Instruction Manual for BEKA models including: BA377E-SS Timer or Clocks, BA377E-SS, Timer or Clocks, Clocks

BA377E

Abbreviated Instruction manuals


File Info : application/pdf, 2 Pages, 773.53KB

PDF preview unavailable. Download the PDF instead.

ba377e short form
1. DESCRIPTION The BA377E is an intrinsically safe, panel mounting instrument with a single input that can be configured as a Timer or as a Clock. As a Timer the BA377E is able to measure and display the elapsed time between external events, or control external events via two optional factory fitted control outputs. When configured as a Clock the BA377E displays local time and the optional control outputs can turn on and off twice in each twenty four hour period. This abbreviated instruction sheet is intended to assist with installation, a comprehensive instruction manual describing safety certification, system design and configuration may be downloaded from the BEKA website or may be requested from the BEKA sales office. The BA377E has IECEx, ATEX and UKEX intrinsic safety certification for use in flammable gas atmospheres. ETL and cETL approval permits installation in the USA and Canada. The certification information label, which is located on the top of the instrument enclosure, shows the certification number and codes. Other certifications may be shown. Copies of certificates may be down loaded from the BEKA website.
Typical certification information label Special conditions for safe use The IECEx, ATEX and UKEX certificates have an `X' suffix indicating that special conditions apply for safe use.
WARNING To avoid an electrostatic charge being generated instrument
enclosure should only be cleaned with a damp cloth.
2. INSTALLATION The BA377E has IP66 front of panel protection but it should be shielded from direct sunlight and severe weather conditions. The rear of the instrument has IP20 protection.

Cut-out dimensions Recommended for all installations. Mandatory to achieve IP66 seal between instrument and panel.
90 +0.5/-0.0 x 43.5 +0.5/-0.0

65

7.5

96
DISPLAY

48

Optional

A1 A2
+ Control output 1

A3 A4
+ Control output 2

12
+ Power supply 10 to 28V dc

RS1 RS2 3 4 5 6
+ Reset Add link Sensor
to energise input sensor input

Support panel wiring to prevent vibration damage Fig 1 Cut-out dimensions and terminals

Abbreviated instructions for
BA377E One input Intrinsically safe Timer or Clock

BA377E

HRS RTx

MINS

SECS

Issue 4 24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: sales@beka.co.uk
web: www.beka.co.uk

1. Align foot and body of panel mounting clamp by turning screw anticlockwise

2. Position gasket behind instrument bezel
3. Insert instrument into the panel from the front

4. Insert panel clamp into recess and gently pull it onto the dovetail. Engage screw & turn clockwise to tighten the clamp, fit the other clamp(s). Recommended tightening torque 22cNm (1.95lbf.in) Equivalent to finger tight plus one half turn. DO NOT OVERTIGHTEN

Fig 2 Installation procedure
EMC For specified immunity all wiring should be in screened twisted pairs with screens earthed at one point within the safe area.

Hazardous area

Safe area

DISPLAY

RS2 RS1

6543 +

21

+

+

Sensor

The input must be maintained not momentary

Remote reset in hazardous
area

Sensor output
Proximity detector Switch Contact Open collector

Input
Link 3 & 4

Voltage

Don't link 3 & 4

Single channel positive polarity 28V: 93mA Zener barrier
+ Power supply
Remote reset in safe area
Single channel positive polarity 28V: 93mA Zener barrier

Fig 3 Use with Zener barriers
Scale card The Timer or Clock's units of measurement are shown on a printed scale card visible through a window at the right hand side of the display. The scale card is mounted on a flexible strip that is inserted into a slot at the rear of the instrument as shown below

Unlock

Insert Lock

Fig 4

Inserting flexible strip carrying scale card into slot at the rear of Timer or Clock.

Thus the scale card can easily be changed without removing the Timer or Clock from the panel or opening the instrument enclosure.

New Timer or Clocks are supplied with a printed scale card showing the requested units of measurement, if this information is not supplied when the Timer or Clock is ordered a blank card will be fitted. A pack of self-adhesive scale cards printed with common units of measurement is available as an accessory from BEKA associates. Custom printed scale cards can also be supplied.

To change a scale card, unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of the enclosure. Peel the existing scale card from the flexible strip and replace it with a new printed card, which should be aligned as shown below. Do not fit a new scale card on top of an existing card.

Align on these edges

Scale card

Align the self-adhesive printed scale card onto the flexible strip and insert the strip into the Timer or Clock as shown.

Fig 5 Fitting scale card to flexible strip

3. OPERATION
The Timer or Clock is controlled by four front panel push buttons. When configured as a Timer they have the following functions in the operating mode:

( + ) Access to configuration menu.

&

When local control is enabled starts the Timer

*

When local control is enabled stops the Timer.

) + *

Shows the grand total (run time) in hours and tenths of an hour irrespective of Timer configuration. If buttons are held for longer than ten seconds the grand total may be reset to zero if the grand total reset sub-function clr gtot is enabled in the LoC r5Et configuration function.

To reset the grand total to zero from the display mode press the ) + * buttons for ten seconds until CLr. no is displayed, using the & or * button change the display to CLr. YE5 and press ).

& + *

Resets the Timer to zero or to the set time 5Et t
depending on whether the Timer is configured to timeup or time-down when the two buttons are operated simultaneously for more than three seconds. This is a configurable function.

( + *

When enabled in the configuration menu, operating these two buttons simultaneously provides direct access to the set time 5Et t and allows adjustment when the timer is in the display mode.

( + &

Shows in succession, firmware version number, instrument function elap5e and any output accessories that are fitted:
- A Dual Control Outputs

See full instruction manual for description of use when configured as a Clock

Display mode

DISPLAY

( )

)

code

(

0000

Security Code
Enter code by pressing
* or & & (
to move to next digit. Code 0000
allows direct access to the menu

4. CONFIGURATION Timer or Clocks are supplied configured as requested at time of ordering, if not specified default Timer configuration will be supplied but can easily be changed on-site.
Fig 6 shows the location of each function within the Timer configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information, description of optional outputs and Clock configuration menu.
Access to the configuration menu is obtained by pressing the ( and ) buttons simultaneously. If the Timer or Clock's security code is set to default 0000 the first parameter function will be displayed. If the instrument is protected by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.
Only included when optional Control Outputs are fitted

()

)

)

)

)

)

)

)

)

)

)

)

& function

* &

input

*

&

di5p-2

* &

5tart5top

* &

unit5

* &

5et t

* &

cycle5

* &

ac5et t

*

&

up or dn

* &

p-fail

* &

loc r5et

*

& op1

()

()

)

()

()

()

()

(

()

)

()

()

()

)

(

elap5e

inp.type

* &

debounce

5td

local

12 : 00 : 00

00 : 00 : 00

enbl

* &

accd

dn

idle

r5etenbl

* &

clr gtot

()

()

()

()

()

()

()

)

)

)

)

* &

op2

* &

clr gtot

* &

code

* &

r5et def

*

()

()

()

()

As op1

clr. no

0000

0000

()

0000

op.col

default

off

0000

off

off

0000

Function

Input

* or &
to select

* or &
to select

Function of instrument
elap5e Interval measurement
cloc Time display
Confirm selection by entering 5ure
by pressing
* or & and ( to move
to next digit

Input type
op.col Open Collector
volt5 l Voltage <1V >3V
volt5 h Voltage <3V >10V
coil 0 < >40mV
pr.det Proximity detector
contact Switch contact

Debounce
* or &
to select
level of debounce.
default light heavy

Lower Display
cycle5 not enabled
* or &
to select display

Start & stop timer
* or &
to select how timer is
controlled

5td Set time 5et t
off lower display disabled ___________
cycle5 enabled
* or &
to select display
5td Cycle No. & total cycle with status shown at start of each operation

local Start & button Stop * button
control 1 Start Input high (open) Stop Input low (closed)
control 2 Start Input low (closed) Stop Input high (open)

label
Cycle No. & total cycle with status shown periodically

off
lower display disabled

hours minutes seconds

Units of display
* or &
to select
12 : 00 : 00 12:00
30 : 00 30

Set time
* or &
to adjust value and
(
to move control to next digit

Enable access to Set Time from display mode

Security code for direct access to Set Time

* or &
to select on or off

Enter code by pressing
* or &
and (
to move to next digit

Code 0000 allows direct
access

Direction of count
* or &
to select up or dn

)

)

)

&

enbl

* &

cycl cnt

* &

r5t dela

*

()

()

()

off

00

00 : 00 : 00 : 00

Enable cycle function
* and &
to toggle between on and off

Cycle count
* and &
to adjust flashing digit
and (
to move to next digit.

Restart delay
* and &
to adjust flashing digit
and (
to move to next digit.

The BA377E is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).

Sets number of cycles between 1 and 99 to be performed.

Sets delay between cycles in the same units
as 5et t

00 for continuous
cycling

Manuals, certificates and datasheets can be downloaded from http://www.beka.co.uk/ba377e

Timer repeat cycle function

Power fail
* or &
to select how timer functions when power is restored after
failure

Local total reset
* or &
to turn the local total reset function on or off

Local grand total clear
* or &
to turn the local grand total reset function
on or off

idle Stopped, requires reset & start input
pau5e Paused, requires start input
continue Resumes timing

When on is selected pressing
* and &
simultaneously for more than 3 seconds in the display mode
resets the total display

When on is selected pressing
) and *
simultaneously for more than 10 seconds in the display mode
resets the grand total

Clear grand total

Define

Reset

Security Code configuration to

press

Timer factory

* or &
to select ye5 to reset grand total to zero.
Confirm instruction by

Enter by pressing
& or * and
( to move to
next digit

defaults
Confirm instruction by entering 5ure.
Press
& or *

entering 5ure.

to adjust each

Press

digit and (

& or *
to adjust each

to move to next digit

digit and (

to move to

next digit

)

)

)

)

&

enbl

* &

op1 on

* &

op1 off

* &

op1 dela

*

()

()

()

()

off

5tart

5top

00000

Enable output 1
* and &
to toggle between on and off

Output on at Output off at Output on delay

* and & * and & * and &

to select

to select

to adjust

required function required function flashing digit

re5et run pau5e

re5et run pau5e

and (
to move to next digit

delay done n re5et n run n pau5e

delay done n re5et n run n pau5e

Set delay in seconds before
output 1 is energised.

n delay

n delay

n done

n done

Select action Select action

that energises that de-energises

output 1

output 1

Fig 6 Timer Configuration menu

Output 1 configuration



References