N1540 Digital Panel Meter

Universal Digital Panel Meter

INSTRUCTIONS MANUAL – V2.1x F

SAFETY ALERTS

The symbols below are used on the equipment and throughout this manual to draw the user's attention to essential information related to the equipment safety and operation.

CAUTION: Read the manual thoroughly before installing and operating the instrument.

CAUTION OR DANGER: Electrical shock hazard.

All safety related instructions that appear in the manual must be observed to ensure personal safety and to prevent damage to either the instrument or the system. If the instrument is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

PRESENTATION

N1540 is a versatile process digital panel meter. With a wide list of input types - thermocouples, thermo-resistance, voltage and current - the N1540 can measure most of the variables and sensors encountered in industrial processes.

It contains two alarms (six functions), sensor offset, configuration of parameters protected by password, serial communication, indication in degrees Celsius (°C) or Fahrenheit (°F), among others.

Configuration can be performed either directly on the digital panel meter or via the USB interface once QuickTune software has been installed on the computer. Once connected to USB, the device will be recognized as a serial communication (COM) port operating with Modbus RTU protocol.

Through the USB interface, even if disconnected from the power supply, the configuration performed in a piece of equipment can be saved in a file and repeated in other pieces of equipment that require the same configuration.

FEATURES

SIGNAL INPUT (TYPE)

The input type to be used by the N1540 is defined in the equipment configuration. Table 1 presents the input options available for the user:

TYPE CODE MEASUREMENT RANGE
J J Range: -110 to 950 °C (-166 to 1742 °F)
K K Range: -150 to 1370 °C (-238 to 2498 °F)
T T Range: -160 to 400 °C (-256 to 752 °F)
N N Range: -270 to 1300 °C (-454 to 2372 °F)
R R Range: -50 to 1760 °C (-58 to 3200 °F)
S S Range: -50 to 1760 °C (-58 to 3200 °F)
B B Range: 400 to 1800 °C (752 to 3272 °F)
E E Range: -90 to 730 °C (-130 to 1346 °F)
Pt100 Pt Range: -200 to 850 °C (-328 to 1562 °F)

ALARMS

The digital panel meter has two alarms. Each alarm is associated with an output with the same name: AM1 and ALM2.

The alarms can assume the functions described on Table 02.

Sensor breaks alarm: It is activated when the Input Err presents problems such as interrupted sensor, bad connection, etc.

Note: The figures are also valid for Alarm 2 (SPA2).

Important note: Alarms configured with the H1, d IF and d IF.H functions also trigger their associated output when a sensor fault is identified and signaled by the digital panel meter. A relay output, for example, configured to act as a High Alarm (H 1), will operate when the SPAL value is exceeded and when the sensor connected to the input is broken.

ALARM BLOCKING INITIAL

The Initial Blocking option inhibits the alarm from being recognized if an alarm condition is present in the process when the digital panel meter is first energized. The alarm will be enabled only after the occurrence of no alarm condition.

The initial blocking is useful, for example, when one of the alarms is set up as a minimum value alarm, which may cause the activation of the alarm soon upon the process start-up; an occurrence that may be undesirable in many cases.

The initial blocking is not valid for the Err (Sensor Break) function.

OFFSET

Allows fine adjustments to the PV indication, correcting measurement errors that appear, for example, after the replacement of the temperature sensor.

MAXIMUM AND MINIMUM

The digital panel meter memorizes the measured maximum and minimum values (peak and valley). The operator can observe these extreme values at any time. These two values are shown when pressing the F1 (maximum) and F2 (minimum) keys. Pressing both keys simultaneously will clear the memory for a new peak and valley detection.

To clear the stored values and begin a new cycle of monitoring endpoints, just press the F1 and F2 keys simultaneously. When turn off, the digital panel meter this information is not saved.

CUSTOM LINEARIZATION

This feature allows accurate measurement of the input signals with non-linear features. Linearization consists in dividing the calibration curve of the input signal into segments of variable gain. Each segment consists of a start and an end. For each input value (InP.xx), a respective output indication (oup.xx) is defined. The input signal must present an always-crescent. Applied to 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V input types.

24 VDC AUXILIARY VOLTAGE SOURCE

The standard version of the N1540 provides an auxiliary power supply for exciting field transmitters (terminals 11 and 13 on the rear panel).

SERIAL COMMUNICATION

Follows a description of the usual communication registers. For full documentation, download the Registers Table N1540 for Serial Communication on our web site: www.novusautomation.com.

RS485 INTERFACE: ELECTRICAL CONNECTION

The RS485 signals are:

D1 D0 C Terminal 17
DD+B DD-A Optional connection that improves the communication performance Terminal 18
Terminal 19 GND

USB INTERFACE

The USB interface is used to CONFIGURE, MONITOR or UPDATE the controller FIRMWARE. The user should use QuickTune software, which offers features to create, view, save, and open settings from the device or files on the computer. The tool for saving and opening configurations in files allows the user to transfer settings between devices and perform backup copies.

For specific models, QuickTune allows to update the firmware (internal software) of the controller via the USB interface.

For MONITORING purposes, the user can use any supervisory software (SCADA) or laboratory software that supports the Modbus RTU communication over a serial communication port. When connected to a computer USB, the controller is recognized as a conventional serial port (COM x).

The user must use QuickTune software or consult the DEVICE MANAGER on the Windows Control Panel to identify the COM port assigned to the controller.

The user should consult the mapping of the Modbus memory in the controller communication manual and the documentation of the supervision software to start the MONITORING process.

Follow the procedure below to use the USB communication of the device:

  1. Download QuickTune software from our website and install it on the computer. The USB drivers necessary for operating the communication will be installed with the software.
  2. Connect the USB cable between the device and the computer. The controller does not have to be connected to a power supply. The USB will provide enough power to operate the communication (other device functions may not operate).
  3. Run the QuickTune software, configure the communication and start the device recognition.

INSTALLATION / CONNECTIONS

The digital panel meter is meant for panel mounting. The sequence of steps is:

Note: RS485 Communication and PV Retransmission features are mutually exclusive.

INSTALLATION RECOMMENDATIONS

OPERATION

The front panel can be seen on Figure 7:

Display: Shows the process variable PV, the configuration parameters prompts and their respective values/conditions.

Indicators A1 and A2: Signalize the occurrence of an alarm condition.

Key P: Used to walk through the parameters in the menu cycles.

F1 / key and F2 / key: Used to change parameter values.

Key: Used to back to the previous displayed parameter.

START-UP

When the digital panel meter is powered up, the digital panel meter displays the number of the software version in the first 3 seconds, then the value of the measured process variable (PV) is shown in the display. This is the Indication Screen.

To be used, the digital panel meter must be previously configured. The configuration consists of the definition of each of the various parameters displayed. The user must understand the importance of each parameter and determine a valid condition or a valid value for each one of them.

The configuration parameters are grouped in levels according to their affinity. The 5 parameters levels are:

The P key provides the access to the levels and to the parameters of these levels.

Keeping the P key pressed, at every 2 seconds, the digital panel meter jumps from one level to another, presenting the first parameter of each level: PV >> FUR 1 >> EYPE >> L.EnbL >> PASS >> PV

To enter a particular level, simply release the P key when the first parameter in that level is displayed.

To walk through the parameters in a level, press the P key with short strokes. To go back to the previous parameters, use the Key.

After the last parameter of the cycle, the digital panel meter always returns to the PV Indication screen.

The display alternates the presentation of the parameter prompt and its value. The parameter value is displayed with a light blinking to differentiate it from the parameter prompt.

Depending on the level of parameter protection adopted, the PASS parameter precedes the first parameter in the level where the protection is active. See CONFIGURATION PROTECTION section.

PARAMETERS DESCRIPTION

OPERATION CYCLE

ALARMS CYCLE

INPUT CYCLE

CALIBRATION CYCLE

All types of input are calibrated in the factory. In case a recalibration is required; it shall be carried out by a specialized professional. In case this cycle is accidentally accessed, do not perform alteration in its parameters.

The factory calibration can be restored in the Str parameter.

CUSTOM LINEARIZATION CYCLE

CONFIGURATION PROTECTION

The digital panel meter provides means for protecting the parameters configurations, not allowing modifications to the parameters values, avoiding tampering or improper manipulation.

The Protection (Prot) parameter in the Calibration level determines the protection strategy, limiting the access to certain levels, as shown in the table below:

PROTECTION LEVEL PROTECTED LEVELS
1 Only the Calibration level is protected.
2 Custom Linearization and Calibration levels are protected.
3 Input, Custom Linearization, and Calibration levels are protected.
4 Alarms, Input, Custom Linearization, and Calibration levels are protected.

ACCESS PASSWORD

When accessed, the protected levels request the user to provide the Access Password for granting permission to change the configuration of the parameters on these levels.

The PASS screen precedes the parameters on the protected levels. If no password is entered, the parameters of the protected levels can only be visualized.

The Access Password is defined by the user in the parameter Password Change (PAS.C), present in the Calibration Level. The factory default for the password code is 1111.

PROTECTION OF THE ACCESS PASSWORD

The protection system built into the digital panel meter blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password.

MASTER PASSWORD

The Master Password is intended for allowing the user to define a new password in the event of it being forgotten. The Master Password does not grant access to all parameters, only to the Password Change parameter (PASC).

After defining the new password, the protected parameters may be accessed (and modified) using this new password.

The master password is made up by the last three digits of the serial number of the digital panel meter added to the number 9000. As an example, for the equipment with serial number 07154321, the master password is 9 3 2 1.

The serial number can be obtained by pressing the key for 5 seconds.

INPUT CALIBRATION

All inputs are factory calibrated and recalibration should only be done by qualified personnel. If you are not familiar with these procedures, do not attempt to calibrate this instrument.

The calibration steps are:

  1. Configure the input type to be calibrated.
  2. Configure the lower and upper indication limits for the maximum span of the selected input type.
  3. Connect to the input terminals a signal corresponding to a known indication value a little above the lower display limit.
  4. Access the InLc parameter. With the and keys, adjust the display reading to match the applied signal. Then press the P key to store it.
  5. Inject a signal that corresponds to a value a little lower than the upper limit of indication.
  6. Access the inhc parameter. With the and keys, adjust the display reading to match the applied signal. Then press the P key to store it.
  7. Validate the calibration.

Note: When checking the calibration with a Pt100 simulator, pay attention to the simulator minimum excitation current requirement, which may not be compatible with the 0.170 mA excitation current provided by the digital panel meter.

ANALOG OUTPUT CALIBRATION

  1. Configure the retransmission type (rEtr = P.0.20).
  2. Install a milliampere meter at the terminals 18(+) and 19(-).
  3. Enter the Calibration Cycle.
  4. Select the OuLC screen.
  5. Press the key or the key.
  6. Read the current value displayed on the milliampere meter. Through the and keys, adjust the value displayed on the digital panel meter to match the value displayed on the milliampere meter.
  7. Press the P key to save and access the ouHC parameter.
  8. Press the key or the key.
  9. Reread the new current value displayed by the milliampere meter. Through the and keys, adjust the value displayed on the digital panel meter to match the value displayed on the milliampere meter.
  10. Read the current displayed in the milliampere meter and indicated in the ouHc screen through the and keys.
  11. Exit the Calibration Cycle.
  12. Validate the performed calibration.

SPECIFICATIONS

CERTIFICATIONS:

IDENTIFICATION
N1540 Basic version.
N1540-24V Basic version with power supply 24 V.
N1540-485 With serial communication RS485.
N1540-485-24V Version with RS485 and power 24 V.
N1540-RT Version with PV retransmission.
N1540-RT-24V Version with PV retransmission and power supply 24 V.

Note:

  1. Communication signals are electrically isolated from the other of the circuits.
  2. The analog output circuit is electrically isolated from the other circuits.
  3. RS485 Communication and PV Retransmission features are mutually exclusive.

MAINTENANCE

PROBLEMS WITH THE DIGITAL PANEL METER

Connection errors and inadequate programming are the most common problems encountered during the operation. A final revision can avoid loss of time and damages.

The digital panel meter displays some messages to help the user identify the problems.

MESSAGE PROBLEM DESCRIPTION
Err 1 Open input. Without sensor or signal.
Err6 Connection and / or configuration problems. Check the wiring and the configuration.

Other error messages may indicate hardware problems requiring maintenance service.

WARRANTY

Warranty conditions are available on our website www.novusautomation.com/warranty.

Models: N1540 Digital Panel Meter, N1540, N1540 Meter, Digital Panel Meter, Digital Meter, Panel Meter, Meter

File Info : application/pdf, 7 Pages, 929.62KB

PDF preview unavailable. Download the PDF instead.

manual-n1540-v21x-f-en-4

References

NOVUS Automation Adobe PDF Library 22.2.244

Related Documents

Preview Novus N322 Temperature Controller Operation Manual
This manual provides detailed information on the operation, specifications, and configuration of the Novus N322 temperature controller, suitable for heating and cooling applications with various sensor inputs like Pt100, Pt1000, NTC, and thermocouples (J, K, T). It covers electrical connections, parameter settings, error indications, and warranty information.
Preview N1040 Controller: Instructions Manual
Comprehensive instructions manual for the NOVUS N1040 Temperature Controller, covering installation, electrical connections, features, alarm functions, control strategies, and serial communication.
Preview Novus TxIsoRail-HRT Temperature Transmitter: Operating Manual & Specifications
Explore the Novus TxIsoRail-HRT, a versatile DIN rail mount temperature transmitter designed for industrial applications. This manual details its universal input capabilities (RTD, Thermocouple, mV), 4-20mA output with HART communication, and electrical isolation features for reliable temperature measurement and process control.
Preview Novus N2000S Controller User Guide: Universal Process Controller
Comprehensive user guide for the Novus N2000S Universal Process Controller, detailing its features, operation, configuration, installation, and troubleshooting for process automation.
Preview NOVUS N1200 Controller User Guide
Comprehensive user guide for the NOVUS N1200 Process Controller, detailing its features, configuration, installation, operation, and communication protocols. Learn about PID control, ramp/soak programming, and serial communication for industrial applications.
Preview Manual de Instruções DigiRail OEE V1.4x - Novus
Guia completo para instalação, configuração e operação do dispositivo DigiRail OEE da Novus, cobrindo protocolos MQTT e Modbus-TCP, interfaces de comunicação e especificações técnicas.
Preview N1030 Temperature Controller Instruction Manual
Instruction manual for the Novus N1030 Temperature Controller, covering features, installation, operation, PID parameters, maintenance, and specifications.
Preview NOVUS NVE-2W-EPV120KP Villa Entrance Panel Installation Manual
Comprehensive installation manual for the NOVUS NVE-2W-EPV120KP Villa Entrance Panel, covering safety, installation, operation, configuration, and technical specifications. This guide provides detailed instructions for setting up and managing the device.