Ion Digital Level Control

19 lug 2022 — Determine bracket mounting position (Figure A). 2. Mount bracket to Ion switch with screw already provided in Ion switch (Figure B).


File Info : application/pdf, 4 Pages, 2.37MB

PDF preview unavailable. Download the PDF instead.

IonDigitalLevelControl OM
Ion® Digital Level Control
Digital Level Control Switch
Patent pending
FEATURES
1. First of its kind, solid-state sensing technology with no moving parts.
2. Space age design with no mechanical contact points.
3. Multipoint sealing mechanism that supersedes single surface seals.
4. Inverter rated for use with any battery back-up system.
5. Standard piggy back connection for use with any pump.
6. Suitable for sump and sewage applications.
PIPE MOUNTING BRACKET (OPTIONAL)
1. Determine bracket mounting position (Figure A). 2. Mount bracket to Ion® switch with screw already
provided in Ion® switch (Figure B). 3. Mount hose clamp with switch around pipe
at predetermined level. Cable should remain outside hose clamp (Figure C). 4. Tighten hose clamp. Note: The Ion® switch is available in a 6" range. The range of the switch is the distance between the On and Off levels. The Off level is at the bracket mounting screw of the switch. From this point, measure up 6" to find the On level. Please refer to the Installation Drawing.

OPERATION MANUAL
Dated: 07/19/2022 Document Name: IonDigitalLevelControl_OM
Page 1 of 4

CAUTION: Bottom of switch should not be mounted lower than suction inlet of pump. When installing the Ion® switch with the pipe mounted bracket be sure not to set the switch too low or too high on the pipe. The Ion® switch must be installed above the inlet of the pump to prevent air-locking as shown in the installation drawing.
To prevent flooding do not set the on point of the switch higher than the top of the basin.

Model IN-006-010 IN-006-020

Cord 10 20

Range 6 6

PIGGY-BACK INSTALLATION
Electrical outlet must not be located in pump pit.
Electrical outlet voltage, piggy-back plug voltage and pump voltage must all be the same voltage.
DO NOT CUT plug off unit.
Ensure vent tube on plug is protected from moisture, dirt and insects and other items that could plug or block tube.
1. Insert the Ion® switch's piggy-back plug into the outlet.
2. Plug pump into piggy-back plug as (Figure E).
3. Allow system to cycle to ensure proper installation.
Please note this product may not work in conjunction with other controllers.
Safety PrecautionS
CAUTION: To prevent electric shock, ensure product is connected to a grounded outlet. The electrical outlet should be properly wired to a dedicated 15A circuit breaker. Proper short-circuit and overload protection must be provided at the distribution panel. Install in accordance with all local

www.ionproducts.net

Ion® Digital Level Control
Digital Level Control Switch
and national electrical codes. WARNING: Electrical outlet must not be located in pump pit. For best performance, do
not use electrical extension cords.
INSTALLATION DRAWING

OPERATION MANUAL
Dated: 07/19/2022 Document Name: IonDigitalLevelControl_OM
Page 2 of 4

FIGURE B

FIGURE C

3"

Ion® Digital Level Switch

FIGURE D

Ø 3 7/8"

Range of 6"

Recommended 1/8" anti-airlocking hole (if not already provided by pump
manufacturer)

Range of 6"

Lowest pump off level

BE SURE TO MOUNT THE ION SWITCH AT PROPER LEVEL.

FIGURE A

Optional bracket

NOTE: If you purchased a pump with the Ion switch hard-mounted to the pump (Figure D) and the installation requires the switch to be mounted to the pipe, the pipe-mount bracket is sold separately, PN: IN-SPB1-1.
FIGURE E

or

www.ionproducts.net

Ion® Switch piggy back
Pump plug

Ion® Digital Level Control
Digital Level Control Switch
TROUBLESHOOTING
Switch Does Not Turn On Pump 1. Test the pump without the Ion® switch
a. Plug the pump directly into the wall outlet, without plugging it into the switch plug.
b. If pump still does not run, see the troubleshooting section in the pump manual.
c. If the pump does run, continue to the next step.
2. Test the switch with the pump
a. Plug the pump into the Ion® switch and plug the Ion switch plug into the wall.
b. Push up on the sensing plate through the diaphragm surface. Please don't use any sharp object to push against the diaphragm. You may hear a small click sound when the pump is turned on.
c. If the pump does not turn on, the switch will have to be replaced.
d. If the pump does turn on, continue to the next step.
3. Verify the range of the switch
a. The part number can be found on the switch cord tag.
i. IN-006... = 6" range
b. For a pipe-mounted switch, see Page 2, Installation Drawing to verify that the On level is appropriate for your basin.
i. Lower the switch on the pipe so the On level is at a point within the basin, insuring that the Off level does not fall below the minimum level shown in the Installation Drawing.
ii. If the On level is still too high, the switch will have to be replaced with a lower

OPERATION MANUAL
Dated: 07/19/2022 Document Name: IonDigitalLevelControl_OM
Page 3 of 4
range Ion® switch.
c. For a pump-mounted switch, see Page 2, Figure D to verify that the On level is appropriate for your basin.
i. If the On level is too high, the switch will have to be replaced with a lower range Ion switch.
Switch Does Not Turn Off Pump 1. Unplug the pump from the Ion® plug and then unplug the Ion plug from the wall outlet.
2. Plug the pump back into the Ion® plug and plug the Ion plug back into the wall outlet.
a. If the pump does not turn on right away, and the water level is not at the On level, let the pump go through an On / Off cycle a few times to insure that the switch is functioning properly. The basin may need to be filled with a garden hose or bucket.
b. If the pump turns on right away, and the water level is not at the On level, the switch will have to be replaced.
WARRANTY IS VOID IF...
1. Using an extension cord.
2. Power cord has been cut or the grounding prong removed or using an adapter fitting.
3. The switch has been disassembled or tampered with.
4. Any tags or labels have been removed.
5. Used in a heavy grease application
6. Used in applications exceeding the designed temperature range of 32 - 104 degrees F.

www.ionproducts.net

Ion® Digital Level Control
Digital Level Control Switch

OPERATION MANUAL
Dated: 07/19/2022 Document Name: IonDigitalLevelControl_OM
Page 4 of 4

3 Year Residential Warranty

1.

Coverage and Term. Metropolitan Industries, Inc. ("Metropolitan") warrants to the original

purchaser (the "Buyer") of each Ion|StormPro product (the "product"), that any part thereof which proves to

be defective in material or workmanship within three (3) years from date of manufacture, will be replaced at

no charge with a new or remanufactured part, F.O.B. factory. Buyer shall be responsible for all freight charges

and all costs of field labor or other charges incurred in the removal and/or reinstallation of any product, part

or component thereof.

2.

Exclusions. THE WARRANTY IS SUBJECT TO THE FOLLOWING CONDITIONS AND

EXCLUSIONS:

(a)

The Warranty excludes products or workmanship which becomes defective as a result

of: (i) earthquake, fire, storms, the elements or any other acts of God; (ii) normal wear and tear from use;

(iii) accident, misuse, abuse or neglect; (iv) modifications made by Buyer or any third party, other than

Metropolitan; and (v) Buyer's failure to properly install, maintain, service and/or operate the product under

normal conditions and according to manufacturer's instructions.

(b)

Metropolitan shall not be responsible for, and the Warranty shall not cover, extended

damage which occurs because of Buyer's failure to notify Metropolitan promptly in writing of apparent

defects.

(c)

Any part or component designated as manufactured by anyone other than Metropolitan

shall be covered only by the express warranty of the manufacturer thereof.

(d)

The Warranty shall lapse upon Buyer's failure to fully comply with the terms and conditions

of its contract with Metropolitan, including Buyer's failure to pay the purchase price for the product or any

portion thereof. Buyer's subsequent compliance with the terms and conditions of any such contract, will not

cause the term of the Warranty to extend beyond the time period set forth above.

(e)

No actions taken by Metropolitan to correct a defect in a product shall extend the Warranty

beyond the period set forth above. Metropolitan shall not be obligated to remedy any defect, where otherwise

required pursuant to the Warranty unless and until Buyer notifies Metropolitan in writing of the defect and

then only if such notification is made prior to the expiration of the period set forth above.

3.

Process of Claims and Repairs. Metropolitan agrees that if the product or any part or component

thereof shall fail to conform to the terms of this Warranty, Metropolitan shall replace such nonconforming

product, part or component at the original point of delivery and furnish instruction for its disposition. Any

transportation charges involved in such disposition and all costs of field labor or other charges incurred in the

removal and/or reinstallation of any product, part or component thereof shall be the responsibility of Buyer.

4.

Limitation on Liability. Notwithstanding any provision to the contrary, Metropolitan's entire

liability under this Warranty shall not in the aggregate exceed, and Buyer's exclusive and sole remedies

are, to the extent permitted by law, shall be to secure replacement of the defective product. UNDER NO

CIRCUMSTANCES SHALL METROPOLITAN BE LIABLE UNDER THE WARRANTY FOR

ANY INDIRECT, PUNITIVE, SPECIAL, EXEMPLARY, CONSEQUENTIAL OR INCIDENTAL

DAMAGES (INCLUDING LOST PROFITS, REVENUE, USE OR ECONOMIC ADVANTAGE).

5.

Express Waiver of Any Other Warranties. THE EXPRESS WARRANTY SET FORTH IN THIS

WRITTENWARRANTYISTHE ONLYWARRANTYMADE BYMETROPOLITAN, ORANYOTHER

PARTY, IN CONNECTION WITH ANY PRODUCT PURCHASED FROM METROPOLITAN.

NEITHER METROPOLITAN, NOR ANY OTHER PARTY, MAKES ANY OTHER EXPRESS OR

IMPLIED WARRANTY WHICH IS NOT SET FORTH HEREIN, AND METROPOLITAN HEREBY

DISCLAIMS AND BUYER HEREBY WAIVES ALL IMPLIED WARRANTIES, INCLUDING THE

IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS

FOR A PARTICULAR PURPOSE.

6.

Not Transferable. The Warranty may not be transferred and shall be void on the sale or other transfer

of the product.

7.

Products and Warranty Subject to Change. Metropolitan reserves the right to make revisions to its

products and their specifications, and to revise this Warranty and related information without notice.

www.ionproducts.net

