Operating Guide
NovoCon® L/XL

NovoCon® L/XL / 73690670

NovoCon® L / SU / SD

NovoCon® XL

NovoCon® L / SU / SD AB-QM DN 125 - 150HF

NovoCon® XL AB-QM DN 200 - 250HF

MAINTENANCE FREE

5-95 % RH no condensing

NovoCon® L © Danfoss | 2021.09

NovoCon® XL AQ321852892717en-010301 | 1

NovoCon® L/XL


2×






2×

= AUTO

=

13 mm

4 mm


12-15 Nm 2×

2×






2×


12-15 Nm 2×


NovoCon® L


= AUTO

=

3,5 - 4,5 mm × 0,7mm

4 mm

T 10



3-5 Nm 2×

2 | © Danfoss | 2021.09

AQ321852892717en-010301

NovoCon® L/XL
NovoCon® L SD
1×
 








3-5 Nm 2×

NovoCon® L SU

1×







 


 
3-5 Nm 2×
AQ321852892717en-010301

© Danfoss | 2021.09 | 3

NovoCon® L/XL
 NovoCon® XL

= AUTO =

HN 10

5 mm



















3-5 Nm 2×






 

40 Nm 1× HH10


 NovoCon® XL

4 | © Danfoss | 2021.09

AQ321852892717en-010301

NovoCon® L/XL

 
0,7-1,1 Nm 2×
 

= AUTO

=

3,5­4,5 mm × 0,7 mm

T 10


M16, M20 / MP16 1/2''

M16 M20

MODE:

Normal



Calibration Flush

De-Air

M16 1/2''




AQ321852892717en-010301

GND is common for all signals

© Danfoss | 2021.09 | 5

NovoCon® L/XL



NovoCon®L
003Z8560
Actuator for AB-QM DN125-150
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA Power: 24VAC/DC, 50/60 Hz, Operating 9.6 VA Force: 2000N. Stroke: 50 mm. Speed: 3-24s/m. IP54/40, 10T55
III

E100 VX01X 281624 0030471

6430 Nordborg, Denmark MADE IN SLOVENIA

E100 VX01X 281624 0030471

Serial number and QR code can be removed from the NovoCon® L/XL label and added to installation drawing.

E100 VX01X 281624 0030471

Device Object Instance Number



DIP Switch 1 2 3 4 5 6 7 8 9 10 ON OFF

Dip switches for addressing and bus protocol selection are located under the lid of the actuator. DIP Switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU. For termination of last unit on the field bus, turn DIP Switch 8 ON. Dip switch 9 is not used. Dip switch 10 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON). When the protocol is changed on DIP Switch 10, a power cycle is required.

 Initial configuration

     Application mode: MSV:9 / 32810 Digital control (default), Analog control

Select Valve Type MSV:3 / 32802
(default AB-QM DN125)

Select application MSV:10 / 32811 Heating (default) Cooling

Design Flow Rate AV:30 / 32796 Heating AV:31 / 32798 Cooling

Activate calibration MSV:0 / 33284 state 2 or use manual calibration

     Application mode: MSV:9 / 32810 Digital control (default), Analog control

Select Valve Type MSV:3 / 32802
(default AB-QM DN200)

Select application MSV:10 / 32811 Heating (default) Cooling

Design Flow Rate AV:30 / 32796 Heating AV:31 / 32798 Cooling

Activate calibration MSV:0 / 33284 state 2 or use manual calibration

NovoCon® XL NovoCon® L

6 | © Danfoss | 2021.09

AQ321852892717en-010301

NovoCon® L/XL

 Safety Note To avoid injury and damage to persons and devices, it is absolutely necessary these instructions are carefully read and observed prior to assembly and commissioning. Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained and authorised personnel. Switch off the pump and the power line before mounting and wiring the actuator.

Safety Note
If the NovoCon® L/XL network is supplied with two or more AC power boosters, caution must be observed when disconnecting one of the transformers from the high voltage power line. As the NovoCons may be connected in a daisy chain, there may be high voltage on the primary side of the disconnected power supply. Disconnect always both the primary and secondary side of the transformer.

Safety Note
Connect via safety isolating transformer. Galvanic separations shall be provided for segments crossing buildings.

Firmware update
We recommend to validate the firmware version before installation. The latest firmware can be downloaded at www.novocon.com by selecting the tab: Support files.

AQ321852892717en-010301

© Danfoss | 2021.09 | 7

NovoCon® L/XL

Part Name

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hazardous Substances Table

Hexavalent Chromium (Cr(VI))

Polybrominated biphenyls (PBB)

Polybrominated diphenyl ethers (PBDE)

Motor

X

O

O

O

O

O

O: Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;

X: Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirement in GB/T 26572;

: UA:    « », .  , 15/15/6, . , 04080, 

8 | © Danfoss | DCS-S/SI | 2021.09

73690670 / AQ321852892717en-010301



References

Danfoss A/S Adobe PDF library 15.00