GP Programmers & Timeswitches
102, 103 and 106 Models, for time control of Domestic Central Heating Systems.
INSTALLATION AND WIRING INSTRUCTIONS

SPECIFICATIONS

Power Supply

: 220/240Vac, 50/Hz

Switch Action

: 1 x SPST, Type 1B

Switch Rating

: 220/240Vac, 50/60Hz, 6(2)A.

Timing Accuracy

: ± 1 min./month

Enclosure Rating

: IP20

Pollution Situation

: Degree 2

Max. Ambient Temp. : 55°C

Designed to meet BS EN60730-2-7

Dimensions

: 112mm wide, 135mm high, 69mm deep

Rated Impulse voltage : 2.5kV

Ball Pressure Test

: 75°C

The unit must be installed by a competent electrician and the installation should conform to I.E.E. Regulations. This unit should be wired via full disconnect in accordance with BS EN60730-1, e.g. via a plug and unswitched
socket or double pole switch outlet with neon.

INSTALLATION INSTRUCTIONS
1. Loosen the fixing screw in the base of the unit to release the grey plastic Wiring Cover. Ensure the protective tape over the thumbwheel remains in place.
2. Holding the unit clockface downwards, press firmly in the centre of the wallplate and slide it from the module as shown.
3. Fix the Wallplate/Terminal Block to the wall with countersunk No.8 woodscrews or to a steel box to BS 4662. 1970 or a surface mounting steel or moulded box having centres of 23/8" (60.3mm).
4. Referring to the Wiring Diagrams overleaf, connect the unit as shown. Ensure that terminals 3 and 6 are linked where required (Mains Voltage applications) with insulated cable capable of carrying full load current.
5. Ensure all dust and debris have been cleared away from the area, then plug the module firmly into the wallplate ensuring that the hook at the top of the wallplate engages with the slot at the back of the body. Press the module down until it locates solidly.
6. Cut a cable aperture in theWiring Cover if necessary; replace theWiring Cover, and tighten the fixing screw.
7. Switch on Mains and test for correct operation as follows:
i) Remove protective tape from the pre-selector wheel. ii) Remove the dial cover and rotate the clock dial two complete
revolutions to clear the mechanism. ii) Check that all positions of the Selector Switch andTappets operate
correctly. (See instructions in User Booklet.)
8. Replace the dial cover. Finally leave the USER INSTRUCTIONS with the Householder.
9. If the unit is to be left turned off and is in a dusty atmosphere, protect the pre-selector wheel by re-affixing the protective tape.
IMPORTANT: Remove tape prior to putting unit into service.

This product complies with the following EC Directives: Electro-Magnetic Compatibility Directive. (EMC) (2004/108/EC) Low Voltage Directive. (LVD) (2006/95/EC)
Pre-Selector Wheel
Selector Switch
Plug-in Replacement Module Wallplate/Terminal Block
Wallplate/ Terminal Block
Plug-in Module

1

INTERNAL WIRING MODEL 102
W OFF
HW

INTERNAL WIRING MODEL 103
TIMED OFF
CONSTANT

1

2

3

Terminals

5

6

Water Heating Output Output
NOTE: Terminals 3 and 6 MUST be linked externally (except when voltage free switch contacts are required).

L N
Mains Supply

TYPICAL EXTERNAL CIRCUITS

102 Terminals

1

2

3

5

6

102 Terminals

1

2

3

5

6

1

2

3

Terminals

5

6

L N

Output

Mains Supply

NOTE: Terminals 3 and 6 should (in most instances) be linked externally. Exceptions are when control circuits are operating at low voltage (e.g. 24 volts) or for certain
Combination Type Boilers (see Boiler Manufacturers Handbook).

TYPICAL EXTERNAL CIRCUITS

103 Terminals

103 Terminals

1

2

3

5

6

1

2

3

5

6

Room Com Stat
N

Link

L

N
Mains Supply

Room Com Stat
N

Link

L

N

Mains Supply

Call

L

N

Pump

L

N Boiler

Call HP2 spring return
zone valve

C

Brown L

N

1

2

Motor Cylinder Stat L641A

Blue Grey

Orange

To Boiler & Pump L

N

1) Typical domestic gas or oil fired system with 2) Fully pumped system with cylinder stat in HW

gravity hot water and pumped heating. (If a circuit and room stat and 2 port spring return

room stat is not requires wire pump L directly to

zone valve in heating circuit.

terminal 2 on the 102).

Link

Com N
Call

Room Stat

L N

Mains Supply

Low voltage room stat

Load

L N
Mains Supply Low voltage supply

L N
Load Terminals
1) Control of Heating Function only (Mains Voltage)
Note: If room thermostat is not required join timeswitch terminals 1 and 2 with a
link suitable for full load current).

103 Terminals

1

2

3

5

6

2) Control of Low Voltage Systems (e.g. warm air gas valves, low voltage
burners).

103 Terminals

1

2

3

5

6

INTERNAL WIRING MODEL 106

Water Priority

OFF
Heating Priority

1

2

3

4

5

6

Terminals
Typical External Circuit

CALL SAT
COM Cylinder Stat
L

SAT CALL
COM Room Stat

N

L N
If Danfoss Randall HS3 valve is used connect valve brown and grey to terminal 2 of 106
To boiler & pump

Honeywell 'W' plan or Satchwell 'K' plan.

L N

Orange not connected (make safe)

Fully pumped system with 3 port (2 way) diverter valve.

Com N
Call

Link
Room Stat

L

N

Com

Mains

N

Supply

Room Call Stat

L N
Mains Supply

L N

L N

Input Output

N L

Boiler Terminals

Pump Terminals

Boiler Terminals

3) Typical gas or oil fired heating system with 4) Typical control of heating when used with

gravity hot water primary and pumped heating.

combination type boilers.

NOTE: Ease of installation can be achieved by using the Danfoss Randall Wiring Centre which is obtainable from most Builders Merchants and Distributors.
IF A WIRING CENTRE IS USED, follow the installation instructions included with the unit and not the wiring diagrams shown on this page.

Danfoss Randall can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss Randall reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.