Instruction Manual for LENNOX models including: 23V24 Low Ambient Kit, 23V24, Low Ambient Kit, Ambient Kit, Kit

PDF preview unavailable. Download the PDF instead.

507914-03
©2023

PACKAGED UNITS - KITS

507914-03 10/2023 Supersedes 507914-02

LOW AMBIENT KIT

INSTALLATION INSTRUCTIONS FOR LOW AMBIENT KIT (23V24; 619589-08) USED ON KGC/KCC 180, 210 PACKAGED ROOFTOP UNITS

Shipping and Packing List
Package 1 of 1 contains:
1- Head pressure control (A190) 1- Temperature switch bracket 1- Wiring harness - A190 24V power 1- Wiring harness - A190 to K254 1- Bag assembly containing:
1-Pressure transducer (A188) 1-Temperature switch (S201) 10-Wire ties 1-Wiring diagram 2-Screws, #8-32 X 1/2 TFS 2-Screws, #8-32 X 1-1/4 TFS
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Application
This kit allows low ambient operation to 0°F (-17.8°C) unless otherwise noted in product specifications.
Operation
When ambient temperature drops below 55°F (adjustable), S201 temperature switch opens to de-energize K10 relay coil. Condenser fans 1 & 2 are de-energized. Liquid line pressure transducer A188 converts the pressure to an analog signal which is sent to the head pressure control (A190). The head pressure control provides a variable output which slows Condenser Fan 3 operation at lower ambient temperatures (A190 terminal M to B21 terminal 3). .

WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
Installation
1 - Disconnect all power to unit and open access panels. 2 - Install the head pressure control (A190) in the
control 3 - Install the temperature switch mounting bracket
onto the mullion. Align the bracket with the 4th screw from the top of the unit; secure with provided screw. See figure 1. 4 - Install the temperature switch onto the bracket. 5 - Using the ICM Omni App, set the head pressure controller as follows:
Probe Type: Pressure Setpoint: 355 psig Hard Start: 0.1s Minimum Voltage Output: 32% 6 - Set heat pump jumper to "CONTROL INPUT". 7 - Install the pressure transducer on compressor 2. liquid line pressure tap as shown in figure 2.
WARNING
To prevent serious injury or death: 1- Lock-out/tag-out before performing maintenance. 2- If system power is required (e.g., smoke detector
maintenance), disable power to blower, remove fan belt where applicable, and ensure all controllers and thermostats are set to the "OFF" position before performing maintenance. 3- Always keep hands, hair, clothing, jewelry, tools, etc., away from moving parts.

Page 1

A190 HEAD PRESSURE
CONTROL

HEAD PRESSURE CONTROL AND TEMPERATURE SWITCH LOCATION

K254 RELAY

TEMPERATURE SWITCH BRACKET

OUTDOOR SECTION
COMPRESSOR SECTION
4TH SCREW FROM THE
TOP

FIGURE 1

LIQUID LINE PRESSURE TAP LOCATION
LIQUID LINE PRESSURE TAP COMPRESSOR 2

DIVISION PANEL

FIGURE 2 Page 2

ROUTE TEMPERATURE SENSOR WIRES
THROUGH HOLE IN
DIVISION PANEL

TEMPERATURE SWITCH WIRING

DISCONNECT

WIRES

K10

MARKED S201

FIGURE 3

Temperature Switch Wire Connections
1 - Route temperature switch wires through the division panel between the compressor and outdoor coil sections. See figure 2.
2 - Disconnect male and female terminals from wires marked "S201" near K10 relay. See figure 3.
3 - Make wiring connections as shown in figure 4.
TEMPERATURE SWITCH WIRING
DISCONNECT UNIT WIRES MARKED S201

S201

S201

AB K10

S201

CONNECT WIRES FROM TEMPERATURE
SWITCH
S201 TEMPERATURE
SWITCH
FIGURE 4

Low Voltage Wire Connections
Use the 24V harness, provided in this kit, to make transducer wire connections as shown in figure 5.
High Voltage Wire Connections
1 - Disconnect factory wires to K254 terminals 4 & 6. Reconnect these wires to the kit harness as shown in figure 6.
2 - Check the voltage to the unit. Connect the harness wire labeled "A190-L1" to the Line 1 / Motor 1 120 600 VAC terminal.
3 - Make the rest of the K254 harness connections as shown in figure 6. Refer to the diagram in figure 7.
4 - Make sure all connections are secure. 5 - Bundle wiring and use wire ties to route wiring away
from sharp edges. 6 - Place the wiring diagram provided in this kit on the
inside of the control door. 7 - Close unit panels and restore power.

Page 3

A190-24V-2 A190-24V-1
BLACK RED BLACK RED STG 1 GREEN

A190 HEAD PRESSURE CONTROL

24V HARNESS WIRING

A188 STG 2 PRESSURE TRANSDUCER

STG 1 GREEN

TB1-C

TB1-R

FIGURE 5

Page 4

Kit Harness

120 - 600 VAC Line 1 / Motor 1

Line 2 Motor 2

A190 HEAD PRESSURE
CONTROL

K254 HARNESS WIRING

Disconnect factory wire labeled "K254-4"

K254-4-A1 K254-6-A1

K254 LOW AMBIENT
RELAY

Disconnect factory wire labeled "K254-6"

K254-6-A2 K254-6
Was connected to K254-6 relay

K254-4-A2 K254-4
Was connected to K254-4 relay

FIGURE 6

OUTDOOR FAN MOTOR 21

Page 5

24V POWER
24V COMMON TB13

A190 GND 24V +5V

COM

T2/P2 T1/P1

BLK RED

B,W,G

A188

7 K66-1
4

10 X 8 INCHES
R 24V POWER
TB1

S50
P35 6 J35
S7

S49
P35 10 J35 S4

S201

P35

4 J35

3

A

A

A

A

K10 K2 K1 K254

B

B

B

B

TB1 C F10

24V COMMON

K1-1

L1 L2 L3

L1 L2 L3

L1 L2 L3

K2-2 K14-1

K2-1

T1 T2 T3 C

T1 T2 T3 C

T1 T2 T3 C

K14-2

K1-2

NC B1
HR1

NC B2
HR2

NC B13
HR5

K10-1 K10-2

7

9

4

6

P36 J36 1 1 C1

2 1 C2

2

2

J86 1 P86

2

P86 3 J86 4

5

6

32 1 B4

32 1 B5

79

K254

A190 L2 L1 M

46

P36 J36 3 1 C18

2
J86 7 8 9 P86

32 1 B21

KEY A188 A190 B1 B2 B4 B5 B13 B21 C1 C2 C18 J/P 35 J/P 36 HR1 HR2 HR5 K1,-1,2 K2,-1,2 K10,-1, 2 K14,-1,2 K66,-1 K254

COMPONENT PRESSURE TRANDUCER, COMP 2 PRESSURE CONTROLLER, COMP 2, LOW AMBIENT KIT
COMPRESSOR 1 COMPRESSOR 2 MOTOR, OUTDOOR FAN 1 MOTOR, OUTDOOR FAN 2 COMPRESSOR 3 MOTOR, OUTDOOR FAN 3 CAPACITOR, OUTDOOR FAN 1 CAPACITOR, OUTDOOR FAN 2 CAPACITOR, OUTDOOR FAN 3 JACK/ PLUG, RUN TEST JACK/ PLUG, RUN TEST OD FANS HEATER, COMPRESSOR 1 HEATER, COMPRESSOR 2 HEATER, COMPRESSOR 3 CONTACTOR, COMPRESSOR 1 CONTACTOR, COMPRESSOR 2 RELAY, OUTDOOR FANS 1, 2 CONTACTOR, COMPRESSOR 3 RELAY, STAGE COOL 1 RELAY, LOW AMBIENT KIT FAN 3

S4 S7 S49 S50 S201 TB1 TB13

SWITCH, LIMIT HI PRESS COMP 1 SWITCH, LIMIT HI PRESS COMP 2 SWITCH, FREEZESTAT COMP 1 SWITCH, FREEZESTAT COMP 2 SWITCH, LOW AMBIENT TEMP SENSOR 1 TERMINAL STRIP, 24V TERMINAL STRIP, POWER DISTRIBUTION

WARNING-ELECTRIC SHOCK HAZARD CAN CAUSE INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES
FOR USE WITH COPPER CONDUCTORS ONLY
DISCONNECT ALL POWER BEFORE SERVICING
IF ANY WIRE IN THIS APPLIANCE IS REPLACED, IT MUST BE REPLACED WITH WIRE OF LIKE SIZE, RATING, INSULATION THICKNESS AND TERMINATION

REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION
F10 USED ON Y-VOLT UNITS ONLY
REFER TO INSTRUCTION SHEETS FOR LOW AMBIENT HARNESS INSTALLATION PROCEDURE

DENOTES OPTIONAL COMPONENTS LIVE VOLTAGE FIELD INSTALLED

WIRING DIAGRAM

10/23

FIGURE 7

COOLING - MSAV
KG/KC C-BOX - 180S, 210S - G, J, Y VOLT LOW AMBIENT KIT

Supersedes
538040-01
C

SECTION B

REV. 2

New Form No.
538040-02

Lennox Commercial

Page 6


Adobe PDF Library 17.0 Adobe InDesign 19.0 (Windows)