Overview
The Danfoss ICAD 600 and ICAD 900 are advanced actuators designed for precise control of ICM valves. This document provides comprehensive instructions for their installation, electrical connection, mechanical mounting, and general operation.
Compatibility
ICAD 600 and ICAD 900 actuators can be used with the following Danfoss ICM valves:
ICAD 600 | ICAD 900 |
---|---|
ICM 20 | ICM 40 |
ICM 25 | ICM 50 |
ICM 32 | ICM 65 |
Installation
Electrical Data
The supply voltage is galvanically isolated from the in-/output signals.
Parameter | Value | Notes |
---|---|---|
Supply voltage | 24 V d.c., +10% / -15% | |
Load (ICAD 600) | 1.2 A | |
Load (ICAD 900) | 2.0 A | |
Fail safe supply | Min. 19 V d.c. | Load: 1.2 A (ICAD 600) / 2.0 A (ICAD 900) |
Analog input (Current) | 0/4 - 20 mA | Load: 200 Ω |
Analog input (Voltage) | 0/2 - 10 V d.c. | Load: 10 kΩ |
Analog output | 0/4 - 20 mA | Load: ≤ 250 Ω |
Digital input | Voltfree contact (Signal/Telecom relays with gold-plated contacts recommended) | ON: contact impedance < 50 Ω, OFF: contact impedance > 100 kΩ |
Digital output | 3 pcs. NPN transistor output | External supply: 5 - 24 V d.c. Output load: Max. 50 mA. Note: Using the same supply as ICAD may spoil the galvanic isolation. |
Temperature range (ambient) | -30°C / +50°C (-22°F / 122°F) | |
Enclosure | IP 65 (~NEMA 4) |
Cable Connection
Two 1.8 m (70.7 in.) cables are premounted.
Supply Cable (3 x 0.34 mm² / ~22 AWG)
- I: White (+) 19 - 24 V d.c. fail safe supply (optional).
- II: Brown (+) 24 V d.c.
- III: Green (-) 24 V d.c.
Control Cable (7 x 0.25 mm² / ~24 AWG)
- A: White (-) Digital output. Common Alarm.
- B: Brown (-) Digital output. ICM fully open.
- C: Green (-) Digital output. ICM fully closed.
- D: Yellow (-) GND - Ground.
- E: Grey (+) Analog input 0/4-20 mA.
- F: Pink (+) Analog input 0/2-10 V / Digital ON/OFF input.
- G: Blue (+) Analog output 0/4-20 mA.
Electrical Installation
General procedure for ICAD 600/900 installed on all ICM valves. Ensure all necessary electrical connections are made for analog or digital operation.
Analog Operation
Uses a 7-wired cable (A-G) for modulation control. The ICM valve is controlled by Danfoss electronics (e.g., EKC) or third-party electronics (e.g., PLC).
- Connect analog input signals (Current or Voltage). Refer to the Parameter list for configuration.
- Grey (+) and Yellow (GND) are used for current (mA) input.
- Pink (+) and Yellow (GND) are used for Voltage (V) input.
- Blue (+) and Yellow (GND) are used for current (mA) output (optional).
Digital Operation
Uses a 7-wired cable (A-G) for ON/OFF ICM solenoid valve operation, controlled by a digital voltfree contact.
- Connect digital input signals. Pink (+) and Yellow (GND) are connected to a voltfree contact.
- Digital output signals are optional.
- White (-) and Yellow (GND) are connected to an auxiliary relay for Common Alarm.
- Brown (-) and Yellow (GND) are connected to an auxiliary relay indicating ICM fully open.
- Green (-) and Yellow (GND) are connected to an auxiliary relay indicating ICM fully closed.
Supply Voltage
The ICAD requires a normal 24 V d.c. supply. An optional fail safe supply (battery or UPS) can be used. When voltage is applied, the ICAD is ready for configuration.
- Connect the Brown (+) and Green (-) to a 24 V d.c. supply voltage.
- For fail safe supply (optional), connect the White (+) and Green (-) to the fail safe supply.
Mechanical Installation
General procedure for mounting ICAD 600/900 on all ICM valves.
- Ensure the four socket set screws are fully unscrewed counter-clockwise using a 2.5 mm Hexagon key.
- Mount the ICAD by slowly lowering it onto the ICM valve. The magnet coupling will align the actuator and valve.
- Fasten the ICM and ICAD together using the four socket set screws with a 2.5 mm Hexagon key.
Note: The special moisture seal can be damaged if screws are removed.
Startup
When voltage is applied for the first time, the ICAD display (Fig. 2) will alternate between showing the actual opening degree and "A1".
"A1" indicates an alarm for "No ICM valve selected". Refer to the Alarms section for details.
An automatic calibration is performed when the correct ICM valve type is entered in parameter ¡26. It is not necessary to perform manual calibration in parameter ¡05. Ensure the correct ICM valve is selected and verified.
General Operation
The ICAD is equipped with an MMI (Man Machine Interface) that allows viewing and changing parameters to adapt the actuator and ICM valve to the specific refrigeration application. Operation is performed using the integrated ICAD MMI (Fig. 2).
MMI Interface and Controls
The MMI consists of:
- [Down Arrow Button] (Fig. 2, pos. 1): Decreases the parameter number by 1 with each activation.
- [Enter Button] (Fig. 2, pos. 2):
- Press and hold for 2 seconds to access the Parameter list.
- Press and hold to change a parameter value once the list is accessed. Acknowledge and save the change.
- Press and hold for 2 seconds to exit the Parameter list and return to the Opening Degree display.
- [Up Arrow Button] (Fig. 2, pos. 3): Increases the parameter number by 1 with each activation.
- Display (Fig. 2, pos. 4):
- Normally displays the Opening Degree (OD) of the ICM valve (0-100%).
- If no buttons are activated for 20 seconds, the display reverts to showing the OD.
- Displays the parameter name and its current value.
Display Status Indicators
The display shows status information using text:
- Mod: Indicates the ICAD is positioning the ICM valve according to an analog input signal (Current or Voltage).
- Low: Indicates the ICM valve is operating as an ON/OFF solenoid valve at low speed, controlled by a digital input signal.
- Med: Indicates the ICM valve is operating as an ON/OFF solenoid valve at medium speed, controlled by a digital input signal.
- High: Indicates the ICM valve is operating as an ON/OFF solenoid valve at high speed, controlled by a digital input signal.
Alarms
The ICAD can handle and display various alarms. If an alarm is detected, the display will alternate between showing the alarm code and the present Opening Degree.
Description | ICM Alarm Text | Comments |
---|---|---|
No valve type selected | A1 | At start-up, A1 and CA will be displayed. |
Controller fault | A2 | Internal fault inside electronics. |
All input error | A3 | Not active if ¡01 = 2 or ¡02 = 2. Conditions apply for AI A > 22 mA (current) or AI A > 12 V (voltage). |
Low voltage of fail safe supply | A4 | Applies if 5 V d.c. < Fail safe supply < 18 V d.c. |
Check Supply to ICAD | A5 | Applies if supply voltage < 18 V d.c. |
If multiple alarms are active, the one with the highest priority (A1 being highest, A5 lowest) will be displayed.
Any active alarm will activate the Common Digital Alarm output (Normally Open).
Alarms automatically reset when the condition causing them disappears. Previously active but now resolved alarms can be found in parameter ¡11.
Parameter List
The following parameters can be accessed and configured via the MMI.
Display Name | Parameter | Min. | Max. | Factory Setting | Unit | Comments |
---|---|---|---|---|---|---|
ICM OD (Opening Degree) | ¡00 | 0 | 100 | - | % | ICM valve Opening Degree displayed during normal operation. Running display value (see ¡01, ¡05). |
Main Switch | ¡01 | 1 | 2 | 1 | - | 1: Normal operation. 2: Manual operation. Valve Opening Degree will flash. OD can be entered manually using arrow buttons. |
Mode | ¡02 | 1 | 2 | 1 | - | 1: Modulating - ICM positioning according to Analog Input (see ¡03). 2: ON/OFF - operating the ICM valve via Digital Input. See also ¡09. |
Analog Input signal | ¡03 | 1 | 4 | 2 | - | Type of Analog Input signal from external controller: 1: 0-20 mA, 2: 4-20 mA, 3: 0-10 V, 4: 2-10 V. |
Speed at ON/OFF and Modulating Mode | ¡04 | 1 | 100 | 100 | % | Speed can be decreased. Max. speed is 100%. Not active when ¡01 = 2. If ¡02 = 2, display indicates speed (Low, Med, High). |
Automatic calibration | ¡05 | 0 | 1 | 0 | - | Always auto reset to 0. "CA" flashes during calibration. Not active before ¡26 has been operated. |
Analog Output signal | ¡06 | 0 | 2 | 2 | - | Type of A0 signal for ICM valve position: 0: No signal, 1: 0-20 mA, 2: 4-20 mA. |
Fail safe | ¡07 | 1 | 4 | 1 | - | Define condition at power cut when fail safe is installed: 1: Close valve, 2: Open valve, 3: Maintain valve position, 4: Go to OD given by ¡12. |
Digital Input function | ¡09 | 1 | 2 | 1 | - | Define function when DI is ON (short circuited DI terminals) when ¡02 = 2: 1: Open ICM valve (DI = OFF > Close valve), 2: Close ICM valve (DI = OFF > Open valve). |
Password | ¡10 | 0 | 199 | 0 | - | Enter number to access password protected parameters: ¡26. |
Old Alarms | ¡11 | A1 | A99 | - | - | Old alarms will be listed with the latest shown first. Alarm list can be reset by activating down arrow and up arrow simultaneously for 2 seconds. |
OD at powercut | ¡12 | 0 | 100 | 50 | % | Only active if ¡07 = 4. If fail safe supply is connected and powercut occurs, ICM will go to entered OD. |
ICM configuration | ¡26 | 0 | 6 | 0 | - | NB: Password protected. Password = 11. At first start-up A1 will flash. Enter valve type: 0: No valve selected (Alarm A1 active). 1: ICM20 with ICAD 600, 2: ICM25 with ICAD 600, 3: ICM32 with ICAD 600, 4: ICM40 with ICAD 900, 5: ICM50 with ICAD 900, 6: ICM65 with ICAD 900. |
Service Parameters
Display Name | Parameter | Min. | Max. | Factory Setting | Unit | Comments |
---|---|---|---|---|---|---|
OD % | ¡50 | 0 | 100 | - | % | ICM valve Opening Degree. |
AI [mA] | ¡51 | 0 | 20 | - | mA | Analog Input signal. |
AI [V] | ¡52 | 0 | 10 | - | V | Analog Input signal. |
AO [mA] | ¡53 | 0 | 20 | - | mA | Analog Output signal. |
DI | ¡54 | 0 | 1 | - | - | Digital Input signal. |
DO Close | ¡55 | 0 | 1 | - | - | Digital Output Closed status. ON when OD < 3 %. |
DO Open | ¡56 | 0 | 1 | - | - | Digital Output Open status. ON when OD > 97 %. |
DO Alarm | ¡57 | 0 | 1 | - | - | Digital Output alarm status. ON when an alarm is detected. |
MAS mP SW ver. | ¡58 | 0 | 100 | - | - | Software version for MASTER Microprocessor. |
SLA mP SW ver. | ¡59 | 0 | 100 | - | - | Software version for SLAVE Microprocessor. |
Reset to Factory Setting
Follow these steps to reset the actuator to its factory settings:
- Remove the power supply.
- Activate the [Down Arrow Button] and [Up Arrow Button] simultaneously.
- Connect the power supply.
- Release the [Down Arrow Button] and [Up Arrow Button].
- When the display on the ICAD (Fig. 2) alternates between showing "CA" and "A1", the factory resetting is complete.