AntMiner S21 Hyd. User Guide

Bitmain, AntMiner, S21, Hyd.

Avi Eliav

[PDF] AntMiner S21 Hyd. User Guide - BITMAIN

The S21 Hyd. server is one of BITMAIN's latest products. The APW11 power supply is a crucial component of the S21 Hyd. server. All S21 Hyd. servers ...


File Info : application/pdf, 34 Pages, 2.39MB

PDF preview unavailable. Download the PDF instead.

S21 Hyd. User Guide-V4.0.14
S21 Hyd.
User Guide
Feb. 2025
BITMAIN TECHNOLOGIES INC. www.bitmain.com

Table of Contents

S21 Hyd. User Guide

1 Overview...........................................................................................................1 1.1 S21 Hyd. Server components ............................................................................... 2 1.2 Specifications of Partial Components................................................................. 4 1.3 Product Specifications ......................................................................................... 5
2 Cooling System Requirements ........................................................................7 2.1 Requirements of Coolant..................................................................................... 7 2.2 Maintenance Requirements of Cooling System................................................ 10
3 Installation and Rack Management .............................................................. 11 3.1 Installation Location.......................................................................................... 11 3.2 Loading Hydro-cooling miner ........................................................................... 11 3.3 Unloading Hydro-cooling miner ....................................................................... 12 3.4 Precautions ........................................................................................................ 12
4 Setting up the Server......................................................................................14 4.1 Setting up the Server ......................................................................................... 14 4.2 Configuring the Server....................................................................................... 15 4.3 Monitor your Server .......................................................................................... 16 4.4 Administering your Server ................................................................................ 18
4.4.1 Checking your Firmware Version ............................................................................... 18 4.4.2 Upgrading your System ............................................................................................... 18 4.4.3 Modifying your Password ........................................................................................... 19 4.4.4 Restoring Initial Settings............................................................................................. 19 4.4.5 Error Code ..................................................................................................................... 20
5 Environmental Requirements ....................................................................... 25 5.1 Basic Environmental Requirements................................................................. 25
5.1.1 Site Requirements of the Server Running Room ...................................................... 25 5.1.2 Electromagnetic Environmental Conditions ............................................................. 25
5.2 Other Environmental Requirements ................................................................ 25
5.2.1 Mechanical Active Substances .................................................................................... 25 5.2.2 Corrosive Gas ................................................................................................................ 26

S21 Hyd. User Guide
6 Regulations ..................................................................................................... 27 6.1 Federal Communications Commission (FCC) ................................................... 27 6.2 Industry Canada................................................................................................. 27 6.3 European Community........................................................................................ 27 6.4 Taiwan ROHS...................................................................................................... 28 6.5 FCC Supplier's Declaration of Conformity ........................................................ 29 6.6 EU Declaration of Conformity ........................................................................... 30
7 Warranty.........................................................................................................31

S21 Hyd. User Guide
1 Overview
The S21 Hyd. server is one of BITMAIN's latest products. The APW11 power supply is a crucial component of the S21 Hyd. server. All S21 Hyd. servers are thoroughly tested and configured before shipping to ensure easy setup.
Figure 1-1 S21 Hyd. server Caution: (1) Please refer to the layout above to place your equipment in their designated locations
to prevent any damage. (2) The equipment must be connected to an earthed mains socket. The socket shall be
installed near the equipment and shall be easily accessible. (3) DO NOT remove any screws or cables attached to the product. (4) Please note that the actual server shall prevail. (5) There must be an external specific surge protection device complying with IEC/EN
61643-11 either in front of the power supply or outside the end system (in a separate distribution box or as part of the building installation). (6) DO NOT plug or remove the device when it is powered on. (7) The external power supply must have a disconnecting device, which can disconnect L1, L2, and L3 simultaneously. (8) The server needs to be manually restarted when the hashrate is abnormal. (9) The S21 Hyd. server shall be used simultaneously with the ANTSPACE series. Please click BITMAIN Shop for more details on ANTSPACE series.
1

1.1 S21 Hyd. Server components

S21 Hyd. User Guide

The main components and control panel of the S21 Hyd. server are shown in the figure below.

Figure 1-2 Main components and control panel of S21 Hyd. server Figure 1-2 illustrates a type of the S21 Hyd. server control panel. The following sections provide a detailed description of the function and specific role of each component.
2

APW11 Power Supply:

S21 Hyd. User Guide

Figure 1-3 APW11 power supply
The APW11 power supply serves as the energy source for S21 Hyd. server. NOTE:  The power connector is designed to be waterproof.  For detailed parameters, please refer to the specifications below.
Bend Pipes, Water Inlet and Outlet:
Bend Pipes, water inlet, and water outlet refer to components in a cooling system that control the flow of coolant into and out of the system NOTE:  When inserting or removing the bend pipes, ensure they are securely tightened.
Control Panel:
Ethernet mode: The device is equipped with an RJ45 Ethernet interface that supports data transfer speeds of 10/100 Mbps. LED Indicators: The green LED indicates normal operation of the Ethernet interface. The red LED signifies a fault condition within the Ethernet interface, requiring attention.
3

S21 Hyd. User Guide
Function Activation: The IP report function can be activated by pressing the raised button.
The reset function can be activated by pressing the recessed button, allowing for quick troubleshooting and maintenance.
SD Card/Micro USB Slot: The SD Card can be used to connect a SD card or micro USB interface for data transfer.
Hashboards Housing:
The hashboards housing is an enclosure designed to store and protect the hashboards. Its primary functions include providing structural support, shielding the hashboards from external environmental factors, and ensuring proper heat dissipation and electrical connections.

1.2 Specifications of Partial Components

Customers can purchase the following parts for the S21 Hyd. on our official website at

https://www.bitmain.com. The specifications for the above parts can be found on the parts

sales page of our official website.

Table 1-1 Specifications of Partial Components

Item Number

Accessories

Picture

Control Board for Hyd. Series

1

APW111721,17V21.6V,RSPri_V1.25EMC 2

4

Manifold (for 3 hashboards) 3
Corrugated Pipe, D10, L=210mm, Transparent FEP 4

S21 Hyd. User Guide

1.3 Product Specifications

Table 1-2 Product Glance

Product Glance

Value

Model

S21 Hyd.

Version

m0-10

Crypto algorithm/coins

SHA256|BTC/BCH/BSV

Typical Hashrate, TH/s(1-1) Power on wall @35(1-2), Watt(1-1) Power efficiency on wall@35(1-2), J/TH(1-1)

335 5360

319 5104
16.0

302 4832

Table 1-3 Detailed Characteristics of Product

Detailed Characteristics

Value

Power Supply

Phase

3

Input voltage, Volt(2-1)

380~415

Input frequency range, Hz

50~60

Input max current, Amp

12

Hardware Configuration

Network connection mode
Server size (length*width*height, w/o package), mm Server size (length*width*height, with package), mm
Net weight, kg

RJ45 Ethernet 10/100M 339*173*207 570*316*430 12.3

Gross weight, kg

13.6

Environment Requirements

Inlet coolant temperature, °C

20~50

5

S21 Hyd. User Guide

Coolant flow, L/min Coolant pressure, bar Working coolant(2-2)
Coolant pH value
Diameter of coolant pipe connector, mm Storage temperature, °C Operation humidity(non-condensing), RH Operation temperature, °C Operation altitude(2-3), m

8.0~10.0 3.5
Antifreeze/ Pure water/Deionized water
Antifreeze: 7.0~9.0 Pure water: 6.5~7.5 Deionized water8.5~9.5
OD10
-20~70
10~90%
-20-50
2000

NOTE:

(1-1) The hashrate value, power on wall, and power efficiency on wall are all typical values. The actual hashrate value fluctuates by ±3%, and the actual power on wall and power efficiency on wall fluctuate by ±5%. (1-2) Inlet coolant temperature. (2-1) Caution: Wrong input voltage may cause server damaged. (2-2) For detailed working coolant use and maintenance instructions, please refer to Chapter 2.1 "Requirements of Coolant". (2-3) When the server is used at an altitude from 900m to 2000m, the highest operating temperature decreases by 1 for every increase of 300m.

6

2 Cooling System Requirements
2.1 Requirements of Coolant

S21 Hyd. User Guide

When purchasing coolant, it is essential to focus on the relevant parameters in Table 2-1. If the requirements are not met, it is necessary to consider refilling and replacing the coolant as appropriate. (1) The primary focus during regular inspection of coolant should be the pH value. It is
not recommended to use the coolant when the pH value is below 7 (a pH indicator can be added to the coolant. When the pH is below 6.8, the coolant will change color for easy observation); the inspection method is shown in the table below. (2) Secondary focuses during regular inspection of coolant include freezing point, ethylene glycol ratio, total hardness, etc. In the later stage, attention should be paid to whether the content of elements such as Al, Fe, and Cu increases or not, as an increase indicates that contact corrosion has already occurred; the inspection method is shown in the table below. It is recommended to regularly add corrosion inhibitors according to the supplier's requirements to maintain the coolant.

Table 2-1 Recommended Standard Parameters for Coolant

Items

Index

Recommended reference standards for inspection

Color Exterior Freezing point Boiling point

Significant color No odor, sediment, or
suspended solids Local minimum freezing
temperature 108°C (low temperature type)

Visual inspection Visual inspection

pH value
Reserve alkalinity
Total hardness

7-9 4ml (organic formula) 9ml (including inorganic
formula)
<120 mg/l

Main element

B

content

Si

<20mg/kg <20mg/kg

7

P

<20mg/kg

Mo

<20mg/kg

Ca

<20mg/kg

Al3+

<50mg/L

Fe2+

<50mg/L

Cu2+

<50mg/L

S21 Hyd. User Guide

Table 2-1 provides the medium requirements for working environments with temperatures below 0°C like glycol. Table 2-2 illustrates the relationship between the concentration of glycol and its freezing point.
Table 2-2 Glycol Refrigerant Concentration vs. Freezing Points

Glycol concentration

Mass

Volume

concentration, % concentration, %

0

0

5

4.4

10

8.9

15

13.6

20

18.1

25

22.9

30

27.7

35

32.6

40

37.5

45

42.5

50

47.6

55

52.7

60

57.8

Freezing point, °C
0 -1.4 -3.2 -5.4 -7.8 -10.7 -14.1 -17.9 -22.3 -27.5 -33.8 -41.1 -48.3

If the working environment temperature is consistently above 0°C, deionized water or

purified water can be used as the secondary side internal circulation medium with

corresponding requirements listed in Table 2-3.

Table 2-3

Recommended standards for deionized water

Index
pH value Sulfide

Deionized water
8.5-9.5
<1 ppm

Reference standards
Intel 632983 TC9.9/Intel
632983
8

Remarks

S21 Hyd. User Guide

Sulfate

<10 ppm

TC9.9/Intel 632983

Chloride

<5 ppm

TC9.9/Intel 632983

Bacterial community

<100 CFUs/ml

TC9.9/Intel 632983

Total hardness (as CaCO3)

<20 ppm

Conductivity

<20us/cm (reference value, not mandatory)

TC9.9/Intel 632983
TC9.9

High conductivity is not necessarily unacceptable, such as 1000us/cm, as corrosion inhibitors and fungicides will both lead to an increase in water conductivity. It is necessary to understand the reasons behind the sharp increase in conductivity trend during circuit operation.

Residues after evaporation

50 ppm

TC9.9/Intel 632983

Turbidity

<20 NTU

TC9.9/Intel 632983

Iron content Copper content

0.1 ppm 10 ppm

Industry standards Industry standards

Carbon steel corrosion rate

3mpy (0.075mm/a)

GB/T 500502017

Corrosion rate of copper or stainless steel

0.2mpy (0.005mm/a)

GB/T 500502017

NOTE:

 The coolant must be configured strictly in accordance with the lowest possible

temperature in the environment. If the coolant is not configured according to the

instructions and the ambient temperature is lower than the freezing point of the

coolant, causing the heat exchanger to freeze and crack, our company will not bear

9

any responsibility.

S21 Hyd. User Guide

2.2 Maintenance Requirements of Cooling System
As the core unit of the container water cooling system, it is recommended to regularly track and record the coolant, at least once a year (pH value should be tested every six months). To ensure long-term reliable operation, when using deionized water or purified water as the internal circulation medium, check every 1-2 weeks and replace the internal coolant every 1-2 months. When using deionized water as the internal circulation medium, please strictly comply with the usage environment above 0°C. Otherwise, if the temperature is below freezing point, unexpected power outage will cause the internal pipes of the system to freeze and cause the pipes to burst. When using deionized water/pure water, the pH value, conductivity, and related index parameters of the coolant must be regularly tested and recorded. When the requirements in Table 2-3 are exceeded, or there are abnormal changes, new deionized water/pure water that meets the requirements must be replaced in time.

10

S21 Hyd. User Guide
3 Installation and Rack Management
3.1 Installation Location
The S21 Hyd. should be installed on the racks in our water-cooled container, with the water and electrical interfaces facing the aisle of the water-cooled container.
3.2 Loading Hydro-cooling miner
First connect the water, then the power supply, and proceed from the top to the bottom in sequence. 1. Water flows: First, close all the inlet and outlet water valves, then insert the water pipes
into the machine's quick connectors, with the upper connector for inlet and the lower one for outlet. Make sure the water pipes are fully inserted to ensure a tight seal. Then, open all the water pipe valves and check for any leaks. 2. Power: The miner's power plug is an aviation plug, and the button can be fully reset to complete insertion. 3. Network: Insert the corresponding network cable below the miner into the miner, and each network cable has a location code.
11

S21 Hyd. User Guide
3.3 Unloading Hydro-cooling miner
First cut off the power, then cut off the water, from the lower level to the higher level in sequence. 1. Power: Turn off the corresponding air switch of the miner. 2. Water flows:
Step 1: close all the inlet and outlet valves of the miner to ensure they are fully closed. Then, slowly pull out the inlet and outlet water pipes, and lower the water pipe mouth to allow the liquid inside the miner to flow into the bucket until no water droplets flow out. Step 2: check the power plug and network cable head, confirm that there is no liquid on the head, and then unplug and remove the miner. Step 3: unplug the water pipe and block the quick connect plug of the miner with a water stop plug. The residual miner coolant should be left in the miner (if repair is required, all the miner coolant should be drained and the residual coolant inside the miner should be blown dry with an air pump). After removal from the rack, the water inlet and outlet of the original miner position should be kept connected. 3. Network: Pull out the network cable from the miner and bend it down to avoid scratching the network cable when removing the miner. 4. After all the above operations are completed, the miner can be taken out and removed from the rack.
3.4 Precautions
1. Before water filling: Check the water pipes to ensure they are securely connected to prevent leaks during water filling.
2. Power connections: Ensure that the power connections are securely plugged in to avoid sparks when powering on. Before plugging in or unplugging the AC power input line, please ensure that the server is powered off.
3. Powering on: First, fill the system with water, wait for 20 seconds, and then confirm that the flow rate and water temperature meet the standards before powering on.
4. Powering off: First, disconnect the power, wait for 20 seconds, and then confirm that the server is powered off before disconnecting the water.
12

S21 Hyd. User Guide
5. In case of water spillage: If there is water splashing or spraying from the watercooled server, do not power on the device directly. Please contact the after-sales service center.
6. Operating below 0°C: If the water-cooled server operates in an environment below 0°C, antifreeze must be used inside; otherwise, there is a risk of freezing and cracking the server.
7. In case of thunderstorms: Unplug the device during thunderstorms or when not in use for an extended period. This will protect the server from damage caused by power fluctuations. Do not overload the power outlet and power cord. Overloading may result in fire or electric shock.
8. In case of strange odors, sounds, or smoke: If the server emits strange odors, sounds, or smoke, immediately disconnect the power and contact the service center. Under no circumstances should you hit or drop the server. Ensure that all connection cables are securely connected and properly aligned.
9. The miner can only be energized after all of the above operations have been completed.
10. When performing batch shelving operations: it is necessary to load the miner from the upper layer to the lower layer in order to avoid the impact of residual water in the water pipe on the miners in the lower layer.
11. For transfer in batches, all the cooling liquid of the miner should be discharged, dried with an air pump, and packaged in original carton boxes for transportation and transfer.
13

4 Setting up the Server

S21 Hyd. User Guide

NOTE:  The file IPReporter.zip is supported by Microsoft Windows only.
4.1 Setting up the Server
To set up the server:
4. Go to the following site: https://file12.bitmain.com/shop-product/firmware/IP%20Reporter.zip. If the link is invalid, please visit the official firmware download page (https://service.bitmain.com/support/download) and select as shown in the image to download IPReporter.zip.

5. Download the following file: IPReporter.zip. 6. Extract the file. NOTE:  The default DHCP network protocol distributes IP addresses automatically 7. Right-click IPReporter.exe and run it as Administrator. 8. Select one of the following options:
 Shelf, Step, Position ­ suitable for farm servers to mark the location of the servers.  Default ­ suitable for home servers. 9. Click Start.

14

S21 Hyd. User Guide
10. On the control panel, click the IP Report button (its location is shown in Figure 1-2). Hold the button down until it beeps (about 5 seconds). The IP address will be displayed in a window on your computer screen.
11. In your web browser, enter the IP address provided. 12. Proceed to login using root for both the username and password. 13. In the Protocol section, you can assign a Static IP address (optional). 14. Enter the IP address, Subnet mask, gateway and DNS Server. 15. Click "Save". 16. Click https://support.BITMAIN.com/hc/en-us/articles/360018950053 to learn more
about gateway and DNS Server.
4.2 Configuring the Server
Setting up the Pool To configure the server: 1. Click Settings as below.
15

S21 Hyd. User Guide

2. Set the options according to the following table:

Option

Description

Mining address

Enter the address of your desired pool. The S21 Hyd. servers can be set up with three mining pools, with decreasing priority from the first pool (pool 1) to the third pool (pool 3). The pools with low priority will only be used if all higher priority pools are offline.

Name

Your worker ID on the selected pool.

Password (optional) The password for your selected worker.

3. Click Save after the configuration.

4.3 Monitor your Server
To check the operating status of your server (taking S21 Hyd. 335T as an example): 1. Click dashboard marked below to check the server status.

16

S21 Hyd. User Guide

2. Monitor your server according to the descriptions in the following table:

Option

Description

Number of chips

Number of chips detected in the chain.

Frequency

ASIC frequency setting.

Real Hashrate

Real-time hashrate of each hash board (GH/s).

Inlet Temp

Temperature of the inlet (°C).

Outlet Temp

Temperature of the outlet (°C).

Chip state

One of the following statuses will appear:  The Green Icon - indicates normal

 The Red Icon- indicates abnormal

3. Monitor your server according to the LED indicator light:

Status

Fault Indicator(RED)

Normal Indicator(GREEN)

Normal

OFF

ON

Over

ON

OFF

temperature

Network

ON

OFF

disconnection

NOTE:

 The frequency of the S21 Hyd. server is fixed at 410 MHz. The firmware will stop

running when the Temp (PCB) reaches 75 , the water temperature is either greater

than 50or lower than 20 and the maximum asic temperature is greater than 95.

17

S21 Hyd. User Guide
An error message, "Fatal Error: Temperature is too high!" will be shown at the bottom of the Kernel log page.
4.4 Administering your Server
4.4.1 Checking your Firmware Version
To check your firmware version: 1. Enter the backend of your server, find the firmware version at the bottom. 2. File System Version displays the date of the firmware your server uses. In the
example below, the server is using firmware version 202412121853.
4.4.2 Upgrading your System
Caution: Make sure that the S21 Hyd. server remains powered during the upgrade process. If power fails before the upgrade is completed, you will need to return it to BITMAIN for repair. To upgrade the server's firmware: 1. In System, click Firmware Upgrade.
18

S21 Hyd. User Guide

2. For Keep Settings: (1) Select "keep settings" to keep your current settings (default). (2) Unselect "keep settings" to reset the server to default settings.

3. Click the

button and navigate to the upgrade file. Select the upgrade file,

then click Update.

4. When the upgrade is completed, restart the server. It will return to the dashboard

page automatically.

4.4.3 Modifying your Password
To change your login password: 1. In System, click the Password tab. 2. Set your new password, then click Save.

4.4.4 Restoring Initial Settings
To restore your initial settings 1. Turn on the server and let it run for 5 minutes. 2. On the controller front panel, press and hold the Reset button for 10 seconds.
19

S21 Hyd. User Guide
Caution: Resetting your server will reboot it and restore its default settings. The red LED will automatically flash once every 15 seconds if the reset is operated successfully.

4.4.5 Error Code

Here is the server error code and the corresponding reasons and suggestions:

Error Code Reason

Suggestion

R:1

Average total Update the firmware to the latest version,

hashrate is low replace the power supply, or return to factory

for repair

R1:1

Chain1 is

Check if chain1 connection is normal, update

broken or has the firmware to the latest version, replace the

low hashrate hashboard, or return to factory for repair

R2:1

Chain2 is

Check if chain2 connection is normal, update

broken or has the firmware to the latest version, replace the

low hashrate hashboard, or return to factory for repair

R4:1

Chain3 is

Check if chain3 connection is normal, update

broken or has the firmware to the latest version, replace the

low hashrate hashboard, or return to factory for repair

R8:1

Chain4 is

Check if chain4 connection is normal, update

broken or has the firmware to the latest version, replace the

low hashrate hashboard, or return to factory for repair

J1:1

Chain1 has bad Update the firmware to the latest version,

ASIC

replace the power supply, or return to factory

for repair

J2:1

Chain2 has bad Update the firmware to the latest version,

ASIC

replace the power supply, or return to factory

for repair

J4:1

Chain3 has bad Update the firmware to the latest version,

ASIC

replace the power supply, or return to factory

for repair

20

S21 Hyd. User Guide

J8:1

Chain4 has bad Update the firmware to the latest version,

ASIC

replace the power supply, or return to factory

for repair

N:1

Average total Update the firmware to the latest version

hashrate

exceeds the

sale hashrate

too much

N:2

Frequency is Update the firmware to the latest version

reduced too

much

V:1

Power

Check power output wiring, update the

initialization firmware to the latest version, replace the

error or power power supply, or return to factory for repair

output voltage

error

V:2

Power supply Update the firmware to the latest version,

is not

replace the power supply, or return to factory

calibrated

for repair

J:8

The number of Check if the hashboard connection is normal,

hashboards is or replace the hashboard

less than the

design

P:1

High

Check if the environment temperature is

temperature normal, or check if the gel on the hashboard is

protection

effective

P:2

Low

Check if the environment temperature is

temperature normal

protection

J1:4

Chain1

Redo the factory test for chain1

EEPROM data

error

21

S21 Hyd. User Guide

J2:4

Chain2

Redo the factory test for chain2

EEPROM data

error

J4:4

Chain3

Redo the factory test for chain3

EEPROM data

error

J8:4

Chain4

Redo the factory test for chain4

EEPROM data

error

J:6

Temperature Check if the hashboard connection is normal,

sensor error update the firmware to the latest version,

replace the hashboard, or return to factory for

repair

J1:5

Chain1 PIC

Check if chain1 connection is normal, update

error

the firmware to the latest version, replace the

hashboard, or return to factory for repair

J2:5

Chain2 PIC

Check if chain2 connection is normal, update

error

the firmware to the latest version, replace the

hashboard, or return to factory for repair

J4:5

Chain3 PIC

Check if chain3 connection is normal, update

error

the firmware to the latest version, replace the

hashboard, or return to factory for repair

J8:5

Chain4 PIC

Check if chain4 connection is normal, update

error

the firmware to the latest version, replace the

hashboard, or return to factory for repair

M:1

Memory

Update the firmware to the latest version,

allocation

replace the control board, or return to factory

error

for repair

J1:2

The number of Check if chain1 connection is normal, update

chain1 chips is the firmware to the latest version, replace the

less than the hashboard, or return to factory for repair

design

22

S21 Hyd. User Guide

J2:2

The number of Check if chain2 connection is normal, update

chain2 chips is the firmware to the latest version, replace the

less than the hashboard, or return to factory for repair

design

J4:2

The number of Check if chain3 connection is normal, update

chain3 chips is the firmware to the latest version, replace the

less than the hashboard, or return to factory for repair

design

J8:2

The number of Check if chain4 connection is normal, update

chain4 chips is the firmware to the latest version, replace the

less than the hashboard, or return to factory for repair

design

L1:1

Chain1 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

exceeds the

limit

L2:1

Chain2 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

exceeds the

limit

L4:1

Chain3 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

exceeds the

limit

L8:1

Chain4 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

exceeds the

limit

L:2

Cannot find the Update the firmware to the latest version, or

mixed level

return to factory for repair

L1:2

Chain1 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

mismatch

23

S21 Hyd. User Guide

L2:2

Chain2 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

mismatch

L4:2

Chain3 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

mismatch

L8:2

Chain4 voltage Update the firmware to the latest version, or

or frequency return to factory for repair

mismatch

N:4

Network

Check if the network connection is normal

connection is

lost

24

5 Environmental Requirements

S21 Hyd. User Guide

Please ensure that your server operates in accordance with the following environmental requirements.
5.1 Basic Environmental Requirements

5.1.1 Site Requirements of the Server Running Room
Please ensure that the server operating room is kept away from industrial pollution sources:
(1) For heavy pollution sources such as smelters and coal mines, maintain a distance of more than 5 km.
(2) For moderate pollution sources such as chemical industries, rubber, and electroplating industries, maintain a distance of more than 3.7 km.
(3) For light pollution sources such as food factories and leather processing factories, maintain a distance of more than 2 km. If unavoidable, choose a site in the perennial upwind direction of the pollution source.
Please do not set up your location within 3.7 km of the seaside or a saltwater lake. If this is unavoidable, ensure that the structure is as airtight as possible and equipped with air conditioning for cooling.
5.1.2 Electromagnetic Environmental Conditions
Please keep your site away from transformers, high-voltage cables, transmission lines, and high-current equipment. For example, there should be no high-power AC transformers (>10KA) within 20 meters, and no high-voltage power lines within 50 meters. Additionally, keep your site away from high-power radio transmitters; for example, there should be no high-power radio transmitters (>1500W) within 100 meters.

5.2 Other Environmental Requirements

The server running room shall be free of explosive, conductive, magnetically conductive and corrosive dust. The requirements of mechanical active substances are shown below.

5.2.1 Mechanical Active Substances
Table 5-1 Requirements of mechanical active substances

Mechanical Active Substance
Sand, mg/m3

Requirement
30

25

Dust (suspended), mg/m3 Dust (deposited) , mg/ m2h
5.2.2 Corrosive Gas
Table 5-2 Requirements of corrosive gas

S21 Hyd. User Guide
0.2 1.5

Corrosive Gas

Unit

Concentration

H2S

ppb

< 3

SO2

ppb

< 10

Cl2

ppb

< 1

NO2

ppb

< 50

HF

ppb

< 1

NH3

ppb

< 500

O3

ppb

< 2

Note: ppb (part per billion) refers to the unit of concentration, 1ppb stands for the volume ratio of part per billion.

26

6 Regulations

S21 Hyd. User Guide

6.1 Federal Communications Commission (FCC)
FCC Notice: This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Caution: Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

6.2 Industry Canada
CAN ICES-003(A) / NMB-003(A)

6.3 European Community
Warning: Operation of this equipment in a residential environment could causeradio interference.

UAB Bitmain Development Lithuania Vilnius, Bistrycios g.40-21

EU WEEE Disposal of Waste Equipment by Users in Private Household in the European Union:

27

S21 Hyd. User Guide
This symbol on the product or on its packaging indicates that this product must not be disposed of with your other household waste. Instead, it is your responsibility to dispose of your waste equipment by handling it over to a designated collection point for the recycling of waste electrical and electronic equipment. The separate collection and recycling of your waste equipment at the time of disposal will help to conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment. For more information about where you can drop off your waste equipment for recycling, please contact your local city office, your household waste disposal service or the shop where your purchased the product.

6.4 Taiwan ROHS



S21 Hyd.















(Pb)

(Hg)

(Cd)

( Cr6+)

(PBB)















--











--











--











--





















 (PBDE)      

 1. 0.1 wt % 0.01 wt %  2.  3.

28

S21 Hyd. User Guide
6.5 FCC Supplier's Declaration of Conformity
Supplier's Declaration of Conformity Trade Name: Model Number: S21 Hyd. Responsible Part---U.S. Contact Information Company: Bitmain Technologies Delaware Limited Street Address: 100 Spectrum Center Drive, Suite 1255 City, State: City of Irvine, State of CA - California Zip Code: CA 92618 Telephone number: +1 949-381-9884 Internet contact information: https://www.bitmain.com/
FCC Compliance Statement: This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
29

6.6 EU Declaration of Conformity

S21 Hyd. User Guide

EU Declaration of Conformity
Manufacturer's Name: BITMAIN DEVELOPMENT PTE. LTD. Manufacturer's Address: 1 Raffles Place, #36-01 One Raffles Place, Singapore 048616
For the following equipment Trade Mark: Product: Server Model No.: S21 Hyd.
is herewith confirmed to comply with the requirements set out in Directive 2014/35/EU, Directive 2014/30/EU, and Directive 2011/65/EU. Compliance with 2014/35/EU and 2014/30/EU are evaluated by applying the following standards:
Safety standard: EN 62368-1:2014+A11 EMC standard: EN 55032:2015+A11:2020(Class A); EN 55032: 2015;
EN 55035: 2017; EN 55035: 2017+A11:2020 EN IEC 61000-3-2: 2019; EN 61000-3-3: 2013+A1:2019
This declaration of conformity is issued under the sole responsibility of the manufacture.

Signature: Position/Title: President of Product Division II

Date: 2025/2

30

7 Warranty

S21 Hyd. User Guide

1. A 365-day warranty is provided starting from the shipping date. BITMAIN will cover shipping costs when shipping a replacement unit within the warranty period. 2. The warranty only applies to the original purchaser who purchased the machine directly from BITMAIN. Once the miner is resold, warranty coverage becomes the responsibility of the re-seller. 3. If the user fails to use the product per the given instructions, specifications, and conditions provided or changes the function settings of the unit without BITMAIN's prior consent, BITMAIN will not be liable for any damage arising therefrom. 4. Click https://service.bitmain.com/support/policy for a complete list of the Terms & Conditions that apply to all orders placed on https://shop.bitmain.com. Note:  Only new machines are eligible for a 365-day warranty; used machines are not
included

31



References