Uni-COM® CB Modules

User Guide UAC-CB-01RS2, UAC-CB-01RS4, UAC-CB-01CAN

This guide provides basic installation information for Unitronics' Uni-COMTM CB Modules. Use them to add communication ports to specific models of the UniStream® family of Programmable Logic Controllers. Compatible models comprise a Uni-COMTM CB COM Module Jack which provides the connection point for the module. Refer to the specifications of your UniStream model to check whether it is compatible with CB modules. UAC-CB-01RS2 offers one RS232 port, UAC-CB-01RS4 offers one RS485 port, and UAC-CB-01CAN offers one CANbus port.
User Guides are available in Unitronics Technical Library at www.unitronicsplc.com.

Before You Begin
Before installing the device, the installer must:  Read and understand this document.  Verify the Kit Contents.

Alert Symbols and General Restrictions

When any of the following symbols appear, read the associated information carefully.

Symbol

Meaning

Description

Danger

The identified danger causes physical and property damage.

Warning

The identified danger could cause physical and property damage.

Caution

Caution

Use caution.

 All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples.
 Please dispose of this product according to local and national standards and regulations.  This product should be installed only by qualified personnel.

 Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
 Do not attempt to use this device with parameters that exceed permissible levels.  Do not connect/disconnect the device when power is on.

Environmental Considerations
 Ventilation: 10mm (0.4") of space is required between the device top/bottom edges and the enclosure's walls.  Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive
heat, regular impact shocks or excessive vibration, in accordance with the standards and limitations given in the product's technical specification sheet.  Do not place in water or let water leak onto the unit.  Do not allow debris to fall inside the unit during installation.  Install at maximum distance from high-voltage cables and power equipment.

UL Compliance

The following models: UAC-CB-01RS2, UAC-CB-01RS4, UAC-CB-01CAN are UL listed for Ordinary Location.

Kit Contents UAC-CB-01RS2  1 UAC-CB-01RS2 module

UAC-CB-01RS4
 1 UAC-CB-01RS4 module  1 RS485 terminal block

UAC-CB-01CAN  1 UAC-CB-01CAN module

Unitronics

1

UAC-CB-01RS2, UAC-CB-01RS4, UAC-CB-01CAN Installation Guide
Uni-COMTM CB Diagram

1

DIN-rail clips, Top and Bottom

2

COM Module Plug

(not shown)

3

Door

4

Communication Port

(not shown)

5

COM Module Jack and cover

6

Communication LEDs

7

DIP switches

These clips secure the module to the DIN-rail Plug this into the COM Module Jack located on a compatible device
Open door to allow easy access to LEDs and DIP switch The type of port depends upon the module
This is the connection point for additional modules; leave covered when not in use Green. Refer to the device's technical specifications Use these to set RS485/CANbus network termination

Installation

NOTE

 Turn off system power before connecting or disconnecting any module or device.  Use proper precautions to prevent Electro-Static Discharge (ESD).  The module is shipped with its COM module jack covered. To protect the jack from debris, damage, and ESD, you
must leave it covered when not in use.  The final module in a row must have its jack covered.
 UAC-CB modules can only be installed onto compatible devices, such as UniStream PLCs, or connected to other UAC-CB modules.

Installing UAC-CB Modules

NOTE

 Mount on a standard DIN-rail next to a compatible device.  Ensure there is sufficient space to install/uninstall modules.  In the first figure below, the module being installed is UAC-CB-01CAN; the second figure shows a UAC-CB-01RS2
being connected to the UAC-CB-01CAN.

Installing the first module onto the side of the controller:
1. Check the controller to verify that its COM module jack is not covered. If the Uni-COMTM CB module the last one in the configuration, leave the COM jack covered.
2. Push the module onto the DIN-rail until the clips located at the top and bottom of the unit have snapped onto the DIN-rail.
3. Slide the module as shown in the accompanying figure, until the COM module plug is firmly seat in the other devices' COM module jack.

Connecting additional modules onto the first:
1. Check the module that is already installed to verify that its COM jack is not covered. If the UAC-CB module is to be the last one in the configuration, do not remove the cover of its COM jack.
2. Insert the module's connection plug into the jack until it is firmly seated.

NOTE 2

If you mount vertically, place a DIN-rail stop or end clamp under the final module in the configuration. This is especially recommended if vibrations are present.
Unitronics

Removing a Module You must remove the end module in a row before removing the next one. 1. Turn off the system power. 2. Disconnect any wires or cables connected to the module. 3. Press the clips on the top and bottom of the modules, and carefully pull the module from its place.

Uni-COMTM CB

Wiring Caution

 All wiring activities should be performed while power is OFF.  Unused points should not be connected (unless otherwise specified). Ignoring this directive may damage the
device.  Double-check all wiring before turning on the power supply.
 To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm).  Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to break.  Install at maximum distance from high-voltage cables and power equipment.

Wiring Guidelines In order to ensure that the device will operate properly and to avoid electromagnetic interference:  Use a metal cabinet. Make sure the cabinet and its doors are properly earthed.  Use shielded cables.

NOTE

For detailed information on avoiding EMI, refer to the document System Wiring Guidelines, located in the Technical Library in the Unitronics' website.

UAC-CB-01RS2 - RS232 module

 Use shielded cable

Pin Number 1 2 3 4 5 6 (see note) 7 (see note) 8, 9

Pin Name RXD TXD SG -

Direction In Out Return -

NOTE

Pins 6 and 7 are not connected to internal circuits.

Description Not connected Receive Data Transmit Data Not connected Signal Ground Connected to Pin 7 Connected to Pin 6 Not connected

UAC-CB-01RS4 ­ RS485 module
Wiring Procedures Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm2 ­3.31 mm2). 1. Strip the wire to a length of 7±0.5mm (0.275±0.020 inches). 2. Unscrew the terminal to its widest position before inserting a wire. 3. Insert the wire completely into the terminal to ensure a proper connection. 4. Tighten enough to keep the wire from pulling free.
Use the RS485 port to create a multi-drop network.
The UAC-CB-01RS4 is shipped with a 4 pin RS485 terminal block. This connector is marked with a pin assignment that is identical to the corresponding marking on the module.

Unitronics

3

UAC-CB-01RS2, UAC-CB-01RS4, UAC-CB-01CAN Installation Guide

RS485 Wiring

D+

Tx/Rx+ (B)

D-

Tx/Rx­ (A)

SG

Signal Ground

Functional Ground  Use shielded twisted-pair cable in compliance with EIA RS485 specifications.  When wiring each node, connect the cable shield to the functional ground point of the RS485 terminal block.

Caution

In order to avoid ground-loops, do not connect the RS485 functional ground terminal to the earth of the system, as it is internally connected to the controller's functional ground point.

RS485 Termination
Use the DIP switches shown in the diagram on page 2 to set the RS485 termination according to this table. The device is shipped with both its DIP switches set to ON; change settings if the device is not at one of the ends of the RS485 network.

Position

1

2

ON

ON

OFF

OFF

DIP Switch State
Terminated (factory default) Not Terminated

UAC-CB-01CAN - CANbus module
There are two RJ45 connectors on the top of this module. Connect one connector to your CANbus network. The other connector may be used to daisy-chain to another device.

CANbus Wiring
 Use CAT-5e shielded cable with RJ45 connector.  When wiring each node, connect the cable shield
to the shield of the RJ45 connector.
 Connect the CANbus cable shield to the system earth at only one point near the power supply.

Pin # shield
1 2 3
4 5 6 7 8

Description Functional Ground
H CAN High L CAN Low -V CANbus
Signal Common
Not connected Not connected Not connected Not connected Not connected

CANbus Termination
Use the DIP switches shown in the diagram on page 2 to set the CANbus termination according to this table. The device is shipped with both its DIP switches set to ON; change settings if the device is not at one of the ends of the CANbus network.

Position

1

2

ON

ON

OFF

OFF

DIP Switch State
Terminated (factory default) Not Terminated

4

Unitronics

Uni-COMTM CB

Technical Specifications

Communication

UAC-CB-01RS2 (RS232 module)

Number of ports

1

Voltage limits (receiver)

±20 VDC maximum, relative to Signal Ground (SG) pin

Baud rate range Isolation voltage Connector type Cable type Cable length Indicator LEDs
Tx: Rx:

1,200 ­ 115,200 bps 500VAC for 1 minute D-Sub 9 pin, male Shielded Maximum 15 m (50 ft)
Green: Blinking when data is Transmitted Green: Blinking when data is Received

UAC-CB-01RS4 (RS485 module)

Voltage limits Baud rate range Nodes Isolation voltage Cable type Cable length Indicator LEDs
Tx: Rx: Termination

-7 to +12 VDC maximum, Common+Differential 1,200 ­ 115,200 bps Up to 32 500VAC for 1 minute Shielded twisted pair, in compliance with EIA RS485 Maximum 1,200 m (4,000 ft)
Green: Blinking when data is Transmitted Green: Blinking when data is Received Set using DIP Switches

UAC-CB-01CAN (CANbus module)

Power requirement Isolation voltage Cable type Indicator LED
Tx/Rx

None. The CANbus port is internally powered. 500VAC for 1 minute DeviceNet® or CAT-5e shielded twisted pair
Green: Blinking when data is Transmitted/Received

Baud rate and maximum trunk line length

Baud rate (bps)

DeviceNet ®

DeviceNet ®

DeviceNet ®

1M 500k 250k 125k, 100k 50k, 20k,10k
Maximum drop line (stub) length

Thick cable

Mid cable

Thin cable or CAT-5e

cable

25m (82 ft)

25m (82 ft)

10m (32 ft)

100m (328 ft)

100m (328 ft)

100m (328 ft)

250m (820 ft)

250m (820 ft)

100m (328 ft)

500m (1,640 ft)

300m (984 ft)

100m (328 ft)

1,000m (3,280 ft)

300m (984 ft)

100m (328 ft)

The maximum cable distance from any device on a branching drop line to the trunk line is 2 m (6.5 ft) with any cable thickness.

Maximum cumulative drop line (stub) length per baud rate

Baud rate (bps)
1M 500k 250k 125k, 100k 50k, 20k,10k Nodes Termination

Cumulative drop line length
5m (16 ft) 25m (32 ft) 60m (197 ft) 100m (328 ft) 100m (328 ft) Up to 64 Set using DIP Switches

Unitronics

5

UAC-CB-01RS2, UAC-CB-01RS4, UAC-CB-01CAN Installation Guide

Environmental Ingress Protection Operational temperature Storage temperature Relative Humidity (RH) Shock Vibration Dimensions Weight
Size

IP20, NEMA 1 -20°C to 55°C (-4°F to 131°F) -30°C to 70°C (-22°F to 158°F) 5% to 95% (non-condensing) IEC 60068-2-27, 15G, 11ms duration IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration.

UAC-CB-01RS2 100 g (0.22 lb) As shown in the images below

UAC-CB-01RS4 89 g (0.19 lb)

UAC-CB-01CAN 105 g (0.23 lb)

UAC-CB-01RS2

6

Unitronics

UAC-CB-01RS4

Uni-COMTM CB

Unitronics

7

UAC-CB-01RS2, UAC-CB-01RS4, UAC-CB-01CAN Installation Guide
UAC-CB-01CAN

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them

10/23

8

Unitronics



References

Microsoft Word for Microsoft 365