ADS-3R-BUS
INSTALLATION MANUAL
TIS ADS BUS 3 RELAYS MODULE SMALL RELAY MODULE
Model: ADS-3R-BUS

PRODUCT INFORMATION
The BUS ADS Relay is a small module with 3 relays that can be used to control lights, shutters, and FCU. It can be located anywhere to complete your installation and minimize the electrical wiring.

Output Output switching current Output service life Output switching times
TIS BUS
Operation Dimensions Housing

PRODUCT SPECIFICATIONS

Number of relays Nominal voltage Nominal current per channel

3 0- 230 V AC 50/60 Hz 8 A / 230 VAC

Max. Switching current
Max. Continues current Max. Switching voltage

10A/230 VAC resistive 6A/230 VAC florescent 8A/230 VAC 277VAC / 30VDC

Mechanical endurance

> 10,000,000 OPS

Operating time Releasing time Max. operating frequency

8 mS (at nomi. Volt) 5 mS (at nomi. Volt) 25 cycle/min

Number of devices on 1 line Max. 64

Bus voltage

12-32 V DC

Current consumption (Normal) <10 mA / 24 V DC

Current consumption (Peak) <30 mA / 24 V DC

Protection

Reverse polarity protection

Programming button/LED By TIS bus Programming

For assignment of the physical address TIS protocol messages and commands Manual basic programming or via software

(Width × Length × Height)

50mm × 35mm × 50mm

Materials Internal parts color IP rating

Fireproof PC White IP 50

BARCODE (UPC-A) 6 58921 79623 8

INSTALLATION MANUAL
TIS ADS BUS 3 RELAYS MODULE
Model: ADS-3R-BUS

Read Instructions
We recommend that you read this Instruction Manual before installation.
Safety instructions
Electrical equipment should only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause damage to the device and other hazards. These instructions are an integral part of the product and must remain with the end customer.
Simple Installation
it fits on most junction box sizes or can be located anywhere.

Data Cable
Use screened stranded RS485 data cable with four twisted pairs. Configure devices in a "Daisy Chain." Do not cut or terminate live data cables.
Electrical Wires
The recommended wire size for light channels is 2.5mm, for the Line, Neutral, and Load cables. The installer should consider the total current consumption when selecting the wires.
Warranty
There is a two-year warranty provided by law. The hologram warranty seal and product serial number are available on each device.

Mounting Location
Install in a dry, indoor area with a suitable temperature and humidity range.

2
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL. All of the specification are subject to change without notice.

TIS CONTROL PTY LIMITED SA , AUSTRALIA

www.tiscontrol.com

TIS CONTROL LIMITED Wanchai, Hong Kong

INSTALLATION MANUAL
TIS ADS BUS 3 RELAYS MODULE
Model: ADS-3R-BUS

INSTALLATION STEPS

1

Turn off the main electrical source

before installation.

Circuit Breaker OFF

WARNING! HIGH VOLTAGE

2

Connect a cat5e TIS network data

cable to the TIS-BUS port as per the

connection diagram.

S3 S2 S1 C

Cat5e 24V D+ D- GND

To the TIS BUS Network

Cat5e connection

GND(Black) D-(Green) D+(Red) 24V(White)

3

Complete the load connection, light,

shutter, and FCU as per the following

steps:

Connect To N

LIGHTS / APPLIANCES / FLOORHEATING CONNECTION
Connect the load electrical wires to outputs 1-3. Each channel can control a maximum of 5A loads. The installer should make sure not to overload the channels.
Load neutral wire should be linked to the neutral connection in DB enclosure.

Connect To L

MCB
0.OFF 1.ON

S3 S2 S1 C

24V D+ D- GND

to the TIS BUS Network

Cat5e connection

GND(Black) D-(Green) D+(Red) 24V(White)

2.5 mm Electric Cable 1.5 mm Electric Cable 1.5 mm Electric Cable

3
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL. All of the specification are subject to change without notice.

TIS CONTROL PTY LIMITED SA , AUSTRALIA

www.tiscontrol.com

TIS CONTROL LIMITED Wanchai, Hong Kong

INSTALLATION MANUAL
TIS ADS BUS 3 RELAYS MODULE
Model: ADS-3R-BUS

INSTALLATION STEPS
SHUTTER / CURTAIN CONNECTION Once you combine the channels as shutter/curtain, then connect the shutter-open wire to the first channel and the shutter-close wire to the second channel. The shutter neutral wire should be linked to the neutral connection in DB enclosure.
WARNING: Do not connect curtain motor wires before combining (interlocking) 2 relay channels together as curtain mode by software to avoid causing damage to motors.

Close Open
Connect to L

S3 S2 S1 C

MCB
O-OFF I-ON

Connect to N

2.5 mm Electric Cable 1.5 mm Electric Cable 1.5 mm Electric Cable

FCU CONNECTION Once you combine the channels as FCU, then connect the FCU (Low, Medium, High) wires to the first, second, and third channels, The FCU neutral wire should be linked to the neutral connection of the same section.
WARNING: Do not connect FCU wires before combining (interlocking) 3 relay channels together as FCU mode by software to avoid causing damage to FCU.

HVAC
S3 S2 S1 C

Fan Heat Cool Com

2.5 mm Electric Cable 1.5 mm Electric Cable

4
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL. All of the specification are subject to change without notice.

TIS CONTROL PTY LIMITED SA , AUSTRALIA

www.tiscontrol.com

TIS CONTROL LIMITED Wanchai, Hong Kong

INSTALLATION MANUAL
TIS ADS BUS 3 RELAYS MODULE
Model: ADS-3R-BUS

INSTALLATION STEPS

4

Connect the live (supply) wire to input

"C". All inputs must have an appropriate

voltage source and an MCB to protect

that load circuit.

5

Turn on the breaker. The module should

turn on accordingly.

Circuit Breaker ON

5
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL. All of the specification are subject to change without notice.

TIS CONTROL PTY LIMITED SA , AUSTRALIA

www.tiscontrol.com

TIS CONTROL LIMITED Wanchai, Hong Kong

INSTALLATION MANUAL
TIS ADS BUS 3 RELAYS MODULE
Model: ADS-3R-BUS

TROUBLESHOOTING

PRG button blinks fast Red color

Reason: The Module address conflicts with other device in TIS network, you need to press and hold the PRG button for 6 seconds so the module can get new address.

Device PRG LED is not Blinking; Device not Powered

Reason: Device is not powered on; no TIS-BUS 24V supply connected to the device.

Wall Panels can't Control the Device Channels

Reason 1: TIS-BUS connection has a problem; check the wires and make sure there's not a short in the connection. Reason 2: Programming address is wrong.

Channel is turning off by itself after few seconds

Reason: It is programmed as shutter/curtain combination, and running time is enabled in the software.