Installation Guide for AcuityBrands models including: 2024 LED Strip Light Linear LED Strip Light, 2024, LED Strip Light Linear LED Strip Light, Light Linear LED Strip Light, Linear LED Strip Light, LED Strip Light, Strip Light, Light

kds02

View

CLX LED Strip Light - CLX Linear LED Strip Light

Download


File Info : application/pdf, 15 Pages, 1.53MB

PDF preview unavailable. Download the PDF instead.

2025 14:51:28&DOC Type=Installation Instruction Sheets
LED IMPORTANT SAFETY INSTRUCTIONS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
· To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
· Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions. · Installation and service of luminaires should be performed by a qualified licensed electrician. · Maintenance of the luminaires should be performed by person(s) familiar with the luminaires' construction and
operation and any hazards involved. Regular fixture maintenance programs are recommended. · It will occasionally be necessary to clean the outside of the refractor/lens. Frequency of cleaning will depend on
ambient dirt level and minimum light output which is acceptable to user. Refractor/lens should be washed in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly become dirty on the inside, wipe refractor/lens and clean in above manner, replacing damaged gaskets as necessary. · DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced. · Recycle: For information on how to recycle LED electronic products, please visit www.epa.gov. · These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's or owner's purposes, this matter should be referred to Acuity Brands Lighting, Inc.

WARNING RISK OF ELECTRIC SHOCK
 Disconnect or turn off power before installation or servicing.
 Verify that supply voltage is correct by comparing it with the luminaire label information.
 Make all electrical and grounded connections in accordance with the National Electrical Code (NEC) and any applicable local code requirements.
 All wiring connections should be capped with UL approved recognized wire connectors.
CAUTION RISK OF INJURY
 Wear gloves and safety glasses at all times when removing luminaire from carton, installing, servicing or performing maintenance.
 Avoid direct eye exposure to the light source while it is on.

WARNING RISK OF BURN  Allow lamp/fixture to cool before handling. Do not touch enclosure or light source.  Do not exceed maximum wattage marked on luminaire label.  Follow all manufacturer's warnings, recommendations and restrictions for: driver type, burning position, mounting locations/methods, replacement and recycling.
CAUTION RISK OF FIRE  Keep combustible and other materials that can burn, away from lamp/lens.  Do not operate in close proximity to persons, combustible materials or substances affected by heat or drying.

U351 ­ Rev. U ­ 07/25/2024

Page 1 of 15

LED IMPORTANT SAFETY INSTRUCTIONS

CAUTION: RISK OF PRODUCT DAMAGE

 LEDs are sensitive components and necessary PCBA/LED handling measures are required to provide
protection from ESD (Electrostatic Discharge), static electricity, transient voltages, and surge current. If this
excess voltage condition occurs it may cause the LED to be damaged leading to non-illumination and/or
operational failure. Measures to prevent such damage are effective use of ESD wrist band, ESD foot ware,
anti-electrostatic glove, grounded workstations/equipment/tool.  Never connect components under load.  Do not mount or support these fixtures in a manner that can cut the outer jacket or damage wire insulation.  Controls for dimming, auto-sensing, or remote control of a luminaire that are not factory-wired to the
luminaire must be checked for compatibility with the luminaire prior to installation. LED fixtures must be
powered directly off a switched circuit.  Unless individual product specifications deem otherwise: Do not restrict fixture ventilation. Allow for some
volume of airspace around fixture. Avoid covering LED fixtures with insulation, foam, or other material that
will prevent convection or conduction cooling.  Unless individual product specifications deem otherwise: Do not exceed fixtures maximum ambient
temperature.  Only use fixture in its intended location.  LED products are Polarity Sensitive. Ensure proper Polarity before installation.  Electrostatic Discharge (ESD): ESD can damage LED fixtures. Personal grounding equipment must be worn
during all installation or servicing of the unit.  LEDs are sensitive components and necessary PCBA/LED handling measures are required to provide
protection from ESD (Electrostatic Discharge), static electricity, transient voltages, and surge current. If this
excess voltage condition occurs it may cause the LED to be damaged leading to non-illumination and/or
operational failure. Measures to prevent such damage are effective use of ESD wrist band, ESD foot ware,
anti-electrostatic glove, grounded workstations/equipment/tool.  Do not touch individual electrical components as this can cause ESD, shorten lamp life, or alter
performance.  Some components inside the fixture may not be serviceable. In the unlikely event your unit may require
service, stop using the unit immediately and contact an ABL representative for assistance.  Always read the fixtures complete installation instructions prior to installation for any additional fixture
specific warnings.  Always ensure that the electrical distribution system is up to NEC (and any applicable local code)
requirements.  Verify that power distribution system has proper grounding. Lack of proper earth ground can lead to fixture
failure and may void warranty.

Choose either Part 15 OR Part 18 and move to Page 3 Installation Instructions under Delivery. Lithonia Outdoor will always use Part 15.
All luminaires that contain electronic devices that generate frequencies above 9kHz from any component within the luminaire comply with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation

This device complies with Part 18 of the FCC Rules but may cause interference with cordless and cell phones, radios, televisions, and other electronic devices. To correct the problem, move the device away from the luminaire or plug into a different outlet. This product may cause interference to radio equipment and should not be installed near maritime safety communications equipment or other critical navigation or communications equipment operating between 0.45-30MHz.

Failure to follow any of these instructions could void product warranties. For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com.

Our Brands

Indoor/Outdoor Lithonia Lighting Carandini

Indoor Lighting Gotham Mark Architectural Lighting

U351 ­ Rev. U ­ 07/25/2024

Outdoor Lighting American Electric Lighting Antique Street Lamps

Controls DARK TO LIGHT LC&D

Daylighting SunOptics
Page 2 of 15

LED IMPORTANT SAFETY INSTRUCTIONS

Holophane RELOC Light Concepts

Peerless Renaissance Lighting Winona Lighting

Hydrel Tersen

ROAM Sensor Switch Synergy

Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products. ABL LED General Warnings, Form No. 503.203

© 2010, 2016 Acuity Brands Lighting, Inc. All rights reserved. 12/01/10

CLX LED STRIP/LOW BAY

INSTALLATION INSTRUCTIONS

WARNING: Please read all "important safety instructions" prior to installation of this product.
*Luminaire is suitable for closet storage space ­ UL1598 Section 13.6. Available only with nomenclature: CLX L24 1500LM SEF FDL MVOLT GZ10 40K 80CRI
A) Identification of CLX Luminaire ­ Page 4 - 5
1) CLX L24 1500LM, 2000LM, 2500LM, 3500LM, 4500LM, 5000LM 2) CLX L36 2250LM, 3000LM, 3750LM, 5250LM, 6750LM, 7500LM 3) CLX L48 3000LM, 4000LM, 5000LM, 7000LM, 9000LM, 10000LM 4) CLX L96 6000LM, 8000LM, 10000LM, 14000LM, 18000LM, 20000LM 5) Lens (FDL, RDL, WDL) Options 6) Sensor Option 7) E10WLCP PS1055 Option 8) ZAC/HC36 V-HANGER Accessory 9) THCLX (Surface Mount) Accessory
10) CLXANGBKT Accessory

B) Required Handling Locations ­ Page 5

C) Pre-installation for all mounting ­ Page 5

D) Installation ­ Suspended Fixture ­ Page 6 - 7

E) Installation ­ THCLX (Surface) Mount ­ Page 8

F) Wiring ­ Emergency (BGTD, PS1050) ­ Page 9

G) Commissioning nLight AIR (NLTAIR2 RES7, NLTAIR2 RES7PDT, NLTAIR2 RIO) ­ Page 9

H) Servicing ­ Lens Attachment/Removal, LED Channel Removal - Page 10 - 12

I) Accessory installations ­ Page 13 - 15

1) Narrow Reflector 2) Wide Reflector 3) Wire guard

U351 ­ Rev. U ­ 07/25/2024

Page 3 of 15

4) Louver 5) Angle Bracket 6) LUGR Reflector
SECTION A: Identification of CLX Luminaire
CLX Length Options

LED IMPORTANT SAFETY INSTRUCTIONS

CLX Lens Options

U351 ­ Rev. U ­ 07/25/2024

Page 4 of 15

LED IMPORTANT SAFETY INSTRUCTIONS

PS1050 OPTION

Sensor OPTION

Test switch located on the side of the fixture

ZAC/HC36 V-HANGER ACCESSORY

THCLX HANGER

Sensor option location
*Sensor option adds 2" to overall fixture length CLXANGBKT

SECTION B: HANDLING PRECAUTIONS
ACYRLIC LENS
SHEET METAL HOUSING
PLASTIC LENS CAPS PLASTIC HOUSING END CAPS
When handling the fixture during unpacking and installation take precautions of the plastic Lens and plastic end caps. Dropping the fixture or excess force on the end caps or lens can cause damage.
Section C: PRE-INSTALLATION FOR ALL MOUNTING
1. Ensure power is OFF. 2. Inspect the mounting location for damage before installing new CLX Luminaire. Ensure mounting structure is
properly sized to support the fixture. 3. Remove luminaire from packing and inspect for any damages. If the fixture is damaged do not use; call your local
representative for assistance. 4. WARNING! Removing the lens and opening the fixture during installation exposes the LED's and puts them at risk for
damage. Damage to the LEDs caused during installation will not be covered under the warranty.

U351 ­ Rev. U ­ 07/25/2024

Page 5 of 15

LED IMPORTANT SAFETY INSTRUCTIONS
SECTION D: INSTALLATION - SUSPENDED FIXTURE
For V-hanger 1) Feed V-hanger into holes on the Driver channel. 2) Ensure supply wire is not active. If using a continuous row mount skip to steps 5-9. 3) Remove access plate screw as shown below. Input wires will be attached to the access plate. Remove the necessary knockout(s) and connect input wires black to black, white to white and green to green. Use only UL listed connectors rated 75C or greater. Purple and Gray wires are low voltage dimming leads. If ordering with OUTEND option ensure end cap hole and wires are enclosed with a UL approved barrier (cordset, conduit, etc). 4) Push wires into Driver channel and reattach the access plate.

V-Hanger V-Hanger Holes

Access Plate Screw Housing End Cap Screw

For Aircraft Cable 1) Attach bracket to ceiling. Feed aircraft cable through the small threaded pipe. Insert threaded rod into small threaded pipe. Place canopy over bracket and screw the threaded pipe/rod assembly into bracket holding the canopy in place. 2)Open fixture by removing LED Channel and attach large threaded assembly to fixture through 0.3" dia hole using nut provided. Close fixture and feed aircraft cable through large threaded assembly. Requires two per fixture, see following images. Refer to Section H: Servicing on Page 10 for detailed opening instructions. 3) Ensure supply wire is not active. If using a continuous row mount skip to steps 5-9. 4) Remove access plate screw as shown below. Input wires will be attached to the access plate. Remove the necessary knockout(s) and connect input wires black to black, white to white and green to green. Use only UL listed connectors rated 75C or greater. Purple and Gray wires are low voltage dimming leads. If ordering with OUTEND option ensure end cap hole and wires are enclosed with a UL approved barrier (cordset, conduit, etc). 5) Push wires into Driver channel and reattach the access plate.

U351 ­ Rev. U ­ 07/25/2024

Page 6 of 15

LED IMPORTANT SAFETY INSTRUCTIONS
Aircraft cable Threaded assembly

For Continuous Row 5) For STD configurations, Remove Housing End Cap(s) with one screw and disengage end cap snap features. For L/EP option, fixture shipped without endcaps for ease of continuous row mounting. WARNING - Fixtures at end of row must have Housing End Caps installed, as shown below. Housing End Caps can be ordered using nomenclature CLXEPxx xxxx. Failure to install Housing End Caps is a safety hazard. 6) If supplied with a PLR (continuous row wiring), pull PLR connector from fixture. Male will be located on the access plate side. 7) Attach Continuous row mounting bracket into fixture A (supplied with fixture) by snapping into the driver channel and attaching two screws provided in hardware bag. 8) If using a PLR continuous row wiring system, connect female PLR plug from fixture B into the Male PLR plug from fixture A. 9) Snap fixture B into the continuous row bracket and attach using the remaining two screws from the hardware bag.

Step 5

Without Sensor ­ Continuous Row Step 7

Step 9

Included in Box

Sensor Version ­ Continuous row

Use caution to not damage sensor lens U351 ­ Rev. U ­ 07/25/2024

Page 7 of 15

LED IMPORTANT SAFETY INSTRUCTIONS

SECTION E: INSTALLATION ­ CLX HANGER MOUNT (THCLX)

1) Attach CLX brackets to structure. If mounting to a T-Grid snap Mounting bracket into T-Grid as shown below. Two CLX brackets MUST be used for standalone fixtures. If mounting in a continuous row one bracket per fixture with one additional bracket per row must be used at a minimum. Two brackets per fixture is highly recommended. 2) Snap Fixture into the THCLX mounting bracket. Ensure fixture is fully engaged into the THCLX bracket, as shown below. 3) Follow steps 2-9 from the suspended mount instructions 4) Tighten THUN brackets around center channel as shown below. Tighten bolts to 13 in/lbs.

T-grid

DO NOT REMOVE OR TIGHTEN BOLT BEFORE INSTALLING FIXTURE

THCLX

Rotate THCLX bracket to lock onto T-Grid
Installing THCLX to T-GRID

Installing THCLX to fixture

U351 ­ Rev. U ­ 07/25/2024

THCLX

Ensure mounting bracket is fully engaged with the driver channel

DRIVER CHANNEL
USE CAUTION WHEN WORKING NEAR EXPOSED LEDS

Damage to LEDS during installation will not be covered under warranty

Page 8 of 15

LED IMPORTANT SAFETY INSTRUCTIONS

Section F: Wiring ­ Emergency (BGTD, PS1055, E10WLCP, E10WSTAR)

1) Install fixture with mounting brackets, directly to surface, or with V-hooks. Do not wire. 2) The emergency battery pack indicator light needs to be plugged in during installaion. Remove housing end cap near access plate as shown in previous instructions. 3) For the emergency battery pack the fixture will be provided with a wiring harness at the access plate end. Attach the two connectors together to activate the battery pack 4) Connect unswitching power to unswitched fixture wire. Connect switched power to white, black, and green wires. Supply wire must meet applicable electrical codes and be rated for a minimum of 90C. Purple and gray leads are 0-10V (low voltage) dimming leads.

Worst case maximum mounting height

CLX FDL WD 30K 90CRI

21 T

5) (OPTION E10WSTAR) STAR (SELF-TESTING AUTOMATED REPORT) ­ WIRELESS a. Please see STAR Self-Testing Automated Reporting for commissioning and additional information.
b. LED Status Codes.

Flashing Amber Green
Off

Battery is charging Battery is fully charged
Emergency mode

Flashing Green

Unit is performing a test

Flashing Red (once per 0.5 sec.) Electronics failure

Flashing Red (once per 6 sec.)

Battery failure

Two Red Flashes

Load failure

c. Button Sequences to initiate manual test.

Press and Hold

Quick Test

2 X Press and Release

60-Second Test

3 X Press and Release

90-Minute Test

1 X Press and Release 4 X Press and Release

Cancel 90-Minute Test Load Calibration

SECTION G: nLight AIR Commissioning (NLTAIR2 RES7, NLTAIR2 RES7PDT, NLTAIR2 RIO) Out of the Box Sensors perform as follows:
100% Light Output for 7.5 minutes, then 1% light output for 2.5minutes before turning off.

1) Please refer to nLight AIR Quick Start Guide (912-00058-001) included with the luminaire.

2) Please locate additional references and resources below:

http://www.acuitybrands.com/clx

http://www.acuitybrands.com/nlightair

U351 ­ Rev. U ­ 07/25/2024

Page 9 of 15

LED IMPORTANT SAFETY INSTRUCTIONS
SECTION H: SERVICING NOTE:
1) Clean fixture as needed. Double check all mounting hardware. 2) After installation, wear protective gloves if the lenses need to be removed 3) The lens snaps into the LED channel. To remove lens, carefully squeeze lens together to disengage from LED channel. 4) To replace the lens snap into LED Channel as shown in the image below.
LED CHANNEL
Lens

Squeeze together to disengage Lens from LED Channel FDL/RDL detachment
USE CAUTION WHEN WORKING NEAR EXPOSED LEDS
Damage to LEDS during installation will not be covered under warranty

WDL DETACHMENT/REATTACHMENT

PRESS AGAINST LENS WALL TO DISENGAGE
PRESS TOWARD THE FIXTURE WHILE PRESSING AGAINST THE SIDE WALL TO REENGAGE.

U351 ­ Rev. U ­ 07/25/2024

Page 10 of 15

LED IMPORTANT SAFETY INSTRUCTIONS

NOTE: Cleaning: The LED PCBA should not be exposed or cleaned with any type of fluid such as water, oil, organic solvent, etc other than IPA (Isopropyl Alcohol). Some solvent-based cleaning agents may damage and/or impact the operation and lifetime of the PCBA or LED. Handling and Packaging of Removed PCBA for Return: All PCBAs removed from luminaires during a repair process, which are intended to be returned to Acuity, must be handled with extreme care to ensure no handling or shipping damage occurs. If the PCBAs are to be returned for review they must be repackaged and returned in the same shipping methods as the new replacement PCBAs arrived.
5) If replacing PCBA, ensure power to the fixture is off. 6) If fixture has lens, remove per SECTION H: SERVICING steps 3 & 4. 7) Tag leads before disconnecting from PCBA 8) Disconnect all leads to Old PCBA by pressing down on tab

Push down on tab to release

Typical Connector:

9) Unscrew fasteners holding the PCBA (L24: ~8 screws, L36: ~12 screws, L48: ~10 screws L96: ~20 screws)
REMOVE ALL SCREWS HOLDING PCBA

10) Replace Old PCBA with New PCBA. Note: be mindful of orientation of PCBA to ensure PCBA is centered on LED Channel

U351 ­ Rev. U ­ 07/25/2024

Page 11 of 15

LED IMPORTANT SAFETY INSTRUCTIONS
11) Torque down all fasteners to 11 ± 1 IN-LB to secure PCBA to LED Channel
12) Connect all leads to corresponding terminals. Note: Ensuring that positive lead terminate to positive terminal, and negative lead to negative terminal. 13) If installing lens, please refer to steps 3 & 4 of SECTION H: SERVICING. 14) To access electrical components, remove the six screws shown below.
USE CAUTION WHEN WORKING NEAR EXPOSED LEDS
Damage to LEDS during installation will not be covered under warranty
15) LED Channel MUST hang from driver channel during servicing as shown below.

16) If replacing drivers, ensure power to the fixture is off 17) Tag leads before disconnecting 18) Disconnect all leads from old driver. 19) Unscrew driver using two screws. Attach new driver to channel using two screws. 20) Connect leads to corresponding driver ports 21) Close LED channel and secure using six screws.
U351 ­ Rev. U ­ 07/25/2024

Page 12 of 15

LED IMPORTANT SAFETY INSTRUCTIONS
SECTION I: ACCESSORIES
Wire guard (WGCLX)/Louver (SBL) 1) Install accessory brackets to the top of the fixture with two screws provided. 2) Install Louver or Wire guard to Accessory bracket using four screws provided.
Angle Bracket (CLXANGBKT) 1) Attach fixture to angle mounting bracket using screws provided 2) Attach Angle brackets to ceiling (hardware not provided) 3) Choose desired angle (0, 15, 30, or 45 degrees) and fix mounting bracket into angle position using two screws provided
CLXANGBKT Screws provided

U351 ­ Rev. U ­ 07/25/2024

Page 13 of 15

LED IMPORTANT SAFETY INSTRUCTIONS
LUGR REFLECTOR (CLXLUGR)
1. Insert tabs which are on both sides of the Reflector into the respective slots in the Channel in such a way that mounting holes in the Reflector are in line with the holes in the Channel.
2. Install screws on either side, so that Reflector is firmly assembled to the Channel. Tighten to 11in-lbs. 3. Install screws on either side, so that Reflector is firmly assembled to the Channel. 4. Follow  and  to install another Reflector on other side of the Channel. 5. If installing on an 8ft fixture, repeat process  to  for each of the remaining 2 Reflectors (8FT Fixture uses 4 x 4FT
Reflectors).






U351 ­ Rev. U ­ 07/25/2024

Page 14 of 15

LED IMPORTANT SAFETY INSTRUCTIONS
Warranty terms are located at the link below: http://www.acuitybrands.com/resources/terms-and-conditions
Importado por: Holophane, S.A. de C.V.
Av, La Silla #7711 Parque Industrial La Silla Guadalupe, N.L. C.P. 67193 Tel: 52-81-8318-0460
LUMINARIOS
Marca: Lithonia Lighting Modelo: CLX
PRECAUCION: Por su seguridad y el funcionamiento adecuado del luminario, lea cuidadosamente las siguientes instrucciones antes de empezar la instalación. Este instructivo aplica a todos los luminarios de Lithonia Lighting para uso interior y/o exterior. El número de catálogo especifico, y sus características eléctricas, se encuentran en la etiqueta del producto. 1. Desconecte la alimentación eléctrica de la caja de fusibles antes de instalar el luminario. 2. Abra el luminario para tener acceso a los cables de conexión. 3. Monte el luminario en la ubicación deseada, y asegúrela utilizando dispositivos mecánicos adecuados. 4. Utilizando capuchones aislantes, conecte los cables del luminario. Si el luminario tiene un cable blanco y uno negro, conecte
el blanco al neutro del circuito de alimentación y el negro a la "línea", aterrice el luminario. En el caso de equipos con más cables de conexión, identifique el adecuado a la línea de alimentación (todas vienen marcadas con etiquetas) y conéctela a la "línea" de la alimentación, conecte la punta marcada con "com" al neutro de la alimentación. Asegúrese de aislar perfectamente los cables que no utilizó. 5. En los casos en que aplique, reinstale la cubierta del balastro o controlador. 6. Reestablezca la alimentación eléctrica en la caja de fusibles y verifique la operación del luminario. GUARDE ESTAS INSTRUCCIONES

U351 ­ Rev. U ­ 07/25/2024

Page 15 of 15

