User Guide for LEDone models including: LOC-EMDR-25WHV, LED LOC-EMDR Emergency Driver Series, Emergency Driver Series, LED LOC-EMDR Driver Series, Driver Series

Susan Miller

规范表下载

应急驱动,25W或40W, 100-347V,工作时间1.5小时,充电时间24小时 - 欧宝体育官网入口首页

PDF preview unavailable. Download the PDF instead.

LOC-EMDR-XXWHV SERIES 88547e7d-39be-49fd-96a4-9f23b0c03afb ?v=1655498009
Date: _______________ Location: _____________________________________
Product: ___________________Project: ________________________________
Quantity: _____________Catalog #: ____________________________________
LED LOC-EMDR Emergency Driver Series
FEATURES
· Listed to UL924 · Test to CSA C22.2 NO. 141 Field or factory
installation · High output voltage · Low energy consumption CEC Title 20 compliant · Constant output power · Self-testing · Battery: Li-ion · Battery: over temperature protection · Ambient Temp: Li-ion: 0°-50°C (32°F-122°F) · 5-year warranty

SELF-TESTING

CAUTION

· The emergency LED driver contains a control/ monitor circuit which will perform a 30second discharge test once a month and a full discharge test once a year. At this time, the unit will simulate an AC power failure and automatically switch to emergency mode. During routine testing, the unit will monitor the operation of the LED load, battery voltage and emergency duration. If the unit detects any problems, the indicator will flash quickly.

· During AC operation, remember not to touch or remove and wires in case of electrical shock.
· During emergency operation, before touching and disconnecting the wires, remember to press the test button again to make the LED lamp and indicator light turn off to avoid electric shock.
· The voltage input to the dimmable wires (DIM+, DIM-) of emergency LED driver must be less than 20Vdc.
· Maximum suggested LED fixture wattage is

FUNCTION
· AC operation, indicator light will keep on. · Emergency operation, indicator light will
flash slowly (light on for 2 seconds, light off for 2 seconds). · In a failure, indicator light will flash quickly (light on for 0.2 seconds, light off for 0.2 seconds).

TEST SWITCH
· In AC operation, press the test switch once to run the emergency power for 30 seconds.
· In AC operation, press the test twice within 3 seconds to make the battery full discharge.
· In emergency operation, press the test switch once. This will turn off both the emergency as well as the lamp and indicator light at the same time.

MODEL NUMBER LOC-EMDR-25WHV LOC-EMDR-40WHV

INPUT VOLTAGE 100-347Vac, 50/60Hz 100-347Vac, 50/60Hz

INPUT CURRENT 200mA max.
200mA max.

INPUT POWER RATING 12W max.
12W max.

OUTPUT VOLTAGE 170Vdc 170Vdc

EMERGENCY POWER 25W max.

RECHARGE TIME 24Hrs.

DISCHARGE TIME
90 mins.

40W max.

24Hrs.

90 mins.

LED LOC-EMDR EMERGENCY DRIVER SERIES

Series LOC-EMDR

Type Emergency Driver

MEASUREMENTS

Wattage 25W 40W

MODEL LOC-EMDR-25WHV LOC-EMDR-40WHV

QUANTITY 1 1

WEIGHT 2.65lbs 2.65lbs

UPC CODE 00815586029891 00810050941488

