Instruction Manual for BEOK models including: TCR8WIFI, RGB Colorful LCD Screen Smart Thermostat, TCR8WIFI RGB Colorful LCD Screen Smart Thermostat

TCR8WIFI Fan Coil Thermostat Manual

UI Rti-Tek

TCR8WIFI Fan Coil Thermostat Manual - Beok Controls

4 févr. 2022 — Scan QR code to finish network configuration swiftly, easy and convenient. Programmable device, multiple periods allowed to set per day.

RGB Colorful LCD Screen Smart Thermostat

Scan QR code to finish network configuration swiftly, easy and convenient. Programmable device, multiple periods allowed to set per day. 2.8 inches ultra-large colorful LCD screen, delicate visual effect.


File Info : application/pdf, 2 Pages, 1.20MB

PDF preview unavailable. Download the PDF instead.

TCR8WIFI-Fan-Coil-Thermostat-Manual
RGB Colorful LCD Screen Smart Thermostat

03.11 Thur

18:00

Fair 22
Humidity 68%

ROOM
25.5 

next

enter

home

back

Version:TCR8 1.0(04/2021)

Scan QR code to finish network configuration swiftly, easy and convenient.
Programmable device, multiple periods allowed to set per day.
2.8 inches ultra-large colorful LCD screen, delicate visual effect.
The device can be controlled by voice through Amazon Alexa and Google Assistant Parameter

Supply voltage Power consumption Temp. setting range Floor limited range On/off deviation Ambient temperature Protection level Shell material

AC100~240V;50~60Hz 1W Max (Wi-Fi 3W Max) 5~95 20~90 0.5~10, Factory setting ±1 - 5~50 IP20 Anti-Flammable PC

Product Overview

Auto-mode Setting

This series of thermostat has Floor Heating, Fan Coil, and Integrated version, meeting the requirements under different scenarios.

Version
Floor heating

System mode Heating

Model

Application

EP

Built-in & floor sensor, floor limit sensor + Weekly programming

WP A NC/NO dual-output + Weekly programming

WPB

A NC/NO dual-output Potential-free output

+

Weekly

programming+

Fan Coil

Heating /Cooling / Ventilation

Ac2 Timer task + 2-pipe system

Ac2485

Timer task + 2-pipe system + 485Modbus (optional)

Ac4485

Timer task + 4-pipe system + 485Modbus (optional)

Heating / Cooling /

Floor heating & fan coil, weekly programming +

Integrated Ventilation/Floor heating / AWY Potential-free output + Timer task +

Floor heating + Heating

485Modbus (optional) + Door card (optional)

When device is off, press " " to enter menu page, choose "period setting" to set parameters, then press " " to save and exit.

Events

Time Default value Modify

Sunrise 0 6 : 0 0

Morning 0 8 : 0 0

Workdays Nooning 1 1 : 3 0 Afternoon 1 2 : 3 0

Evening 1 7 : 0 0

Temperature Default value Modify
2 0 15 15 15 22

Rotate handwheel Rotate handwheel

Display Symbols

Night 2 2 : 0 0

15

Time Display
Date Week Outdoor temp.
Humidity Fan Col valve Floor Heating valve
Mode Menu Power on/off Fan Speed

03.11 Thur

18:00

Fair 22
Humidity 68%

ROOM
25.5 

next

enter

home

back

Child-lock WiFi
Room Temp.
Current mode Fan Auto Mode Manual Mode Temporary Mode
Knob

Sunrise Weekends
Night

06:00 22:00

2 0 15

Advanced Setting (Usually for Professional Technicians)
Choose "advanced setting" on menu page and put in password 123456 to enter advanced setting page, set parameters then press " " to save and exit.

Meaning Sensor Mode

Rotate handwheel
Built-in Sensor Floor Sensor Built-in Control&Floor Limitation

Default value IN

Temperature Control Mode(Floor Heating/Integrated)
Auto Mode Weekly-circled programme, up to 6 heating events can be set per day. Heating events, workdays and temperature can be separately customized based on personal routines.
Manual Mode Thermostat works based on manually-set temperature, disconnecting from auto mode.
Temporary Mode Thermostat works based on manually-set temperature temporarily and then shifts back to auto mode till next event.
User Operation
Power on/off : Long press " " to turn on/off the thermostat.

Buit-in Sensor Calibration -5~5
Buit-in Max Setting Value 5~95 Floor Max Setting Value 10~95
Limitation Value 20~95 Output Jitter Control 0~5 Anti-Freeze Protection ON/OFF

Linkage Mode

Noninverting Inverting Inverting Inverting and Anti-Freeze closed

Linkage Time Delay 0~5Min

-3 50 50 35 1 OFF
Noninverting
0Min

Weekday Mode

Monday to Friday/Monday to Saturday /Monday to Sunday/

2-day

Temp setting: Rotate handwheel" "to change setting temperature by 0.5°C. System mode: Press " " shortly to switch cooling/heating/ventilation. (Fan Coil)
Press " " shortly to switch cooling/heating/ventilation/floor heating/floor heating + heating. (Integrated) Temp control mode: Press " " shortly to switch manual/auto mode. (Floor heating) Press " " shortly to switch manual/auto mode. (Integrated, floor heating)
Enter menu: Press " " enter the menu interface. Child-lock: Press " " + " " for 3 seconds to activate child-lock.

Boot Type Temperature Unit
Child Lock Type
Control Mode Cloud Region Reset All Settings

Function Off/Function On/Function Saved
/
None Lock All All but power
All/Air/Floor
CN/US/EU
/

OFF

None
Floor CN
/

RGB Colorful LCD Screen Smart Thermostat

Installation instructions

Sensor failure
Please select work mode of sensors correctly. When it shows E0/E1 error, thermostat will stay power-off till the error is eliminated.E0: built-in sensor is short-circuited or disconnected. E1: floor sensor is short-circuited or disconnected.
Timer Task Setting (Fan Coil/Integrated)
Press" "to enter the menu page. Turn the knob" ", choose "Auto Mode", and then choose "Schedule". Set the parameters by turning the knob, then press "Home"
to save and exit to home page.

Schedule Task

Time Setting

00:00

Repeat

Everyday

Action

OFF

Dimensions (Unit: mm)

Floor Heating #EP #WP #WPB #AC2

11 32.6

51 51

Integrated #AC2-485 #AC4 #WPH

11 2 4

64 66

Mounting Steps
The thermostat adopt pre-guide and limited snap-fit design. It is easy to mount. 1Release front cover by inserting a head screw-driver into bottom crack.

2Insert the wires and then fix these wires with screws. Suggested wire-stripping length is 7-9mm.
3Mount backing plate into wall-cassette, put screws and then fix thermostat. Make sure that the thermostat is fixed without deformation. Suggested torque is 0.2~0.4N.m (2.0~4. 1kgf.cm).

4Re-mount the front cover via snap-fit connection.

Connecting Diagram
The thermostat operates in full capacity in areas with the altitude of less than 2500 above sea level. Power rating of external load should be less than or equal to 80% rated power of the thermostat in areas with altitude of 2500m to 4200m.

Floor Heating

# TCR8-WIFI-EP # TCR8-EP

L N N1 L1 AC100~240V

# TCR8-WIFI-WP # TCR8-WP # TCR8-WIFI-WPB

# TCR8-WPB

LN AC100~240V

Normally close valve 3A Max

Electro thermal actuator or electrical ball valves

NTC
PC1 PC2
Potential-free (Potential-free output, for WPB only)
Dry contact signal to control boiler

Linkage control; delay time of linkage control is adjustable
PC1 PC2

LN AC100~240V

Normally open Potential-free valve 3A Max (Potential-free output, for WPB only)

Electro thermal actuator or electrical ball valves

Dry contact signal to control boiler

Linkage control; delay time of linkage control is adjustable
PC1 PC2

Fan Coil # TCR8-WIFI-AC2 # TCR8-AC2

LN

Potential-free

AC100~240VThree-wire electrical (Potential-free output, for WPB only)

ball valve with two

types of control mode

Electro thermal actuator or electrical ball valves

Dry contact signal to control boiler

Linkage control; delay time of linkage control is adjustable

L N H M S OPEN CLOSE

LN AC100~240V
N
N
#TCR8-WIFI-AC2-485
#TCR8-AC2-485

Fan
OPEN CLOSE H

Air conditoner valve
MS L
89

N

Air conditoner

valve

Fan

L

AC100~240V

N

CARD

RG A B

16 15 14 13 12 11 10

# TCR8-WIFI-AC4 # TCR8-AC4

Room card room card linkage(optional)

485A 485B (optional)

N OPEN CLOSE OPEN CLOSE H M S L
89

N

L

heat valve cool valve

Fan AC100~240V

N

CARD

RG A B

16 15 14 13 12 11 10

Room card

485A 485B

room card linkage(optional) (optional)

Integrated
# TCR8-WIFI-AWY # TCR8-AWY

N OPEN CLOSE OPEN CLOSE H M S L
89

N

Floor heating Air conditoner

valve

valve

Fan

L

AC100~240V

N
PC1 PC2 CARD RS RG A B

Linkage control; delay time of 16 15 14 13 12 11 10

linkage control is adjustable

Dry contact signal

NTC Room card

485A 485B (optional)

to control heat pump room card linkage(optional)



References