MiCOM P123R Overcurrent Relays
Upgrade Documentation
MiCOM P123R ADDENDUM: MiCOM P12x UPDATE DOCUMENTATION
The MiCOM P123R is a new overcurrent protection relay from the MiCOM P12x range, designed as a cost-effective solution for retrofitting KCGG122 and KCGG142 relays. It shares the same firmware as the standard MiCOM P123, offering identical software features. The primary difference is mechanical, with re-assigned internal digital input/output terminals for easier retrofit. While the MiCOM P123R offers only 5 logic inputs compared to 8 in KCGG142 01 relays, and one watchdog contact (NC) instead of two (NC and NO) in KCGG122 & 142 relays, it fully supports the protective functions of its predecessors and offers additional functionalities. This document supplements the MiCOM P123 Technical Manual.
The following table outlines the relationship between this addendum and the P12x Technical Manual chapters:
Document Ref. | Section | Version | Description |
---|---|---|---|
P12x/EN IT/Eb6 | 6 | P12x/EN T/Eb6 | New section: Addition of section "evolution from KCGG122 & 142 to MiCOM P123R" (retrofit). |
P12x/EN TD/Eb6 | - | Information required with order (CORTEC) for MiCOM P123R | |
P12x/EN IN/Eb6 | 8 | New section: Instruction to install a MiCOM P123R (replacement of a KCGG 122 & 142) | |
P12x/EN FT/Eb6 | 1.4 | Warning message: specific instructions for MiCOM P123R (watchdog & terminals number) | |
3 | Wiring explanation: Block terminals numbering | ||
3.1 | Auxiliary supply and terminal numbers adaptation and / or modification | ||
3.5 | Additional wiring for RS485 rear communication port | ||
P12x/EN GS/Eb6 | 1.2 | Terminal numbers modification | |
3.2 | Terminal numbers modification | ||
3.3 | Terminal numbers modification | ||
3.7 | Terminal numbers modification | ||
3.8 | Terminal numbers modification | ||
3.9 | Terminal numbers modification | ||
P12x/EN CM/Eb6 | 4.3 | Terminal numbers modification | |
5.2 | Terminal numbers modification | ||
5.3 | Terminal numbers modification | ||
P12x/EN CO/Eb6 | - | Connection diagram for MiCOM P123R |
P12x/EN IT/Eb6: Introduction
Evolutions from KCGG122 & 142 to MiCOM P123R
The KCGG122 & 142 protective functions are fully supported by the MiCOM P123R relay. The following sections highlight the key differences between the two products.
Main characteristics
Characteristic | KCGG122 & 142 | MiCOM P123R |
---|---|---|
Power supply | 24-125 Vdc, 48-250 Vdc | Universal 24-250 Vdc / 48-240 Vac |
Output contacts | 8 output contacts | 8 output contacts |
Watchdog contact | 2 watchdog contacts (1NO + 1 NC) | 1 watchdog contact (1 NC) |
Opto-isolated logic inputs | 8 opto-isolated logic inputs | 5 opto-isolated logic inputs |
Powered by the 48 Vdc field voltage: Nominal value = 48 Vdc | Powered by the same relay power supply value: default nominal value is 24-250 Vdc | |
Communication protocols | KBus courier protocol | Modbus / KBus – Courier / IEC 60870-5-103 / DNP3 |
Protective functions | 46BC - Broken conductor protection 49 - thermal protection 50/51(N) – Phase and earth overcurrent 50BF - Breaker failure detection 81U - Under frequency |
37 - 3-phase undercurrent 46 - Negative phase sequence overcurrent 46BC - Broken conductor protection 49 - thermal protection 50/51(N) – Phase and earth overcurrent 50BF - Breaker failure detection 64N - Restricted earth fault 79 - Autoreclose |
CB maintenance | CB maintenance Cold Load Pick-up |
86 - Output relay latching CB maintenance & trip circuit supervision Cold Load Pick-up Selective relay scheme logic Inrush blocking |
Remote CB control | Remote CB control Blocking logic Switch on to fault (SOTF) Test of output relays Logic equations |
Remote CB control Blocking logic Switch on to fault (SOTF) Test of output relays Logic equations |
Disturbance recorder | Clockwise and anti-clockwise phase rotation Disturbance recorder: up to 5 Event recorder: last 50 Fault recorder: last 5 |
Disturbance recorder: up to 5 Event recorder: up to 250 Fault recorder: up to 25 Front port communication |
P12x/EN TD/Eb6 : Technical Data
Information required with order (MiCOM P123R)
Information required with order | Order - No. | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Versions | MiCOM P123R – Overcurrent protection | P123R | * | * | * | * | * | * | * | * | * | * | * | * | * | * |
Variant | Retrofit variant, replacement of KCCG 122 & 142 | 3 R | ||||||||||||||
Earth current input | 0.01 to 8 Ion | B | ||||||||||||||
0.002 to 1 Ion | C | |||||||||||||||
Current rating | 1 A | 1 | ||||||||||||||
5 A | 5 | |||||||||||||||
Auxiliary voltage | 24-250 Vdc / 48 - 240 Vac | Z | ||||||||||||||
Digital input voltage | 24-250Vdc/24-240Vac | |||||||||||||||
Communication interface | Modbus | 2 | ||||||||||||||
KBus / Courier | 3 | |||||||||||||||
IEC 60870-5-103 | 1 | |||||||||||||||
DNP3 | 4 | |||||||||||||||
Language | French | 0 | ||||||||||||||
English / American | 1 | |||||||||||||||
Spanish | 2 | |||||||||||||||
German | 3 | |||||||||||||||
Italian | 4 | |||||||||||||||
Russian | 5 | |||||||||||||||
Polish | 6 | |||||||||||||||
Portuguese | 7 | |||||||||||||||
Dutch | 8 | |||||||||||||||
Czech | A | |||||||||||||||
Hungarian | B | |||||||||||||||
Greek | C | |||||||||||||||
Chinese (only available in phase II hardware with larger LCD display) | D | |||||||||||||||
Turkish | E | |||||||||||||||
Platform | SE look&feel Phase 2 | 2 | ||||||||||||||
SE look&feel Phase 2 with larger LCD | 3 | |||||||||||||||
Latest Major Software release | V XX.X (1) | ? | ||||||||||||||
Latest Minor Software release | V XX.X (1) | ? | ||||||||||||||
Mounting option | None (default) | 0 | ||||||||||||||
Pre-fixed HMI (no withdrawability) | 1 | |||||||||||||||
Sealed cover | 2 | |||||||||||||||
Pre-fixed with sealed cover | 3 |
(1) Unless specified, the latest version will be delivered.
P12x/EN IN/Eb6 : Installation
Important Safety Information: Before performing any work on the equipment, the user must be familiar with the contents of the Safety Guide SFTY/4LM/E11 (or later issue), the Safety and Technical Data sections of the Technical Manual, and the ratings on the equipment rating label.
Retrofit of KCGG122 or 142 relays
Step 1: Identify CT Ratio
IDENTIFY IF THE CURRENT CIRCUIT CT RATIO IS 1 A OR 5 A. SELECT THE MICOM P123R RELAY ACCORDINGLY.
Deposit of KCGG122 or 142 relays
The steps to replace a KCGG122 or 142 with a MiCOM P123R are described below. Extract all settings from the KCGG relay before switching off and ensure they are reported in the MiCOM P123R or updated if necessary.
- Switch off the existing KCGG122 or 142 relay. Isolate the current, power supply, and tripping circuits, including CBF initiations and intertrip signals, if any.
- If necessary, remove the cover. Unscrew the upper and lower screw.
- Withdraw the KCGG122 or 142 active part by pulling the lower and upper handles.
- Disconnect the two rear side terminal blocks (2). Unscrew and remove the 4 retaining screws (1) (S/TAP screws Nr 2 × 1½ per block - Pozidrive screwdriver Nr 0).
- Unscrew the case retaining screws, pull the case, and remove it.
Note: If necessary, unscrew the two screws (3) retaining the middle plate to facilitate the removal of the terminal block (S/TAP screws Nr 4 × 1/4).
MiCOM P123R assembly
Note: The P123R is provided with the same terminal block arrangement as the KCGG relay. It is recommended to energize this relay, set it accordingly, and test it "on the table".
Withdraw the active module part of the MiCOM P123R relay (see section P12x/EN GS) from its case, and remove the two terminal blocks as explained in the previous lines.
- Place the MiCOM P123R case and screw the retaining screws.
- Fix the terminal blocks in the MiCOM P123R case after inverting their position from left to right. Screw the same retaining screws and fix the earth connecting plate.
- Move the K-Bus communication terminals as follows:
- Terminal 54 to pin 9,
- Terminal 56 to pins 10 and 1 (earth). - Fit the active part of the MiCOM P123R and screw the four retaining screws to the case. Close the top and lower hinged covers.
P12x/EN FT/Eb6 : User Guide
1.4 Displays of Alarm & Warning Messages
1.4.2 Relay Hardware or Software Warning Messages
The watchdog of the MiCOM P123R is a normally closed contacts relay (terminals 3-5), instead of a change-over contacts relay. If an internal hardware or software failure occurs, the MiCOM P123R closes its watchdog contact.
Alarm and Warning messages operation is identical to other MiCOM P12x devices; only normally open contacts are not used.
3 Wiring
The MiCOM P123R relay has the same terminal layout for common elements. Terminals numbers are inverted: terminals 1 to 28 are on the right side of the relay (view from the rear), and terminals 29 to 56 are on the left side. The wiring diagram is provided in this addendum.
3.1 Auxiliary supply
The auxiliary power supply for the MiCOM P123R relays can be either direct current (24-250 Vdc) or alternating current (48-240 Vac / 50-60 Hz). The auxiliary power supply must be connected only to terminals 13 (+) and 14 (−).
3.5 Communication
3.5.1 RS485 rear communication port
The MiCOM P123R terminals 9 and 10 are dedicated to the RS485 communication port. For retrofitting KCGG122 & 142 relays, if the RS485 rear communication port is used, connect a wire from terminal 54 to pin 9 and a wire from terminal 56 to pin 10.
P12x/EN GS/Eb6 : Getting Started
1.2 Auxiliary Power Supply Connections
Connect a DC or AC voltage power supply (according to nominal supply rating Ua).
POSITIVE Vaux to TERMINAL 13
NEGATIVE Vaux to TERMINAL 14
3 LOCAL CONNECTION TO A PC
3.2 Products plugged in the same panel
The connection principle for plugging a MiCOM P123R into another product in the same panel is identical to other MiCOM P12x relays. The MiCOM P123R earth terminal pin number is 1:
- A cable (green / yellow wire) must be screwed to the earth connection of each product.
- The communication cable shield must be connected to pin number 1 of each product.
- The pin number 1 of each terminal block must be connected and screwed to the case earth connection of each product.
3.3 Communication between distant products
The connection principle for plugging a MiCOM P123R to distant products is identical to other MiCOM P12x relays. The MiCOM P123R earth terminal pin number is 1:
- A cable (green / yellow wire) must be screwed to the earth connection of each product.
- The communication cable shield must be connected to the pin number 1 of each product.
- The pin number 1 of each terminal block must be connected and screwed to the case earth connection of each product.
P12x/EN CM/Eb6 : Commissioning and Maintenance
3 Product verification tests
3.7 Auxiliary supply
Check the auxiliary supply voltage (terminals 13 and 14). The measured value should be between 0.8 and 1.2 times the DC nominal auxiliary supply voltage, or 0.8 and 1.1 times the AC nominal auxiliary supply voltage.
Uaux range (Volts) | Uaux nominal zone (Volts) | Maximum peak value (Volts) |
---|---|---|
24-250 Vdc/48-240 Vac | 19.2-300 Vdc/38.4-264 Vac | 336 |
3.8 Logic inputs
The MiCOM P123R relays have 5 opto-isolated inputs. Terminal 52 is the common (–) pin for opto-isolated inputs L1 and L2, connected to pins 46 and 48 (+) respectively. Terminal 55 is the common (–) pin for opto-isolated inputs L3 to L5, connected to pins 45, 47, and 49 (+) respectively.
Input | Terminals | OP. PARAMETERS/Inputs Status cell value | |
---|---|---|---|
Pin + | Pin - (common) | ||
Opto input 1 | 46 | 52 | 00001 |
Opto input 2 | 48 | 00010 | |
Opto input 3 | 45 | 55 | 00100 |
Opto input 4 | 47 | 01000 | |
Opto input 5 | 49 | 10000 |
3.9 Logic outputs
The MiCOM P123R relays have 9 outputs. The watchdog output is a normally closed relay (WD, terminals 3-5). The RL1 to RL8 logic output relays are normally open (NO) relays.
Output | Terminals | OP. PARAMETERS/Inputs Status cell value |
---|---|---|
RL 1 | 42-44 | 00000001 |
RL 2 | 34-36 | 00000010 |
RL 3 | 38-40 | 00000100 |
RL 4 | 30-32 | 00001000 |
RL 5 | 29-31 | 00010000 |
RL 6 | 33-35 | 00100000 |
RL 7 | 37-39 | 01000000 |
RL 8 | 41-43 | 10000000 |
4 Setting checks
MiCOM P123R RELAYS HAVE 1 OR 5 AMP CURRENT INPUTS (depending on the model: refer to the label under the upper flap). CHECK THAT THE INJECTED CURRENT IS COMPATIBLE WITH THE SELECTED RANGE.
4.3 Phase overcurrent (I> and I>>)
This test wiring diagram allows for tests related to the I> and I>> thresholds. The diagram shows current injection onto the 1 or 5 Amp phase current inputs (terminals 21-22, 23-24, 25-26).
INJECTION TEST SET
FIGURE 4: I> AND I>> TESTS WIRING
5 Maintenance
5.2 & 5.3 Minor or major fault
A communication failure is considered a minor fault for MiCOM P123R relays. In case of communication fault, the MiCOM P123R protection and automation modules are unaffected, and the relay remains fully operational. The watchdog relay is energized (3-5 contact open).
Major faults for MiCOM P123R relays include all software and hardware failures except communication faults. Upon detection of a major fault, the watchdog (WD) is de-energized (3-5 contact closed), and all operations (protection, automation, communication) are stopped.
P12x/EN CO/Eb6: Connection Diagram
Diagrams illustrating connection schemes for the MiCOM P123R relay.
Note on CT connections: CT connections are typical. CT shorting links make before (b) and disconnect (c). Long terminals (a), short terminals (b) break before (c). Pin terminals are PCB type (d).
Note on Earth terminals: Earth terminals are typical.
Advice for Connection:
- A tightening torque of 1.3 Newton-metres is recommended for all screws fitted to the MIDOS terminal blocks.
- Functioning temperature is limited to 55°C.
- For any connection, use the provided kit or use cable terminals UL LISTED.
- Wiring: use copper conductors only, size AWG22 to AWG10.
Schneider Electric Contact Information
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
Publication: P123R/EN AD/A11
Publishing: Schneider Electric
09/2012
© 2012 Schneider Electric. All rights reserved.
Related Documents
![]() |
MiCOM P120, P121, P122, P123 Overcurrent Relays Technical Guide Technical guide for Schneider Electric's MiCOM P120, P121, P122, and P123 series overcurrent relays, detailing installation, commissioning, operation, and safety aspects. Includes product specifications and support information. |
![]() |
MiCOM P841 Multifunctional Line Terminal IED Technical Manual This technical manual provides comprehensive information on the installation, commissioning, operation, and maintenance of the MiCOM P841 Multifunctional Line Terminal IED. It covers safety procedures, technical data, settings, application notes, and troubleshooting. |
![]() |
Schneider Electric MiCOM C264/C264C Bay Computer Technical Guide Comprehensive technical guide for the Schneider Electric MiCOM C264/C264C Bay Computer, detailing specifications, functions, safety, installation, and maintenance for power system applications. |
![]() |
MiCOM P921/P922 & P923 Voltage and Frequency Relays Technical Guide Comprehensive technical guide for Schneider Electric's MiCOM P921, P922, and P923 Voltage and Frequency Relays, covering installation, commissioning, operation, and safety. |
![]() |
Schneider Electric Com'X 200/210/510 User Guide and Technical Specifications A comprehensive guide for Schneider Electric's Com'X 200, Com'X 210, and Com'X 510 devices, detailing installation, wiring, operation, features, and troubleshooting. Includes safety information and technical characteristics. |
![]() |
MiCOM P24x (P241, P242 & P243) Technical Manual Comprehensive technical manual for the MiCOM P24x series of rotating machine protection relays, including models P241, P242, and P243. This guide covers installation, commissioning, operation, maintenance, and troubleshooting. |
![]() |
Easergy MiCOM P64x Transformer Protection Relay Technical Manual This technical manual provides comprehensive instructions for the installation, commissioning, and operation of the Easergy MiCOM P64x series transformer protection relays, including models P642, P643, and P645. It covers safety information, technical data, settings, operation, application notes, and troubleshooting. |
![]() |
Easergy MiCOM C434 Technical Manual Comprehensive technical manual for the Schneider Electric Easergy MiCOM C434 Bay Unit, detailing its control and monitoring capabilities, specifications, operation, and communication interfaces for substation automation. |