DocumentDocumentOperating Guide
NovoCon® L/XL
NovoCon® L/XL / 73690670
NovoCon® L / SU / SD
NovoCon® XL
NovoCon® L / SU / SD AB-QM DN 125 - 150HF
NovoCon® XL AB-QM DN 200 - 250HF
MAINTENANCE FREE
5-95 % RH no condensing
NovoCon® L © Danfoss | 2021.09
NovoCon® XL AQ321852892717en-010301 | 1
NovoCon® L/XL
2×
2×
= AUTO
=
13 mm
4 mm
12-15 Nm 2×
2×
2×
12-15 Nm 2×
NovoCon® L
= AUTO
=
3,5 - 4,5 mm × 0,7mm
4 mm
T 10
3-5 Nm 2×
2 | © Danfoss | 2021.09
AQ321852892717en-010301
NovoCon® L/XL
NovoCon® L SD
1×
3-5 Nm 2×
NovoCon® L SU
1×
3-5 Nm 2×
AQ321852892717en-010301
© Danfoss | 2021.09 | 3
NovoCon® L/XL
NovoCon® XL
= AUTO =
HN 10
5 mm
3-5 Nm 2×
40 Nm 1× HH10
NovoCon® XL
4 | © Danfoss | 2021.09
AQ321852892717en-010301
NovoCon® L/XL
0,7-1,1 Nm 2×
= AUTO
=
3,54,5 mm × 0,7 mm
T 10
M16, M20 / MP16 1/2''
M16 M20
MODE:
Normal
Calibration Flush
De-Air
M16 1/2''
AQ321852892717en-010301
GND is common for all signals
© Danfoss | 2021.09 | 5
NovoCon® L/XL
NovoCon®L
003Z8560
Actuator for AB-QM DN125-150
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA Power: 24VAC/DC, 50/60 Hz, Operating 9.6 VA Force: 2000N. Stroke: 50 mm. Speed: 3-24s/m. IP54/40, 10T55
III
E100 VX01X 281624 0030471
6430 Nordborg, Denmark MADE IN SLOVENIA
E100 VX01X 281624 0030471
Serial number and QR code can be removed from the NovoCon® L/XL label and added to installation drawing.
E100 VX01X 281624 0030471
Device Object Instance Number
DIP Switch 1 2 3 4 5 6 7 8 9 10 ON OFF
Dip switches for addressing and bus protocol selection are located under the lid of the actuator. DIP Switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU. For termination of last unit on the field bus, turn DIP Switch 8 ON. Dip switch 9 is not used. Dip switch 10 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON). When the protocol is changed on DIP Switch 10, a power cycle is required.
Initial configuration
Application mode: MSV:9 / 32810 Digital control (default), Analog control
Select Valve Type MSV:3 / 32802
(default AB-QM DN125)
Select application MSV:10 / 32811 Heating (default) Cooling
Design Flow Rate AV:30 / 32796 Heating AV:31 / 32798 Cooling
Activate calibration MSV:0 / 33284 state 2 or use manual calibration
Application mode: MSV:9 / 32810 Digital control (default), Analog control
Select Valve Type MSV:3 / 32802
(default AB-QM DN200)
Select application MSV:10 / 32811 Heating (default) Cooling
Design Flow Rate AV:30 / 32796 Heating AV:31 / 32798 Cooling
Activate calibration MSV:0 / 33284 state 2 or use manual calibration
NovoCon® XL NovoCon® L
6 | © Danfoss | 2021.09
AQ321852892717en-010301
NovoCon® L/XL
Safety Note To avoid injury and damage to persons and devices, it is absolutely necessary these instructions are carefully read and observed prior to assembly and commissioning. Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained and authorised personnel. Switch off the pump and the power line before mounting and wiring the actuator.
Safety Note
If the NovoCon® L/XL network is supplied with two or more AC power boosters, caution must be observed when disconnecting one of the transformers from the high voltage power line. As the NovoCons may be connected in a daisy chain, there may be high voltage on the primary side of the disconnected power supply. Disconnect always both the primary and secondary side of the transformer.
Safety Note
Connect via safety isolating transformer. Galvanic separations shall be provided for segments crossing buildings.
Firmware update
We recommend to validate the firmware version before installation. The latest firmware can be downloaded at www.novocon.com by selecting the tab: Support files.
AQ321852892717en-010301
© Danfoss | 2021.09 | 7
NovoCon® L/XL
Part Name
Lead (Pb)
Mercury (Hg)
Cadmium (Cd)
Hazardous Substances Table
Hexavalent Chromium (Cr(VI))
Polybrominated biphenyls (PBB)
Polybrominated diphenyl ethers (PBDE)
Motor
X
O
O
O
O
O