HVS
Variable Speed Heat Pump

2 Ton HVS-24

3 Ton HVS-36

5 Ton HVS-60

Installation and Operation

From the Manufacturers of Hi-Velocity SystemsTM www.hi-velocity.com

Module-HVS-Variable-Speed-Heat-Pump-120121b

www.hi-velocity.com
HVS Variable Speed Heat Pump

Module HVS Variable Speed Heat Pump Installation

HVS Series Inverter Drive Variable Speed Heat Pumps are ideally suited for any application. When used with the HE-Z Series, the system modulates refrigerant flow and indoor air flow to precisely match output capacity to load. The ability to match output capacity to load results in superior energy performance not just at the ANSI/AHRI Standard test conditions but right through the entire operational range.

Fixed speed and 2-staged condensing units are not well suited for constantly changing load requirements and multizone applications due to their inability to reduce capacity below 70%. These systems overcome the problem by running the indoor fan at high flow rates and dumping or bypassing excess air. This strategy wastes energy, reduces efficiencies and sacrifices comfort in exchange for a properly functioning system.
The HVS Variable Speed Heat Pump in conjunction with the HE-Z Series Air Handler solves this ongoing issue. The outdoor unit (inverter) monitors indoor coil (evaporator) conditions to maintain a steady air off temperature. No matter the load or number of zones open, the Variable Speed Heat Pump will adjust refrigerant flow or capacity to match these everchanging conditions.

HVS Location Selection
· The outdoor unit must be installed level, in a properly supported outdoor location that is adequately ventilated. Avoid installing outdoor unit on walkways and patios.
· Outdoor unit should be installed using the rubber vibration isolation feet that were supplied with the outdoor unit.
· It is good practice to secure the outdoor unit to its footings or base. If unit is to sit on an equipment riser, stand or hanger, it must be properly secured.
· Locate the outdoor unit as close as possible to the indoor unit. Ensure minimum and maximum lineset lengths meet the min/max length specifications on page 4.
· Outdoor unit should be installed in a location that can maintain the clearances specified on page 3 to ensure proper airflow/heat exchange and maintenance space.
· Must be elevated above the Annual Snow Accumulation Level or average snow fall depths.
· Make sure the piping/lineset vertical height drops do not exceed the allowable value specified on page 4.
· Locate the outdoor unit where the noise, vibration and outlet air does not disturb residence, occupants or neighbors.
· Ensure the air inlet or outlet is not impeded and does not face strong/prevailing winds.

2

-2-

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com

Module HVS Variable Speed Heat Pump Installation

HVS Location Selection Cont'd
· Avoid locating the outdoor unit in a location that is severely dirty, polluted, or contaminated (e.g. close to a dryer vent or under a tree) to avoid blockage of the heat exchanger. If it is, maintenance or cleaning may be needed more than bi-annually.
· If the outdoor unit is installed under an overhang or in an encloser to protect it from direct sunlight, rain exposure, snow, or strong winds, ensure it still maintains the needed clearances and avoid roof driplines.

Clearances

More than 12" (30 cm)
OFbesntcaecloer

More than 12" (30 cm)
More than 24" (60 cm) More than 80" (200 cm)

More than 24" (60 cm) (Service Space)

24" (600 mm) is necessary between 2 outdoor units
24" (60 cm)

3

-3-

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com
Refrigeration Circuit

Module HVS Variable Speed Heat Pump Installation

Important: Pipe Insulation (min. 3/8") MUST be used on both liquid and suction lines. Ensure insulation covers the entire line set, including flare fittings & penetrations.

· The Electronic Expansion Valve is internal to the HVS Variable Speed Heat Pump, therefore a TXV at the evaporator (indoor unit) is not needed.
· Maximum pipe length for the HVS-24 is 164.5' (50 m), for the HVS-36 and HVS-60 is 213 ft (65 m). Lines must be sized correctly to ensure that pressure drops within the system are minimized. HVAC mechanics should refer to the pipe sizing table below prior to installation.
· Minimum refrigerant pipe length is 16 ft (5 m). If going less than 16 ft, coil the additional copper pipe up in horizontal loops to ensure proper oil return.
· Refrigeration grade copper tubing is the only tubing to be used. Fittings used for bends, elbow, `P' trap, `Y' piece, etc., must be of the wrought copper type and clean from dust, burrs, oil, etc. It is recommended that the tube is cut with a tube cutter and the entire ID is made the correct size with an expanding device after cutting. All joints in the piping must be clean and free from dust, burrs, oil, etc.
· All joints must be silver soldered with at least 10% silver content.
Minimum pipe sizes, maximum length and maximum lift

Model

Liquid Line

Suction Line

Maximum Length

Maximum Lift

HVS-24 HVS-36 HVS-60

3/8" (9.5 mm) 3/8" (9.5 mm) 3/8" (9.5 mm)

5/8" (15.9 mm) 5/8" (15.9 mm) 3/4 (HVS_60 = 7/8")

164.5' (50 m) 213.25' (65 m) 213.25' (65 m)

82' (25 m) 98.4' (30 m) 98.4' (30 m)

The HVS Variable Speed Heat Pump comes with a factory charge. Additional charge will only be needed on line sets longer than 25 ft. (See table below)
Minimum pipe sizes, factory charge and additional refrigerant required

Model
HVS-24 HVS-36 HVS-60

Liquid Line
3/8" (9.5 mm) 3/8" (9.5 mm) 3/8" (9.5 mm)

Suction Line
5/8" (15.9 mm) 5/8" (15.9 mm) 3/4 (HVS_60 = 7/8")

Factory Charge (kg)
5.18 lbs (2.35 kg) 6.75 lbs (3.06 kg) 10.15 lbs (4.6 kg)

Add extra refrigerant for line sets
over 25 ft (7.5 m)
1 oz/ 3 ft 1 oz/ 3 ft 1 oz/ 3 ft

Flare Connections
When tightening flare connections on the HVS Heat Pump, refer to tightening torque and flare shape below. It is suggested to use "Nylog Blue" to seal flare connections. (If doing so, tighten to the lower end of the range of the chart below.)

Pipe Size
1/4"Ø (6.4 mm) 3/8"Ø (9.5 mm) 1/2"Ø (12.7 mm) 5/8"Ø (15.9 mm) 3/4"Ø (19.1 mm) 7/8"Ø (22.2 mm)
4

Tightening Torque
13 - 15 ft-lb (18-20 N.m.) 24 - 29 ft-lb (32-39 N.m.) 36 - 44 ft-lb (49-60 N.m.) 42 - 52 ft-lb (57-71 N.m.) 49 - 74 ft-lb (67-101N.m.) 63 - 81 ft-lb (85-110 N.m.)
--44--

Flare Dimensions (A)

Min.

Max.

0.33"
(8.4 mm)

0.34"
(8.7 mm)

0.52"
(13.2 mm)

0.53"
(13.5 mm)

0.64"
(16.2 mm)

0.65"
(16.5 mm)

0.76"
(19.3 mm)

0.78"
(19.8 mm)

0.91"
(23.2mm)

0.93"
(23.7 mm)

1.04"
(26.4 mm)

1.06"
(26.9 mm)

Flare Shape

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com
Installing Oil Traps

Module HVS Variable Speed Heat Pump Installation

For proper oil return to compressor, oil traps must be installed on the suction line risers: - Every 33 ft (10 m) when indoor unit is higher than the outdoor unit. - Every 20 ft (6 m) when outdoor unit is higher than the indoor unit

Indoor is Higher than Outdoor

Gas Piping Oil Trap

Indoor Unit

Outdoor is Higher than Indoor

Gas Piping Oil Trap

Outdoor Unit

Outdoor Unit
5

33 ft Liquid (10 m) Piping
33 ft (10 m)
Indoor Unit
Oil Trap Detail
8" Minimum (200 mm)
Minimum bend radius of 6x
diameter of pipe -5-

Liquid Piping

20 ft (6 m)

20 ft (6 m)

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com
Interface Panel

Module HVS Variable Speed Heat Pump Installation

· The interface panel is critical for indoor and outdoor unit communication.
· Field wiring shown on the wiring page is needed between the indoor unit and the interface panel, and between the interface panel and the outdoor unit using unshielded cable on the HVS-24, and shielded cable on the HVS-36 & HVS-60.

IMPORTANT
For the HVS-24 ­ It is critical to use unshielded communication cable (14 AWG / 4 Conductor, stranded) when running the 1, 2 and 3 communication wires between the '24v Interface Kit' and the HVS-24 outdoor unit.
For the HVS-36 & HVS-60 ­ It is critical to use shielded cable (18 AWG / 4 Conductor) when running the S1 and S2 communication wires between the '24v Interface Kit' and the outdoor unit.
See wiring diagrams for further details.

· Ground shielding of cable at the condenser side and cap off opposite end with a wire nut or equivalent.
· Use provided EMC magnetic ring. Wrap the communication wires around the ring twice at the `24v Interface Kit' side of the communication wires:

EMC Magnetic Ring - HVS-24
Wrap the electric wires 1, 2 and 3
around the magnetic ring twice

EMC Magnetic Ring - HVS-36 & HVS-60
Wrap the electric wires S1 and S2 ( P & Q & E ) around the magnetic ring twice

· The outdoor unit and the interface panel both require 240v supply power and require surge protection in locations with power fluctuations or inconsistencies.
NOTE: For HVS-24 the interface panel is provided with 240v via the outdoor unit. In this case, only the outdoor unit requires surge protection.
For HVS-36 and HVS-60 the interface panel and outdoor unit require separate power supplies. In this case, both need to be surge protected.
· The interface requires 24v from indoor unit (R & C).
· One temperature sensor is supplied with the interface panel which connects to T1 on the interface panel. This temperature sensor will need to be installed for the unit to operate properly and should be securely installed in the return air ductwork.

6

-6-

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com
Return Air Temperature Sensor

Module HVS Variable Speed Heat Pump Installation

· For the HVS variable speed heat pump to modulate correctly, the provided return air temperature sensor must be installed in the return air ductwork, just upstream from the evaporator.
· A small hole must be drilled into the return air ductwork to fit the temperature sensor in.
· This sensor should be secured using tie straps/nylon cable ties or screw mount cable ties.
· The hole drilled must be sealed back up after the sensor is screwed in the R/A ductwork.
· This T1 temperature sensor must not exceed 23' (7m) in length. This means that the interface panel must be placed within reach of the R/A ductwork just upstream from the evaporator.

Drain Fitting Installation (not provided w/ all models)
1. Fit the rubber seal on the end of the drain fitting that will connect to the outdoor unit. 2. Insert the drain fitting into the hole in the base pan of the unit (located on bottom panel of unit). 3. Rotate the drain fitting 90o until it clicks in place, facing the front of the unit. 4. Connect a drain hose extension (not provided) to the drain fitting to redirect water from the unit (if desired) during
heating mode.
Important: Make sure water drains to a safe location that meets local codes and regulations and where it will not cause water damage or a slipping hazard.

Seal

Base pan hole of outdoor Unit
Note: Make sure water drains to a safe location that meets local codes and regulations and where it will not cause water damage or a slipping hazard.

7

-7-

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com

Module HVS Variable Speed Heat Pump Installation

HVS-24 Variable Speed Heat Pump Wiring

AIRFAHNANCDOLILER

O/B

L A3 A2 A1 N

D

Y1

Y2

R

G

C R C Y1 Y2 W2W1 FZ FZ W2

W1

THERMOSTAT

R

C

Y1 W1 - 1st

Y2 Stage Heat

G (Inverter) W2 - 2nd

W2 Stage Heat

W1

(Hydronic/ Electric)

G1 G2 G3

R C ONOFF

Freeze stat

INTERFACE PANEL

INTERFACE BOARD TO INDOOR TO OUTDOOR T 5A/250VAC
CN12 CN11

BK BL BR BK BL BR
G

OUTSIDE INVERTER
G 1 2 3 L1 L2 G
L1 L2 G INPUT VOLTAGE 208-240/1/50-60
14 AWG/ 4 Conductor, stranded, unshielded communication cable
Magnetic Ring

SW-1 SW-2 SW-3 SW-4 ON ON ON ON ON ON ON ON 12 12 12 12
SWITCH # EARTH 123 123

YWG

TO OUTDOOR TO INDOOR

PQE S1 S2

PQE S1 S2

BLACK INDICATES DIP SWITCH POSITION
T1 WORK ALARM TO RETURN AIR SENSOR
8
-8-

HVS24CNTL 062520
© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com

Module HVS Variable Speed Heat Pump Installation

HVS-36 & HVS-60 Variable Speed Heat Pump Wiring

AIRFAHNACNODILLER

O/B

L A3 A2 A1 N

D

Y1

Y2

R

G

C R C Y1 Y2 W2W1 FZ FZ W2

W1

THERMOSTAT

R

C

Y1 W1 - 1st

Y2 Stage Heat

G (Inverter)

W2 - 2nd

W2 Stage Heat

W1

(Hydronic/ Electric)

Freeze stat

INTERFACE PANEL

R C ON OFF

INTERFACE BOARD

TO INDOOR TO OUTDOOR T 5A/250VAC
CN12 CN11

BK

BL

BR

BK

BL

L2

BR

L1

G1 G2 G3

G

YWG

** Wire nut Ground Wire Magnetic Ring
OUTSIDE INVERTER

PQE S1 S2

BLACK INDICATES DIP SWITCH POSITION

SW-1 SW-2 SW-3 SW-4 ON ON ON ON ON ON ON ON 12 12 12 12
SWITCH # EARTH 123 123 INPUT VOLTAGE 208-240/1/50-60

TO OUTDOOR TO INDOOR

G

PQE S1 S2

(1)L1 (2)L2

DO NOT G USE

S1 S2

T1 WORK ALARM

L1 L2

L1 L2 INPUT VOLTAGE

G

208-240/1/50-60

**Use Shielded 18 AWG/ 4 conductor cable with shield grounded at Condenser.

TO RETURN AIR SENSOR

HVS36/60CNTL 062520

9

-9-

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com

Module HVS Variable Speed Heat Pump Installation

HVS Variable Speed Heat Pump Specifications - Dimensions

HVS-24/HVS-36

FRONT VIEW 38"
(965mm)

SIDE VIEW 15.5"
(394mm)

32"
(813mm)

16.14"
(410mm)

TOP VIEW 26.5"
(673mm)

15.5" 15.87"
(394mm) (403mm)

10

-10-

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com

Module HVS Variable Speed Heat Pump Installation

HVS Variable Speed Heat Pump Specifications - Dimensions

HVS-60

FRONT VIEW 37.5"
(953mm)

SIDE VIEW 15.5"
(394mm)

52.5"
(1334mm)

16.14"
(410mm)
11

TOP VIEW 26.5"
(673mm)

15.5" 15.87"
(394mm) (403mm)

-11-

© 1995-2024 Energy Saving Products Ltd.

www.hi-velocity.com

Module HVS Variable Speed Heat Pump Installation

HVS Variable Speed Heat Pump Specifications

Specifications
Part Number

HVS-24
40180400002

HVS-36
40180400003

Outdoor Unit Tonnage
Capacity Data
Nominal Cooling Capacity(1) (2)

2 Ton (7 kW) 23,500 BTU (6.9 kW)

3 Ton (10.5 kW) 35,500 BTU (10.4 kW)

Operational Range (Cooling) Nominal Heating Capacity(1) (2)

6,000-24,000 BTU (1.8 - 7 kW) 26,200 BTU (7.7 kW)

9,000-36,000 BTU (2.6 - 10.5 kW) 38,200 BTU (11.2 kW)

Operational Range (Heating)

6,950-27,800 BTU (2.0 - 8.1 kW)

10,325-41,300 BTU (3.0 - 12.1 kW)

Highest Variable Airflow

2,350 CFM (1,109 L/s)

2,500 CFM (1,180 L/s)

Lowest Variable Airflow
Electrical Data
Power Supply
Nom. Full Load Amps

400 CFM (190 L/s)
208 - 240 Volts 1 Phase - 50/60 Hz
17

400 CFM (190 L/s)
208 - 240 Volts 1 Phase - 50/60 Hz
23

Min. Circuit Ampacity

22

30

Max Fuse

30

45

Electrical Input Cooling (kW)(1)

2.0

3.25

Electrical Input Heating (kW)(1)

2.3

3.15

Sound Pressure (dB) (A) @ 1m

61

62

Soft Starter

Variable Frequency

Dimensions - Outdoor Unit
Dimensions (L x W x H) Weight

38" x 16.14" x 32"
(965mm x 410mm x 813mm)
155 lbs (70.3 kg)

38" x 16.14" x 32"
(965mm x 410mm x 813mm)
155 lbs (70.3 kg)

(1) Capacities are based on A.S.3823.12 (2) Capacity modulation is extended by variable indoor airflow. Actual percentage loading will vary depending on application.
DESIGN CONDITIONS: Cooling 35°C (95°F) DB Outdoor / 27°C (80°F) DB, 19°C (66°F) WB Air Entering Indoor Unit Heating 7°C (44°F)DB, 6°C (43°F) WB Outdoor/ 21°C (70°F) DB Air Entering Indoor Unit Nominal Operating Range -10°C (14°F) WB to 50°C (122°F) DB Sound pressure level is influenced by the surroundings, therefore it may vary upon location.
Features:
· Variable Speed Compressor allows for Zoning with True Efficiency · 2, 3 or 5 Ton Cooling Capacity · Easy Installation
· Energy Efficient Zoning · Patented Interface allows Integration with 3rd Party Air Handlers 12
-12-

HVS-60
40180400005 5 Ton (17 kW) 57,300 BTU (16.8 kW) 15,000-60,000 BTU (4.4 - 17.6 kW) 60,400 BTU (17.7 kW) 15,375-61,500 BTU (4.5 - 18.0 kW) 4,400 CFM (2,077 L/s) 400 CFM (190 L/s) 208 - 240 Volts 1 Phase - 50/60 Hz
26.5 36.5 50 5.3 5.2 63
37.5" x 16.25" x 52.5"
(953mm x 413mm x 1,334mm)
269 lbs (122 kg)
© 1995-2024 Energy Saving Products Ltd.

Energy Saving Products Ltd, established in 1983, manufactures the Hi-Velocity
SystemsTM product line for residential, commercial and multi-family markets. Our facilities house Administration, Sales, Design, Manufacturing, as well as Research & Development complete with an in-house test lab. Energy Saving Products prides itself on Customer Service and provides design services and contractor support.
For all of your Heating, Cooling and Indoor Air Quality needs, the Hi-Velocity System is the right choice for you!
TM
Small Duct Heating, Cooling and IAQ Systems
Build Smart, Breathe Easy
Hi-Velocity HE-Z Air Handlers, Green Technology
Phone: 780-453-2093 Fax: 780-453-1932
Toll Free: 1-888-652-2219
www.hi­velocity.com



References

Adobe PDF Library 17.0 Adobe InDesign 19.4 (Windows)