INSTRUCTIONS
RPLEDTM FIELD-ADJUSTABLE RETROFIT PANEL INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

1x4

2x2

2x4

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside. WARNING: Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of LED retrofit kit. Check for enclosed wiring and components. WARNING - Risk of fire or electric shock. Install this kit only in luminaires that have the construction features and dimensions shown in the photographs and/or drawings .
WARNING - To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects. WARNING ­ Risk of fire or electric shock. LED Retrofit Kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
Only those open holes indicated in the drawings may be made or altered as a result of kit installation. Do not leave any other open holes in an enclosure of wiring or electrical components.
Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
This retrofit kit is accepted as a component of a luminaire where the suitability of the combination shall be determined by authorities having jurisdiction.
Suitable for damp locations. Class 1 Wiring. Suitable for operation in ambient not exceeding 40°C.

RECESSED CEILING MOUNTING
The fixture is suitable only for INDOOR RECESSED CEILING application in an existing luminaire with insulated or non-insulated ceiling. Follow the steps below.
1. Remove existing lamps, door/lens frame (if applicable), reflector and cover. Depending on clearance space, ballast may need to be removed.
2. Gently lift original luminare housing and insert the two Side Brackets between the housing and T-Grid (Fig. 1). Side Brackets should be sitting on the top edge of the T-Grid. Using Self-tapping Screws (provided) as shown in Fig. 3, use a power screwdriver to secure Side Brackets into place through bracket mounting holes from inside of the fixture.
Caution: Luminaire wiring and electrical parts may be damaged when drilling for installation of LED retrofit kit. Ensure that enclosed wiring and components have not been damaged.
3. Insert the two Side Rails (filler strips) into the spaces between the Side Brackets and the T-Grid (Fig. 2).
4. Insert the panel Pivot Pins into the Bracket Slots (Fig. 4). Slide the panel to the end of the Bracket Slots to secure panel in place (Fig. 3 and 4)).
6. Make electrical connections as shown in wiring diagram (Fig. 7). Use approved wiring connectors and appropriate wiring method and wire to local NEC codes. Be careful not to pinch the wires.
7. Attach the Tether Cables with Screws provided (Fig. 4).
8. Raise fixture Panel to close with Latches to the End Bracket as shown in Fig. 5.

INSTRUCTIONS
RPLEDTM FIELD-ADJUSTABLE RETROFIT PANEL INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

Fig: 1

T-Grid

Fig: 4

Pivot Pin

Side Brackets Fig: 2

Tether Cable Fig: 5

Side Rails (filler strips)
Fig: 3

Bracket Slot Latches

Self-tapping Screws (4) Bracket Slot

INSTRUCTIONS
RPLEDTM FIELD-ADJUSTABLE RETROFIT PANEL INSTALLATION

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

FIELD ADJUSTMENT

Fig: 6

Follow instructions below to change the Fixture Power (W) and/ or Color Temperature (CCT) from factory settings:
Factory Settings: RPLED1X4 30W / 4000K RPLED2X2 30W / 4000K RPLED2X4 35W / 4000K

1. Locate the Field Adjustable Switches located on the back of the of Fixture Housing as shown in Fig. 6.
2. Select Power (W) and/or Color Temperature (CCT) by sliding respective switch to the desired value.

CCT Switch

Power (W) Switch

MVS MODELS (Internal)

(optional remote sold separately for custom settings, CAT# MSR1).

Factory Settings:
· Brightness: 100% · Hold Time: 20 Minute · Daylight: Disabled

· Motion Sensitivity: High · Stand-by dimming level: 20% · Stand-by time: 1 Minute

Ceiling Mounted

0.5-1.0M/S
3.2

6.5

Mounting

Height

9.8

13.1

16.4 16.4 13.1 9.8 6.5 3.2 0 3.2 6.5 9.8 13.1 16.4

Highest mounting height is 13.1ft
This figure indicates the maximum distance at the highest mounting height with 100% sensitivity.

Well Detected Area

Possibly Detected Area

INSTRUCTIONS
RPLEDTM FIELD-ADJUSTABLE RETROFIT PANEL INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. 0-10V control wires must be rated for 300V minimum. For 0-10V dimming, follow the wiring directions shown below (Fig. 7).
1. Connect the black fixture lead to the LINE supply lead.
2. Connect the white fixture lead to the COMMON supply lead.
3. Connect the GROUND wire from fixture to supply ground. Do NOT connect the GROUND of the dimming fixture to the output.
4. Connect the purple fixture lead to the (V+) DIM lead.
5. Connect the pink fixture lead to the (V-) DIM lead.

Fig: 7
LINE COMMON ( + ) DIM V ( - ) DIM V
GROUND

BLACK
WHITE PURPLE PINK Vaux 12V YELLOW
GROUND

LIGHT FIXTURE

TROUBLESHOOTING
1. Check that the line voltage at fixture is correct. Refer to wiring directions.
2. Be sure the fixture is grounded properly. 3. If the Lightcloud Blue-enabled fixture does not connect
follow steps to enable device pairing mode and try to pair again.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized. 1. Clean polycarbonate lens & fixture with non-abrasive
cleaning solution. 2. Do not open fixture to clean the LEDs. Do not touch the
LEDs.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

INSTRUCTIONS
RPLEDTM FIELD-ADJUSTABLE RETROFIT PANEL INSTALLATION

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

BATTERY BACKUP MODELS

WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY. To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join BATTERY connector until installation is complete and AC power is supplied to the emergency driver (Fig. 8). NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver. CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.

OPERATION
1. When AC power is applied, the charging indicator light is illuminated, indicating that the BATTERY is being charged.
2. When power fails, the standby power automatically switches to emergency power (internal battery), operating at reduced illumination. The emergency driver supplies standby power for a minimum of 90 minutes.
3. When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE

1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
2. If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
3. If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external.
4. Connect the pink fixture lead to the (V-) DIM lead.
5. For 0-10V Dimming, connect DIM (+) and DIM (-) to the supply ground. Do not connect GROUND to the output leads.
6. All unused leads must be capped and insulated.
7. After installation is complete, supply AC power to the fixture and connect the BATTERY.
8. When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
9. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button ( Fig. 9) After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.

Fig: 8

Purple/DIM+

INSIDE FIXTURE

LIGHT FIXTURE

Pink/DIM­
Black/Switched Line Black/Unswitched Line

BACKUP DRIVER

BATTERY CONNECTOR: CONNECT ONLY AFTER AC SUPPLY POWER IS CONNECTED

White/Neutral Green/Ground

BATTERY

Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended: 1. Visually inspect the charging indicator light monthly. It should
be illuminated. 2. Test the emergency operation of the fixture at 30-day intervals
for a minimum of 30 seconds. 3. Conduct a 90-minute discharge test once a year. Fixture would
operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
1. Is the fixture grounded properly? 2. If the charging indicator light does not illuminate after pressing
the Test Button, check if battery is connected properly.
Fig: 9
Battery Test Button

© 2024 RAB LIGHTING Inc.
RPLED-0624 P-100922

Easy Answers
rablighting.com Visit our website for product info