NEEP's Cold Climate Air Source Heat Pump List
TOSOT
Product Overview
Brand: TOSOT
Product Type: Central Air Conditioning Heat Pump (HP)
Configuration: Singlezone Non-Ducted, Wall Placement
AHRI Certificate #: 211931452
Outdoor Unit Model #: GWH12QCXB-D3DND4C/O
Indoor Model #: GWH12AFCXB-D3DN*** /I
Indoor Unit Type: Mini-Splits
[NEEP CCASHP Listed]
Performance Specifications
Heating/Cooling | Outdoor Dry Bulb | Indoor Dry Bulb | Unit | Min | Rated+ | Max |
---|---|---|---|---|---|---|
Cooling | 95°F | 80°F | Btu/h+ | 2,400 | 12,000 | 13,500 |
Cooling | 95°F | 80°F | kW | 0.18 | 1.06 | 1.45 |
Cooling | 95°F | 80°F | COP | 3.91 | 3.32 | 2.73 |
Cooling | 82°F | 80°F | Btu/h+ | 2,600 | 14,100 | |
Cooling | 82°F | 80°F | kW | 0.11 | 1.35 | |
Cooling | 82°F | 80°F | COP | 6.93 | 3.06 | |
Heating | 47°F | 70°F | Btu/h+ | 3,070 | 12,000 | 15,000 |
Heating | 47°F | 70°F | kW | 0.14 | 0.99 | 1.45 |
Heating | 47°F | 70°F | COP | 6.43 | 3.55 | 3.03 |
Heating | 17°F | 70°F | Btu/h+ | 2,700 | 7,000 | 10,500 |
Heating | 17°F | 70°F | kW | 0.26 | 0.75 | 1.46 |
Heating | 17°F | 70°F | COP | 3.04 | 2.74 | 2.11 |
Heating | 5°F | 70°F | Btu/h+ | 2,600 | 8,500 | |
Heating | 5°F | 70°F | kW | 0.3 | 1.42 | |
Heating | 5°F | 70°F | COP | 2.54 | 1.75 | |
Heating | -13°F | 70°F | Btu/h+ | 1,800 | 6,500 | |
Heating | -13°F | 70°F | kW | 0.26 | 1.34 | |
Heating | -13°F | 70°F | COP | 2.03 | 1.42 |
Efficiency Ratings and Features
- EER: [Not specified]
- SEER: [Not specified]
- HSPF (Region IV): 8.5
- EER2: 11.3
- SEER2: 20
- HSPF2 (Region IV): 8.5
- HSPF2 (Region V): 7.3
- ENERGY STAR V6.1: [Not specified]
- ENERGY STAR V6.1 Cold Climate: [Not specified]
- ENERGY STAR V5.0: [Not specified]
- Variable Capacity: ✔️
Capacity Maintenance and Other Information
Capacity Maintenance (Rated 17°F/Rated 47°F): 58%
Capacity Maintenance (Rated 5°F/Rated 47°F): [Value Missing]
Capacity Maintenance (Max 5°F/Rated 47°F): 70%
Refrigerant: R-410A
Sold In: USA, Canada
Federal Tax Credit Eligibility
North: [Not Specified]
South: [Not Specified]
Visual Description
The document includes a graph titled "Heating/Cooling Capacity Graph". This graph plots Capacity (Btu/h) on the y-axis against Outdoor Temperature (°F) on the x-axis, ranging from -13°F to 95°F. It displays data points for Heating Max. Cap., Cooling Max. Cap., Heating Rated Cap., Cooling Rated Cap., Heating Min. Cap., and Cooling Min. Cap.