frame, a pause time of 3.5 characters or more is required at the beginning and end of each information frame (T1-T2-T3-T4, the time can be calculated based on the specified baud rate), each byte of the information frame needs to be transmitted continuously. If there is a pause time greater than 1.5 characters, the transmitter will treat it as invalid information and will not respond.

6.3 Information frame format

Start T1-T2-T3-T4

Address 1 byte

Function code 1 byte

Data area N byte

CRC check 2 byte

End T1-T2-T3-T4

6.4 Register definition

Register Address

Meaning

0

Temperature

1

Relative humidity

2

Reserved 1

3

CO value

4

RS485 address

5

Baud rate

6

Hardware version

7

Software version

Description
The unit is 0.1 degree, MSB First, complement format, 7FFF H means the transmitter is abnormal
The unit is 0.1%, MSB First,complement format, 7FFF H means the transmitter is abnormal

Read and write Read only
Read only
Read only

Unit ppm, MSB First, FFFFH means the transmitter is abnormal
Set by the DIP switch, the settable range is [1,255]
Support 4800bps/9600bps

Read only
Read only
Can read and write Read only Read only

-6-

6.5 Address setting
You can specify when ordering, we will preset it for you, or you can modify it by yourself through the dial switch.
6.6 Baud rate setting
You can specify when ordering, we will preset it for you, or you can modify it by yourself through the serial port assistant.
6.7 Host reads transmitter information (function code 03)
The transmitter allows the host to use the function code 03 to read the CO concentration measurement value of the transmitter and other information. The information frame format of the 03 code is as follows
-7-

Host request information frame

Transmitter response information frame

Field Description Slave address Function code Register address high byte Register address low byte High byte of query quantity Low byte of query quantity CRC check code low byte CRC check code high byte

Example FF 03 00 00 00 08 51 D2

Data parsing

Field Description

Example

Slave address

FF

Function code

03

Return the number of

bytes

10

Temperature data high

byte

7F

Temperature data low

byte

FF

Humidity data high byte 7F

Low byte of humidity data FF

1 high byte reserved

00

1 low byte reserved

00

CO concentration data

high byte

04

CO concentration data

low byte

59

Address code high byte 00

Address code low byte

FF

Baud rate high byte

25

Baud rate low byte

80

Hardware version high

byte

07

Hardware version low byte 01

Software version high byte 00

Software version low byte 10

CRC check code low byte 87

CRC check code high byte AE

Temperature = 7FFFH = 32767, indicates no temperature data

Humidity = 7FFFH = 32767, indicates no temperature data

Reserved 1 = 0000H;

CO concentration = 0459H=1113, indicating that the CO concentration is 1113ppm;

Address code = 00FFH = 255;

Baud rate = 2580H = 9600;

-8-

Hardware version = 0701H; Software version = 0010H = 16 = V1.6
Note! If users only want to read the CO concentration or other registers, they only need to read the corresponding registers.

6.8 Host setting transmitter information (function code 06)

This device can currently set the baud rate (register address is 0005H), and the message

frame format is as follows:

Host request information frame

Transmitter response information frame

Field description Slave address Function code Register address high byte Register address low byte Set value high byte Set value low byte CRC check code low byte CRC check code high byte

Example 01 06 00 05 25 80 82 FB

Data parsing: Set the baud rate to 9600

Field description Slave address Function code
Register address high byte Register address low byte
Set value high byte Set value low byte CRC check code low byte CRC check code high byte

Example 01 06 00 05 25 80 82 FB

6.9 Abnormal response

When the host sends request information to the transmitter, various errors may occur. At this time, the transmitter sets the highest position of the function code to 1, and then returns an error code. The host can determine whether an error has occurred by detecting whether the highest bit of the function code is 1.
-9-

Slave address 1 byte

Function code 1 byte

Error code 1 byte

CRC check 2 byte

Error code
01: Illegal function code 02: Illegal data address 03: Illegal data value
6.10 CRC check code
RTU mode uses CRC-16 check, the check code occupies 2 bytes, if the check code is wrong, the transmitter will ignore the host's request and not respond. The calculation method of CRC-16 check code is as follows:  Preset a 16-bit register as hexadecimal FFFF, call this register CRC register;  XOR the first 8-bit binary data (the first byte of the information frame) with the lower 8 bits of the 16-bit CRC register, and place the result in the CRC register;  Shift the content of the CRC register one bit to the right (toward the low bit) and fill the highest bit with 0, check the right shift out position after shift;  If the shifted out bit is 0, repeat step  (shift one bit to the right again), if the shifted out bit is 1, the CRC register is XORed with the polynomial A001 (1010 0000 0000 0001);  Repeat steps  and  until the right shift is 8 times, so that the entire 8-bit data has been processed;  Repeat steps  to step  to process the next byte of the message frame;  After calculating all the bytes of the information frame according to the above steps, the content of the CRC register obtained is: 16-bit CRC check code.
- 10 -

7. Dimensions (unit: mm)
- 11 -


WPS 文字