Siemens SITOP UPS500S Ex and UPS501S Ex DC-UPS Operating Instructions

Product Numbers: SITOP UPS500S Ex – Grundgerät / basic unit (6EP1933-2EC51-8AA0), SITOP UPS501S Ex – Erweiterungsmodul / expansion module (6EP1935-5PG01-8AA0)

Document Reference: A5E51289135

Introduction and Overview

These operating instructions provide detailed information for the Siemens SITOP UPS500S Ex and UPS501S Ex DC-UPS units. These devices are designed for mounting on a DIN rail (TH 35-15/7,5) and are used to buffer a portion of the load current for 24V DC SITOP power supplies.

The DC-UPS basic unit connects to the output of a 24V DC power supply. Up to three expansion modules can be connected to the basic unit. When the primary 24V DC supply fails or drops below a set threshold, the loads are supplied by the DC-UPS via its internal capacitors or expansion modules.

Key features include adjustable cut-in threshold, charging power, and buffering time via DIP switches. The units also feature LEDs for status indication, potential-free relay contacts, and a USB interface for remote control and signaling.

Safety Warnings:

Technical Data

Input Quantities:

Output Quantities:

Settings

Setting the Cut-in Threshold:

This setting determines when the DC-UPS switches to floating operation if the input voltage drops. It is adjustable via three DIP switches in 0.5V steps from 22.0V to 25.5V DC. The delivery state is 22.5V DC ± 0.1V.

Setting the Charging Current:

This setting determines how quickly the buffer ready state is restored. The charging current is set via a DIP switch to typ. 1A or typ. 2A. The delivery state is 1A.

Setting the Operating State ON/OFF:

For normal operation, the unit must be set to "ON" (delivery state is "OFF"). This can be done via a DIP switch or by connecting terminals X2.9 and X2.10. Setting to "OFF" prevents unintentional capacitor discharge but disables floating operation upon power loss. The "ON/OFF" status is polled approximately every 20 seconds during normal operation.

Setting the Buffering Time:

The buffering time can be set in 10s steps from 5s to 315s using five DIP switches. A switch (Switch 5) allows selection between terminating buffering after a prespecified time or when the capacitors reach their deep discharge threshold (maximum buffering time). The delivery state is maximum buffering time. A remote signal can initiate the timer for termination.

Interruption of the Output Voltage:

A DIP switch can be used to select whether the output voltage is interrupted for 5 seconds at the end of the buffering time. The delivery state is no interruption. With the "max. time" setting, an interruption is initiated by the remote signal.

Protective and Monitoring Functions

Signaling

The DC-UPS provides status information via LEDs and relay contacts:

The "Alarm" signal in floating operation indicates capacitor voltage has dropped below 12V, and disconnection is imminent. After termination (overload, short circuit, etc.), the red LED goes out, but the relay contact remains closed. Relay contacts are rated for 30V DC / 1A (SELV (ES1) must be maintained).

USB Interface: Signals are also output via a PC-compatible USB interface (Specification 2.0, Full Speed). A software tool for reading signals is available online. Remote signals "R" (Timerstart) and "S" (Shutdown) can be sent via USB.

Environment and Standards

Environment:

Standards:

Installation Instructions

Connection and Terminal Assignments

Terminals Function Cable Cross-Section Comments
X1.1 Input voltage DC 24V 1.0 ... 4mm² (17...11 AWG) Screw-type terminals for screwdriver with 4.5mm blade width. Torque: 0.7-0.9Nm.
X1.3, X1.5 Output voltage DC 24V
X1.2/X1.4, X1.6 Input/output voltage DC OV
X2.1,2,3 Signal: Normal operation / Floating operation 0.5... 2.5mm² (20...13 AWG) Screw-type terminals for screwdriver with 3.5mm blade width. Torque: 0.5-0.7Nm.
X2.4,5,6 Signal: Buffering not ready / ready
X2.7,8 Signal: charge >85%
X2.9/X2.10 On/Off jumper (no jumper = Off) See description above.
X3 USB interface Tailored wire set.
X10 Capacitor module Serial interface or USB-interface. Use copper wire approved for 60/75 °C.

Caution: External circuitry for all terminals must meet SELV (ES1) requirements per EN61204-7.

ATEX / Standards Compliance

6EP1933-2EC51-8AA0:

6EP1935-5PG01-8AA0:

Models: 6EP1933-2EC51-8AA0 Uninterruptible Power Supply, 6EP1933-2EC51-8AA0, Uninterruptible Power Supply, Power Supply, Supply

File Info : application/pdf, 8 Pages, 600.94KB

PDF preview unavailable. Download the PDF instead.

A5E51289135-1-74 OP-INST UPS500S-Ex de-en 2021-12-20

References

Robert Deininger Adobe PDF Library 21.7.131

Related Documents

Preview Siemens SITOP Power Supplies: Reliability, Efficiency, and Integration
Explore the comprehensive range of Siemens SITOP power supplies, designed for reliability, efficiency, and seamless integration into industrial automation systems. Discover solutions for every application, from basic to advanced.
Preview Siemens SITOP Stromversorgungen: Effizienz, Zuverlässigkeit und Integration
Entdecken Sie die umfassende Produktpalette der Siemens SITOP Stromversorgungen, die für höchste Effizienz, Zuverlässigkeit und nahtlose Integration in industrielle Automatisierungssysteme entwickelt wurden. Erfahren Sie mehr über die vielfältigen SITOP Lösungen für Ihre industriellen Anwendungen.
Preview Siemens SFP991-1 SCALANCE X Plug-in Transceiver Datasheet (6GK5991-1AD00-8AA0)
Technical datasheet for the Siemens SFP991-1 SCALANCE X plug-in transceiver (model 6GK5991-1AD00-8AA0). Details include 1x 100 Mbit/s LC optical port, multimode fiber support up to 5 km, ambient conditions, dimensions, weight, and relevant industry standards and approvals.
Preview Siemens SITOP PSU300S 6EP1437-2BA20: 24V 40A Switch Mode Power Supply Operating Instructions
Comprehensive operating instructions and technical specifications for the Siemens SITOP PSU300S 6EP1437-2BA20, a 24V 40A 3-phase AC input switch mode power supply unit. Covers safety, mounting, connection, technical data, signaling, and accessories.
Preview Siemens SITOP PSU200M Power Supply Unit - Operating Instructions
Comprehensive operating instructions and safety guidelines for the Siemens SITOP PSU200M power supply unit, covering installation, connection, operation, and technical specifications. Available in multiple languages.
Preview Siemens LOGO! 8 Product Overview: Logic Modules, Expansion, and Accessories
A comprehensive overview of the Siemens LOGO! 8 series, detailing its logic modules, digital and analog expansion modules, communication modules, HMI devices, power supplies, software, mounting kits, and starter kits. The document highlights features such as easy installation, cloud connectivity via MQTT, versatile communication protocols like Modbus TCP/IP, and integration with SIMATIC S7 systems. It also provides article numbers for various components.
Preview Siemens SIMARIS UPS Modeling for Data Centers: Technical Series Edition 3
A technical guide detailing the modeling of Uninterruptible Power Supply (UPS) systems for data centers using Siemens SIMARIS design software. It covers UPS classifications, operating modes, integration into power distribution networks, technical specifications, and critical considerations for planning and simulation.
Preview Siemens SIMOREG CM 6RA70 Series Operating Instructions: Control Module for Variable-Speed DC Drives
Comprehensive operating instructions for the Siemens SIMOREG CM, 6RA70 Series control module. This manual details the microprocessor-based control module designed for variable-speed DC drives, covering installation, connection, parameterization, safety, and maintenance. Order Number: 6RX1700-0BD76.