Carrier Rooftop Units

Louvered Hail Guard Accessory

Installation Instructions

Part Numbers: CRLVHLGD004A00, CRLVHLGD011A00-CRLVHLGD016A00, CRLVHLGD020A00-CRLVHLGD022A00, CRLVHLGD023B00, CRLVHLGD024A00, CRLVHLGD032A00, CRLVHLGD045A00-CRLVHLGD051A00

IMPORTANT

Read entire instructions before installing the accessory.

Safety Considerations

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.

It is important to recognize safety information. This is the safety-alert symbol [safety-alert]. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

WARNING

Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.

Package Contents and Usage

Table 1: Package Contents

QTYCONTENTS
1Outside coil side panel
1Outside coil end panel
1Control box side panela
10Plastic insertsa
Varies based on kitScrews

a CRLVHLGD024A00 and 032A00

General

Louvered hail guard packages are designed to protect the rooftop unit condenser coil from hail and general contact damage. Excessive damage to rooftop unit outdoor coils can result in diminished performance due to reduced air flow over the heat transfer surfaces.

Package Usage

Table 2: Package Usage

HAIL GUARD PACKAGEROOFTOP UNIT MODEL
CRLVHLGD004A0050TCQ*08-12
CRLVHLGD011A0048/50KC**05 (3-Phase)
48/50TC**04
50TCQA04
50HCQ*04
CRLVHLGD012A0048/50KC**04
48/50KC**05 (1-Phase)
48/50TC**05-06
50KCQ*04
50TCQA05
48LC/50LC**04
48/50HC**04
CRLVHLGD013A0050HCQ*05-06
48/50KC**06 (1-Phase)
50KCQ*05-06
48/50TC**07
50TCQA07
48/50LC**05-06
48/50HC**05-06
CRLVHLGD014A0048/50FC*08
50HCQ*07
48/50TC*A, D08a
48/50HC**07
CRLVHLGD015A0048/50TC*A09a
CRLVHLGD016A0048/50FC*12
48/50FC*14
50HCQ*08-09
48/50LC**07
48/50TC-D09a
48/50TC*A,D12a
48/50TC*D14a
48/50HC**08-12
48/50FCQ*08-12
CRLVHLGD020B0048/50TC*D08
CRLVHLGD021B0048/50TC*D12
CRLVHLGD022A0048/50TC*D14
CRLVHLGD023B0050TCQA06
CRLVHLGD024A0048/50LC*08
50TCQ*14
50FCQ*14
CRLVHLGD032A0048/50FC*16
50HCQ*12
48/50LC**09-12
48/50TC**16a
48/50HC**14
CRLVHLGD045A0048/50KC**06 (3-Phase)
48/50FC**04
48/50GC**04
50GCQ*04
CRLVHLGD046A0048/50FC**05
CRLVHLGD047A0048/50FC**06
50FCQ*05
48/50GC**05
CRLVHLGD048A0048/50FC**07
48/50GC**06
50FCQ*06
50GCQ*05-06
48/50JC**04-06
CRLVHLGD049A0050FCQ*04
CRLVHLGD050A0050FCQ*07
CRLVHLGD051A0048/50FC*09

a Round tube plate fin outdoor coil only.

Installation (All Kits Except CRLVHLGD024A00 and 032A00)

  1. Verify the correct hail guard part number is provided for the desired rooftop unit size. See Table "Package Usage" on page 2.
  2. Remove the screws in the top panel of the rooftop unit above the condenser coil. Save the screws.
  3. Remove the screws at the base of the outdoor coil where the hail guard panel will be installed. Save the screws.
  4. Align the hail guard panel with the respective section of the outdoor coil and insert the top edge of the panel under the lip of the top panel. (See Fig. 1 and 2.)
  5. Re-insert top and bottom screws from Steps 2 and 3 to hold the hail guard in place.
  6. Insert side screws from the kit through the holes in the side(s) of the hail guard panels. The provided self tapping screws may be required for these screws.

Diagram Description: The illustration shows the unit assembly of hail guards. It depicts a SIDE PANEL with one bent side flange attached with supplied screws, and an END PANEL with two bent side flanges attached with supplied screws.

Table 3: Screw Installation Details

PART NUMBERSIDE PANELEND PANEL
TOPLEFTBOTTOMRIGHTTOPLEFTBOTTOMRIGHT
CRLVHLGD004A0000400057
CRLVHLGD011A0000320252
CRLVHLGD012A0000320263
CRLVHLGD013A0000320263
CRLVHLGD014A0000400056
CRLVHLGD015A0000400056
CRLVHLGD016A0000400057
CRLVHLGD020A000442a02a82
CRLVHLGD021A000672a02a74
CRLVHLGD022A000332a02a73
CRLVHLGD023B00N/ASee Fig. 2See Fig. 3
CRLVHLGD024A0000320252
CRLVHLGD032A0000320252
CRLVHLGD045A0000320252
CRLVHLGD046A0000320252
CRLVHLGD047A0000320262
CRLVHLGD048A0000321272
CRLVHLGD049A0000321272
CRLVHLGD050A0000321262

a Plastic inserts and 7/8 in. long gasketed screws.

Figure 1 Description: Illustrates typical louvered hail guard screw installation for 3-5 ton units, showing the attachment of side and end panels to the rooftop unit.

Figure 2 Description: Details louvered hail guard screw installation for specific models (CRLVHLGD014A00, 015A00, 016A00, 020A00, 021A00, 022A00, and 051A00), showing the screw counts for side and end panels.

Installation (CRLVHLGD024A00, 032A00)

  1. Verify the correct hail guard part number is provided for the desired rooftop unit size. See Table 2, "Package Usage," on page 2.
  2. The units associated with this hail guard kit are shipped with a center post located on the end of the unit. It should have been removed during unit installation. This post is located approximately 1.5 ft from the left corner post on the end of the unit. Remove this post if it has not been removed already.
  3. Insert plastic inserts into both corner posts (6 inserts) and center post (2 inserts) located by the control box as indicated in Fig. 3.
  4. Align the hail guard panel with the respective section of the outdoor coil and insert the top edge of the panel under the lip of the top cover.
  5. Use the long 7/8 in. gasketed screws to secure the hail guard in the plastic inserts (8 locations). Use the shorter serrated screws to secure the panels to the remaining holes in the vertical direction. Use shorter serrated screws to secure the panels along the bottom of the panels.

Diagram Description: The illustration shows the installation of louvered hail guards for CRLVHLGD024A00 and 032A00 models. It labels the CONTROL BOX PANEL, SIDE PANEL, and END PANEL, and indicates the placement of plastic inserts and gasketed screws, as well as serrated screws.

Figure 3 Description: Depicts the louvered hail guard installation process for CRLVHLGD024A00 and 032A00 units, highlighting the attachment points and hardware.

Models: CRLVHLGD004A00, CRLVHLGD011A00, CRLVHLGD016A00, CRLVHLGD020A00, CRLVHLGD022A00, CRLVHLGD023B00, CRLVHLGD024A00, CRLVHLGD032A00, CRLVHLGD045A00, CRLVHLGD051A00, CRLVHLGD004A00 Gas Heating-Electric Cooling Electric Cooling and Heat Pump Units, CRLVHLGD004A00, Gas Heating-Electric Cooling Electric Cooling and Heat Pump Units, Electric Cooling and Heat Pump Units, Cooling and Heat Pump Units, Heat Pump Units, Pump Units, Cooling Electric Cooling and Heat Pump Units

PDF preview unavailable. Download the PDF instead.

IIK-CRLVHLGD04-08 Acrobat Distiller 22.0 (Windows)

Related Documents

Preview Carrier 48/50K Louvered Hail Guard Accessory Installation Instructions
Detailed installation instructions for the Carrier 48/50K Louvered Hail Guard Accessory, including safety considerations, package contents, and step-by-step guidance for models CRHAILGD030A00, CRHAILGD031A00, and CRHAILGD032A00.
Preview Carrier 48SD/48SDN Single-Packaged Gas Heating/Electric Cooling Units - Product Data
Comprehensive product data for Carrier's 48SD/48SDN series of single-packaged gas heating and electric cooling units. This document details features, benefits, specifications, performance data, installation guidelines, electrical information, and options for residential and light commercial applications.
Preview Carrier 48FC04-07 Rooftop Unit Service and Maintenance Manual
Comprehensive service and maintenance guide for the Carrier 48FC04-07 Single Package Rooftop Gas Heat/Electric Cooling Unit, covering safety, operation, troubleshooting, and component details for trained service personnel.
Preview Carrier AIRSNAP 80: 80 kW Rooftop Heat Pump - Technical Data Sheet
Technical data sheet for the Carrier AIRSNAP 80, an 80 kW rooftop heat pump. This compact and monobloc system offers efficient heating and cooling for industrial and commercial applications, featuring simplified installation and optimal thermal comfort.
Preview Carrier WeatherMaker 48TC Series Installation Instructions
This guide details the installation of Carrier WeatherMaker 48TC series single package rooftop units, featuring gas heat and electric cooling. It covers safety, site preparation, unit mounting, ductwork, gas and electrical connections, and start-up procedures for qualified installers.
Preview Carrier 50FEQ*04-07 Rooftop Heat Pump Service & Maintenance Manual
Detailed service and maintenance instructions for Carrier 50FEQ*04-07 Single Package Rooftop Heat Pumps (3-6 Tons) with R-454B refrigerant. Covers safety, troubleshooting, operation, and component servicing.
Preview Carrier 25VNA4 Infinity Variable Speed Heat Pump Installation Instructions
Comprehensive installation guide for the Carrier 25VNA4 Infinity Variable Speed Heat Pump with Greenspeed Intelligence, covering safety, mounting, electrical connections, refrigerant charging, and troubleshooting procedures.
Preview Carrier Louvered Hail Guard Accessory Installation Guide for Rooftop Units
Installation instructions for Carrier Louvered Hail Guard Accessory, designed for Gas Heat/Electric Cooling, Electric Cooling, and Heat Pump rooftop units (15-28 Tons). Includes safety information, package contents, usage tables, and step-by-step installation guidance.