Vertiv™ Liebert XDC High Heat Density Precision Air ...

17 giu 2021 — The products covered by this instruction manual are manufactured and/or sold ... Vertiv™ Liebert XDC I User Manual ... Connecting Refrigeration Piping .

Vertiv™ Liebert XDC High Heat Density Precision Air Conditioner

PDF preview unavailable. Download the PDF instead.

liebert-xdc-user-manual
VertivTM Liebert® XDC High Heat Density Precision Air Conditioner
User Manual

VertivTM | Liebert® XDC | User Manual

The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.

Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com for additional assistance.

Product XDC XDC

BOM 31014396 31014396

Version 1.0 1.0

Date 17-06-2021 29-01-2021

Revision R1 R0

VertivTM | Liebert® XDC | User Manual

This page is intentionally left blank.

VertivTM Liebert® XDC I User Manual
Table of Contents
1 Overview...................................................................................................................................................................................................................................1 1.1. Product Introduction.................................................................................................................................................................................................. 1
1.1.1. Energy Saving.......................................................................................................................................................................................................1 1.1.2. Diversified Terminal Types.....................................................................................................................................................................2 1.2. Model Nomenclature...............................................................................................................................................................................................4 1.3. Product Appearance................................................................................................................................................................................................ 5 1.4. Main Components...................................................................................................................................................................................................... 5 1.4.1. Compressor...........................................................................................................................................................................................................5 1.4.2. Sight Glass............................................................................................................................................................................................................6 1.4.3. Color Display Screen...................................................................................................................................................................................6 1.4.4. Safety Control Device................................................................................................................................................................................ 7 1.4.5. Oil Separator....................................................................................................................................................................................................... 7 1.4.6. Remote Monitoring Software.............................................................................................................................................................. 7 1.4.7. Outdoor Unit........................................................................................................................................................................................................ 7 1.5. Refrigerant Requirements....................................................................................................................................................................................7 1.6. Environmental Requirements.......................................................................................................................................................................... 8 1.6.1. Operating Environment.............................................................................................................................................................................8 1.6.2. Storage Environment.................................................................................................................................................................................8
2 Mechanical Installation...........................................................................................................................................................................................9 2.1. Equipment Room Requirements................................................................................................................................................................... 9 2.2. Maintenance Space Requirements........................................................................................................................................................... 9 2.3. Unpacking and Inspection...............................................................................................................................................................................10
2.3.1. Transportation and Handling...........................................................................................................................................................10 2.3.2. Unpacking...........................................................................................................................................................................................................11 2.4. Inspection........................................................................................................................................................................................................................ 12 2.5. Installation Notes...................................................................................................................................................................................................... 12

VertivTM Liebert® XDC I User Manual
2.6. System Installation Layout..............................................................................................................................................................................13 2.6.1. Overall System Layout.............................................................................................................................................................................13 2.6.2. System Installation Diagram............................................................................................................................................................ 14
2.7. Installation of the Unit...........................................................................................................................................................................................15 2.7.1. Mechanical Parameters..........................................................................................................................................................................15 2.7.2. Leveling the Cabinet................................................................................................................................................................................ 16 2.7.3. Removing Leveling Feet and Fixing Cabinet.....................................................................................................................17 2.7.4. Parallel Connecting Cabinets.......................................................................................................................................................... 19
2.8. Unit Piping Installation.......................................................................................................................................................................................20 2.8.1. Connecting Refrigeration Piping................................................................................................................................................. 20 2.8.2. Dimension Refrigerant Piping........................................................................................................................................................22 2.8.3. Branch Manifold...........................................................................................................................................................................................24 2.8.4. Connecting Refrigerant Piping.....................................................................................................................................................25 2.8.5. Air Tightness Test.....................................................................................................................................................................................26 2.8.6. Charging Refrigerant Oil......................................................................................................................................................................26
2.9. Remove Transportation Fixing Plate of Compressor............................................................................................................28 2.10. Mechanical Installation Checklist..........................................................................................................................................................29
3 Electrical Installation..............................................................................................................................................................................................30 3.1. Installation Tasks and Cautions..................................................................................................................................................................30
3.1.1. Cabling Connection at the Site....................................................................................................................................................... 30 3.1.2. Installation Notes........................................................................................................................................................................................ 30 3.2. Cabling of the Unit...................................................................................................................................................................................................31 3.2.1. Electrical Interface Location of the Unit.................................................................................................................................31 3.2.2. Connection of Unit Power Supply Cables..........................................................................................................................32 3.3. Control Cables Connections......................................................................................................................................................................... 33 3.4. Electrical Inspection Checklist...................................................................................................................................................................35
ii

VertivTM Liebert® XDC I User Manual
4 System Startup and Commissioning.....................................................................................................................................................36 4.1. Startup and Commissioning...........................................................................................................................................................................36
4.1.1. Preparation Before Commissioning........................................................................................................................................... 36 4.1.2. Vacuuming........................................................................................................................................................................................................ 36 4.2. MCB Position................................................................................................................................................................................................................37 4.3. Static Refrigerant Charge.................................................................................................................................................................................37 4.4. Dynamic Refrigerant Charging...................................................................................................................................................................37 4.5. Commissioning Inspection Checklist...................................................................................................................................................38
5 Color Display Screen Operating Instructions..............................................................................................................................39 5.1. Features..............................................................................................................................................................................................................................39 5.2. Appearance...................................................................................................................................................................................................................39 5.3. Color Screen Interface....................................................................................................................................................................................... 40
5.3.1. Startup Interface..........................................................................................................................................................................................40 5.3.2. Main Interface of the Color Screen...........................................................................................................................................40 5.3.3. Operation Example...................................................................................................................................................................................42 5.4. Other Interfaces........................................................................................................................................................................................................43 5.4.1. Alarm Status.................................................................................................................................................................................................... 43 5.4.2. Main Unit Menu...........................................................................................................................................................................................44 5.4.3. Terminal Menu............................................................................................................................................................................................. 45 5.4.4. Run Time...........................................................................................................................................................................................................46 5.4.5. About......................................................................................................................................................................................................................47
6 System Operation and Maintenance.....................................................................................................................................................48 6.1. Routine Maintenance Inspection (Monthly)..................................................................................................................................48 6.2. Routine Maintenance Inspection (Semi-annual).....................................................................................................................49 6.3. System Troubleshooting Test.....................................................................................................................................................................50 6.4. Electrical Connection Inspection.............................................................................................................................................................50
6.4.1. Electrical Maintenance.........................................................................................................................................................................50

VertivTM Liebert® XDC I User Manual
6.4.2. Control Maintenance.............................................................................................................................................................................50 6.5. Cooling System...........................................................................................................................................................................................................51
6.5.1. Suction Pressure...........................................................................................................................................................................................51 6.5.2. Exhaust Pressure........................................................................................................................................................................................51 6.6. Terminal Electronic Expansion Valve....................................................................................................................................................51 6.7. Terminal Fan................................................................................................................................................................................................................. 52 6.8. Air-cooled Condenser......................................................................................................................................................................................... 52 6.9. Compressor................................................................................................................................................................................................................... 52 6.10. Mechanical Failure...............................................................................................................................................................................................53 6.11. Electrical Failure......................................................................................................................................................................................................53 7 Troubleshooting...........................................................................................................................................................................................................54 Appendix I: Circuit Diagram of VertivTM Liebert® XDC............................................................................................................57 Appendix II: Alarm Output Menu....................................................................................................................................................................58 Appendix III: Hazardous Substance Content....................................................................................................................................59 Appendix IV: List of Maintenance Inspection Items (Semi-annual).........................................................................60 Appendix V: Toxic and Hazardous Substances or Elements...........................................................................................61
iv

1 Overview
This chapter introduces the product description, model description, product appearance and main components of VertivTM Liebert® XDC High Heat Density Precision Air Conditioner (hereafter referred as Liebert XDC). The Liebert XDC is a specially engineered equipment for the applications which does not permit any unauthorized and unqualified access in the system. It must be used only by professionally trained personnel if it is placed in shopping malls, light industry, or any business environment.
1.1. Product Introduction
The Liebert XDC main unit is a large, multi-connected precision environmental control equipment, suitable for the environment control of medium and large computer rooms, modular computer rooms and similar ecosystem that also calls for energy-saving, high heat density and reliability requirements. It is specifically designed to ensure precision equipment such as sensitive equipment, industrial process equipment, communication equipment and computers have a reasonable and safe operating environment.
Liebert XDC is highly effective and efficient in solving the problem of heat dissipation in server rooms with high heat density, and it is installed where cooling load changes drastically.
It is also configured with VertivTM Liebert® XD multi-connected air conditioners with the following features
1.1.1. Energy Saving
The Liebert XDC main unit adopts a high-efficiency variable capacity compressor, and Liebert XD terminal adopts highefficiency EC fan, high-precision electronic expansion valve control device. The Liebert XD terminal has three types: VertivTM Liebert® XDH, VertivTM Liebert® XDV, and VertivTM Liebert® XDO, which can be flexibly selected for different application environments. It is placed close to the server, reducing the air supply distance; improving efficiency and energy saving.
The unit provides real-time compressor operating status, terminal operating status, indoor ambient temperature, outdoor ambient temperature, outdoor fan running status, etc., and also enable to adjust the status of each operating component of the system in real time to make the system run in the most energy-saving state. The XD multi-connected air conditioning system has a new PID optimization algorithm that significantly improves the energy efficiency ratio of the system under different compressor outputs. The system energy efficiency comparison between Liebert XD multi-connected air conditioner and traditional computer room air conditioner is shown in Figure 1-1.

Figure 1-1 System Optimization Algorithm Comparison

1

Overview

1.1.2. Diversified Terminal Types
The VertivTM Liebert® XD terminal air conditioners are arranged close to the server, and the diversified layout can be applied to different installation and use environments, as shown in Figure 1-2, Figure 1-3, and Figure 1-4.
Note: For the related contents of the Liebert XD terminal, please refer to the user manual of the respective terminal (for example VertivTM Liebert® XDH, VertivTM Liebert® XDO, and VertivTM Liebert® XDV).

Figure 1-2 Liebert XDH Layout Diagram

Figure 1-3 Liebert XDO Layout Diagram

VertivTM | Liebert® XDC | User Manual

2

Figure 1-4 Liebert XDV Layout Diagram
· Precision Control VertivTM Liebert® XD air conditioner can accurately control temperature and humidity. The indoor temperature control range is from 18 °C to 40 °C, the temperature adjustment accuracy can reach the setpoint of ±1 °C, and the temperature change rate is less than 5 °C/hour. If the temperature fluctuation exceeds the limit, the system will send a remote alarm signal. The indoor relative humidity control range is from 20% to 80% RH, and the control accuracy can reach the setpoint of ±5% RH.
· Convenient and Durable Durable parts, compact structure, small overall sizes; unique structure design frame which is stable, strong and easy to disassemble and can be easily handled under extreme conditions.
· Highly Efficient Refrigerant In order to meet the international requirements, the unit uses R410A a highly efficient refrigerant.
· Multiple Protection The built-in automatic alarm and diagnosis functions protect the air conditioner unit in all aspects, and can more effectively prevent the occurrence of failures, can identify the fault location more quickly that effectively extend the service life of the air conditioner unit.
· Easy to Maintain VertivTM Liebert® XDC unit adopts a front door opening arrangement which helps in accessing all the live parts for the maintenance from the front side, and also enable the compact footprint of the unit.

3

Overview

1.2. Model Nomenclature
The VertivTM Liebert® XDC is defined by twelve digits, as represented in Table 1-1. Table 1-1 VertivTM Liebert® XDC Nomenclature

1 2 3 4 5 6 7 8 9 10 11 12

XDC 1 3 0 RM 1 L A 1

Digit 1, 2 Product Model

XD

X-treme High Density

Digit 3 Cooling System

C

Compressor

P

Pump

Digit 4, 5, 6 Cooling Capacity kW

0-9

130 kW

Digit 7 Redundancy

R

Pump Redundancy

9

Dual Invert Compressor

Digit 8 Power Supply

M

380 V to 400 V, 3 Ph, 50 Hz

N

380 V to 415 V, 3 Ph, 50 / 60 Hz+N

Digit 9 Refrigerant

1

R410A

2

R134A

Digit 10 Installation Option

L

In-row Installation

R

Perimeter Installation

Digit 11 System Type

2

2 Way Water Valve

3

3 Way Water Valve

A

Air-cooled

Digit 12 Order Identifier

1

With Dehum function (China XDP Only)

C

China Version

A

America Version

E

EMEA

The standard components are represented in `Bold Italic' font in

VertivTM | Liebert® XDC | User Manual

4

1.3. Product Appearance
The appearance of VertivTM Liebert® XDC main unit is shown in Figure 1-5.

High Heat Density Main Unit Between Rows

High Heat Density Main Unit in Room

Figure 1-5 Air Conditioner Appearance Drawing

1.4. Main Components
The Liebert XDC main unit mainly has a compressor, sight glass, safety control device, oil separator, compressor's driver color screen and other supporting components.

1.4.1. Compressor
The unit uses a high-efficiency variable capacity compressor, as shown in Figure 1-6. This compressor not only have the characteristics of low vibration, low noise and high reliability, but also can automatically adjust the speed and output difference capabilities according to the changes in cooling requirements, which greatly improves the overall energy efficiency of the system.

Figure 1-6 Variable Capacity Compressor

5

Overview

1.4.2. Sight Glass
The unit is provided with a system cycle window that allows user to observe the state of the refrigerant and to determine the moisture content of the system. When the moisture content of the system exceeds the standard, its background color changes from green to yellow.
Figure 1-7 Sight Glass
1.4.3. Color Display Screen
Liebert XDC main unit is equipped with a 7-inch HMI color screen display configuration that has a simple user interface and multi-level password protection which can effectively prevent the illegal operations. It has power-down self-recovery function, and high/low voltage protection function. It can display the running status of set parameters of the components in real time. Through the menu operation, you can accurately understand the running time of each key components. The expert fault diagnosis system can automatically display the current fault, which helps maintenance personnel to maintain the unit. It can store up to 1000 historical event records.

Figure 1-8 Color Display Screen

VertivTM | Liebert® XDC | User Manual

6

1.4.4. Safety Control Device
Each VertivTM Liebert® XDC system is equipped with high-pressure protection, low-pressure protection and exhaust temperature protection devices. When the compressor's discharge pressure or discharge temperature is too high, an emergency alarm is triggered and protection protocol is executed; when the compressor cannot work normally due to low suction pressure, an alarm signal is triggered and protection protocol is executed.
1.4.5. Oil Separator
The unit uses a high-efficiency oil separator with oil separation efficiency of 90% or more, ensuring stable oil return from the compressor.
1.4.6. Remote Monitoring Software
Liebert XDC air conditioner is provided with the standard industrial communication protocols such as Modbus RTU protocol (default), RS485 interface, and computer to computer serial communication.
1.4.7. Outdoor Unit
For outdoor unit related information, please refer to VertivTM Liebert® LVC Series Condenser User Manual.
1.5. Refrigerant Requirements
· Do not use inferior quality refrigerant as it can cause an extensive damage to the system. · Vertiv does not undertake any responsibility for all the related consequences that result from using a
inferior quality refrigerant.

7

Overview

1.6. Environmental Requirements

1.6.1. Operating Environment
The operating environment of the VertivTM Liebert® XDC main unit meets the requirements of GB4798.3-2007, as shown in Table 1-2.
Table 1-2 Operating Environment Requirements

Items
Ambient temperature
Main unit protection level Altitude Operating voltage range Pollution level

Requirements

Indoor Outdoor IP20

18 °C to 40 °C, RH<60%
-15 °C to 45 °C (Please contact Vertiv when outdoor temperature below -15 °C)

<1000m, more than 1000m, please contact Vertiv Technology

380 V to 415 V (-10% to +6%) V, 3 N~, 50 Hz/60 Hz

Level II

1.6.2. Storage Environment
The storage environment of the Liebert XDC main unit meets the requirements of GB4798.1-2005, see Table 1-3 for details.
Table 1-3 Storage Environment Requirements

Items Storage environment

Requirements Indoor, clean (no dust)

Environment humidity <95%RH

Ambient temperature Storage time

-25°C to +55°C
The total transportation and storage time does not exceed 6 months, and the performance needs to be re-calibrated after 6 months

VertivTM | Liebert® XDC | User Manual

8

2 Mechanical Installation
This chapter introduces the mechanical installation of the VertivTM VertivTM Liebert® XDC main unit, including computer room requirements, maintenance space requirements, equipment handling, unpacking, inspection, installation notes, system installation layout, installation of unit piping and installation inspection, etc.
2.1. Equipment Room Requirements
The equipment room requirements are as follows:
1. In order to ensure the normal operation of the environment control system, the equipment room should be moistureproof and heat-insulated.
2. The equipment room must have the moisture-proof layer of the ceiling and walls must be made of polyethylene film or painted with moisture-proof paint.
3. The entry of outdoor air may increase the load of the system, so it is necessary to minimize the entry of outdoor air into the equipment room. It is recommended that the intake of outdoor air be kept below 5% of the entire indoor air circulation.
4. All doors and windows should be fully enclosed.
5. The thermal load of the computer room should not be less than 30% of the rated cooling capacity of the unit.
· The Liebert XDC precision air-conditioner main unit is prohibited to be used in the open harsh outdoor environment.
· Keep the unit upright, place it indoors, keep it away from damp and low-temperature places, and avoid contact damage.
2.2. Maintenance Space Requirements
The Liebert XDC unit can be installed in two ways: `Installation between rows' and `installation in room', customers can flexibly choose the respective model according to the actual application.
· Maintenance Space Requirements
User can choose installation between rows or installation in room, both of which require opening of the front door and the rear door for maintenance. (In some cases, the main unit requires opening of the side door with the display screen). The maintenance space of at least 600 mm should be provided at the front, rear and display side of the unit, as shown in Figure 2-1.

Maintenance space of main unit between rows

Maintenance space of main unit in room

Figure 2-1 Schematic Diagram of Unit Maintenance Space

9

Mechanical Installation

The minimum maintenance space requirements of the unit are shown in Table 2-1.

Table 2-1 Minimum Maintenance Space (unit: mm)

Location Front door

Minimum Maintenance Clearance 600 mm

Rear door Display screen side

600 mm 600 mm

Note: · These spaces are used for daily maintenance of the unit. · The front door of the unit is defined as the side with the display screen, and the side opposite the front door is the rear door. · The main units that are installed between the rows, only require maintenance space at the front and rear sides. · In case of a special application, consult Vertiv local representative.

2.3. Unpacking and Inspection

2.3.1. Transportation and Handling
1. When transporting, the priority shall be given to rail or water transportation. If user choose road transportation then a road with better road conditions should be select to prevent excessive bumps.
2. VertivTM VertivTM Liebert® XDC unit is heavy. Refer Table 2-3 for weight parameters. Mechanical handling tools, such as electric forklifts are required for unloading and handling.
3. When transporting, transport the unit to the place closest to the installation site. Figure 2-2 illustrates the forklift lifting the unit and the fork should be at the center of gravity to prevent tipping of the unit.

Figure 2-2 Forklift Position to Lift the Unit

VertivTM | Liebert® XDC | User Manual

10

While moving the indoor unit, keep the obliquity within the range of 75° to 105°, as shown in Figure 2-3.
Figure 2-3 Handling Angle
2.3.2. Unpacking
The unit's cabinet is packed with honeycomb cardboard and stretch film. After moving the unit to the place closest to the final installation site, unpack it. The unpacking procedures are as follows: 1. First remove the top cover and winding stretch film, then remove the honeycomb cardboard, as shown in Figure 2-4.

ITEMS DESCRIPTION

ITEMS DESCRIPTION

1

Top cover

2

Remove the top cover

3

Honeycomb cardboard

4

First remove the winding stretch film and then remove the honeycomb cardboard

Figure 2-4 Unpacking the Unit

2. Remove the bottom pallet, the unit is fixed on the bottom pallet with M8x20 and M8x80 screws (as shown in Figure 2-5), and a 17 mm open wrench, ratchet wrench or socket can be used for disassembly.

11

Mechanical Installation

ITEMS 1

DESCRIPTION

ITEMS DESCRIPTION

Screw GB9074_13-88_M8 x 20

2

Hexagon head bolt GB/T 5782-2000_M8 x 80

Figure 2-5 Bottom Pallet Screw Fixing Position

2.4. Inspection
After unpacking, check whether the accessories are complete according to the packing list (the VertivTM Liebert® XDC accessories list is shown in the following Table 2-2), and check whether any part is obviously damaged.
If any part is found to be missing or damaged during inspection, or if any concealed damage is identified, it should be reported immediately to the carrier, Vertiv local representative and product supplier.
Table 2-2 Liebert XDC Accessories List

Name

Specifications

Quantity Usage

User manual

Paperback (A4 Booklet) 1

Engineering sight glass

Connection size 16

2

L-shaped cabinet parts and matching screws

Screw specifications GB819_1_2000_M5x12

4

On-site reference use.
To be welded on the main liquid piping at site, one for each refrigerant piping system. It is use to see while charging the refrigerant and to observe the state of the refrigerant in the system.
If the Liebert XDC main unit is installed between the rows, user can fix it with the adjacent cabinets by combining the cabinets.

2.5. Installation Notes
1. The Liebert XDC main unit is recommended to be installed between the rows or on the floor of the equipment room or the computer room. According to the diversified types of VertivTM Liebert® XD terminals, user can choose VertivTM Liebert® XDH floor installation, VertivTM Liebert® XDO (ceiling mounted at cold aisle), VertivTM Liebert® XDV placed on the server rack.
2. Prior to installing the unit, confirm whether the installation environment meets the requirements (refer Section 1.6 Environment Conditions), and confirm whether the building need any modification to match the requirement of pipeline's layout, for more details consult Vertiv local representative.
3. The installation must strictly follow the design drawings, and reserve maintenance space for daily maintenance and repairs. Refer to the engineering dimension drawing provided by the manufacturer.

VertivTM | Liebert® XDC | User Manual

12

2.6. System Installation Layout
2.6.1. Overall System Layout
VertivTM Liebert® XDC air conditioner contains at least two cooling systems. The installation and application methods of these two cooling systems are same, but the pipelings are completely independent. The overall system layout is shown in Figure 2-6.

Figure 2-6 Overall layout of the system
Note: Figure 2-6 shows a schematic diagram of Liebert XDC with a Terminal Fan, in actual practise the number of fans may be more than 2. Note: Each system of the Liebert XDC main unit can be equipped with multiple cooling terminals. In Figure 2-6, one system is equipped with 2 terminals, which is only for an example. Note: The terminal type is not limited to VertivTM Liebert® XDH, VertivTM Liebert® XDV, VertivTM Liebert® XDO, consult Vertiv Technical Team for more details.

13

Mechanical Installation

2.6.2. System Installation Diagram
The bottom piping of VertivTM Liebert® XDC unit is in the outlet mode that supports at least two cooling systems. The installation and application methods of these two cooling systems are same, but the pipelines are completely independent. Figure 2-7 shows the installation of the piping when the outdoor unit is placed higher than the indoor unit with single system and Figure 2-8 shows the installation of the piping when the outdoor unit is placed lower than the indoor unit with single system.

ITEMS 1 2 3 4 5

DESCRIPTION

ITEMS DESCRIPTION

Condenser

6

Floor

No direct sunlight

7

Heat insulation

Oil return bend

8

Floor

Slope

9

Slope

Seals

Figure 2-7 Installation of Terminal or Outdoor Unit Higher than Liebert XDC

VertivTM | Liebert® XDC | User Manual

14

ITEMS DESCRIPTION

ITEMS DESCRIPTION

1

Condenser

3

Floor

2

Slope

4

Oil return bend

Figure 2-8 Installation of Terminal or Outdoor Unit Lower than Liebert XDC

Note: Refer to the installation diagram to ensure that the relevant pipeline is at least 1/100 inclination.
Note: Refer to the installation diagram. When the outdoor unit is higher than Liebert XDC, or the terminal is lower than Liebert XDC, pay attention to install an oil trap on the air pipe.

2.7. Installation of the Unit

2.7.1. Mechanical Parameters
The VertivTM Liebert® XDC unit dimensions and mechanical parameters are shown in Figure 2-8 and Table 2-3.

Figure 2-9 Dimension of Liebert XDC

15

Mechanical Installation

Table 2-3 Mechanical Parameters of VertivTM Liebert® XDC

Product Model XDC1309N1LAC XDC1309N1RAC

Mechanical Parameters (WxDxH) (mm)
600x1100x1944

Net Weight of Equipment (kg)
320

Note: The total cabinet height including leveling feet is 2000 mm; and total height excluding leveling feet is 1944mm.
2.7.2. Leveling the Cabinet
The followings are steps to level the Liebert XDC cabinet 1. Place the unit on the open floor of the installation site. 2. Use an adjustable wrench to loosen the fastening nuts on the 4 hexagonal bolts in a clockwise direction
(refer Figure 2-10). 3. Turn the hexagonal bolt at the bottom of the foot until the foot is raised or lowered to the desired position. Use a spirit
level to ensure that the cabinet is in a horizontal position, as shown in Figure 2-11.

ITEMS 1 2

DESCRIPTION Fixing nut The feet rise or drop

ITEMS DESCRIPTION

3

Hexagon bolt

Figure 2-10 Leveling Feet

4. Tighten the fastening nut on the anchor screw counterclockwise to complete the adjustment. If there is a mounting bracket in the equipment room, user needs to remove the leveling feet and fix the cabinet on the mounting bracket.

VertivTM | Liebert® XDC | User Manual

16

2.7.3. Removing Leveling Feet and Fixing Cabinet
To avoid personal injury and damage to the unit, the operation should be performed by two trained professional.

ITEMS 1 2

DESCRIPTION Front top fixing hole Rare top fixing hole

ITEMS DESCRIPTION

3

Front bottom fixing hole

4

Rare bottom fixing hole

Figure 2-11 Cabinet Fixing Holes

· Remove the Leveling Feet
1. Use an adjustable wrench to loosen the fastening nuts on the 4 hexagonal bolts in turn clockwise.
2. Turn the hexagonal bolt at the bottom of the leveling foot clockwise until the foot falls off the cabinet frame.
· Fix the Cabinet
There are two holes on each side of the top, bottom, front, and rear, as shown in Figure 2-11. Four bottom holes are bolted to the floor bracket in the equipment room (front fixing holes at the bottom of the cabinet are symmetrical to the rear fixing holes, and only the front fixing holes are shown in the figure). The four holes at the top can be connected to the top bracket of the room after they are installed with bolts.

17

Mechanical Installation

· Location of the Piping Outlet Position and Sizes on Bottom Plate Table 2-4 shows the outlet piping specifications of the VertivTM Liebert® XDC host.
Table 2-4 Liebert XDC Piping Outlet Specifications

Pipeline Type

Pipe Size (OD, mm)

Suction Line

28

Discharge Line

22

The location and dimensions of the inlet and outlet piping of the unit at the bottom plate are shown in Figure 2-12

ITEMS DESCRIPTION

ITEMS DESCRIPTION

1

Control cable entry

4

#1 Discharge

2

Power input entry

5

#2 Suction

3

#1 Suction

6

#2 Discharge

Figure 2-12 Inlet and Outlet Location on the Bottom Plate of the unit

Note The front side of the unit is defined as the side with the display screen, and the opposite side is the rear side.

VertivTM | Liebert® XDC | User Manual

18

2.7.4. Parallel Connecting Cabinets
If the VertivTM Liebert® XDC is installed between the rows, it needs to be combined with the server rack. There are connecting parts which helps in connecting the cabinet in parallel to the server racks, where users can easily fix them with adjacent cabinets. Note: Ensure to level the cabinets, before connecting the cabinets in parallel. For the adjustment method, refer Section 2.7.2 Leveling the Cabinets.
Following are the steps for connecting the cabinets in parallel
1. Remove the L-shape combined cabinet part from the unit accessories kit. Figure 2-13 shows position A (left) of the L-shape combined cabinet parts.
2. Use M5 countersunk screws to fix the cabinet parallel connecting parts (L-shaped) on the unit frame (hinge side) and the installation holes of the adjacent server rack, as shown in Figure 2-13.
3. Repeat the Step 1 and Step 2 for all other cabinets.

ITEMS 1

DESCRIPTION

ITEMS DESCRIPTION

Mounting screw GB819_1_2000_M5 x 12

2

Parallel kit

Figure 2-13 Connecting the Unit and Server Racks in Parallel

19

Mechanical Installation

2.8. Unit Piping Installation
2.8.1. Connecting Refrigeration Piping
Prior to the piping installation, user needs to calculate the length and height difference of each pipes, and the piping specifications are provided in Table 2-5.
Figure 2-14 shows the piping connection that needs to be consider, including: Discharge pipe L1, Liquid return pipe L2, Suction pipe L3, branch liquid pipe L4, and branch suction pipe L5.

ITEMS 1 2 3 4 5

DESCRIPTION Discharge pipe Liquid pipe Sight glass Suction pipe Suction distributor

ITEMS DESCRIPTION

6

Branch suction pipe

7

Liquid distributor

8

Branch liquid pipe

9

Ball valves

10

Dry filter for XDO and XDV

Figure 2-14 Engineering Pipeline Diagram

VertivTM | Liebert® XDC | User Manual

20

Table 2-5 Maximum Allowable Difference

Parameters

Maximum length of pipeline
Height difference

Maximum equivalent length of discharge pipe L1

Maximum equivalent length of liquid return pipe L2

Maximum equivalent length of suction pipe L3

Maximum equivalent length of branch liquid pipe L4

Maximum equivalent length of branch discharge pipe L5

Height difference between main unit and condenser H1

Condenser on top Condenser at bottom

The height difference between terminal Condenser on top

and condenser H2

Condenser at bottom

Height difference between terminal and Main unit on top

main unit H3

Main unit at bottom

Height difference between terminals H4

Maximum Allowable Value(m) 70 130 60 40 40 20 5 40 10 20 5 15

Note: For the applications with larger piping lengths or height differences, consult Vertiv local representative.

Example

The calculation of the piping equivalent length are as follows:

For the discharge pipe L1, if the actual length is 30 m, then 90° elbows; two oil traps are used; and the pipe diameter is 25 mm, the equivalent length of the discharge pipe is: 30 + 0.5 x 10 + 3.4 x 2 = 41.8 (m)

Refer to Table 2-6 to confirm the local equivalent length according to the pipe diameter.

Table 2-6 Local Equivalent Length

Pipe Diameter

Local Equivalent Length (m)

(mm) (inch) 90°elbow

45°elbow

"T" Shaped 3-way Connector Oil Trap

9.52

3/8

0.21

0.10

0.76

1.3

12.7

1/2

0.24

0.12

0.76

1.5

16

5/8

0.27

0.15

0.76

2.0

19

3/4

0.3

0.18

0.76

2.4

22

7/8

0.44

0.24

1.1

3.0

25

1

0.5

0.27

1.2

3.4

28

1-1/8

0.56

0.3

1.4

3.7

32

1-1/4

0.62

0.34

1.6

4.0

35

1-3/8

0.68

0.38

1.8

4.4

21

Mechanical Installation

2.8.2. Dimension Refrigerant Piping
According to the rated cooling capacity and equivalent piping length of the VertivTM Liebert® XDC with the rated single system, select the specifications of discharge pipe L1, Liquid return pipe L2, and Suction pipe L3, from Table 2-7, Table 2-8, and Table 2-9 respectively.
According to the terminal type, the rated cooling capacity of the terminal and the equivalent piping length, select the specifications of the branch liquid pipe L4 and the branch gas pipe L5 from Table 2-10.
Table 2-7 Discharge Pipe Diameter Requirements

Liebert XDC Rated Cooling Capacity of Single System (kW)

Equivalent Pipe Length L (m)
0-20

Discharge Pipe L1 OD (m)
19

35A50

20-40

22

40-70

25

0-20

22

50 <A65

20-40

25

40-70

28

Table 2-8 Diameter Requirements of Liquid Return Pipe

Rated Cooling Capacity of Single Liebert XDC System (kW)

Equivalent Pipe Length L (m)
0-30

Liquid Return Pipe L2 - OD (m)
16

35A50

30-60

16

60-90

19

90-140

22

0-30

16

50 <A65

30-60

19

60-90

22

90-140

25

VertivTM | Liebert® XDC | User Manual

22

Table 2-9 Diameter of the Suction Pipe

Rated Cooling Capacity of Single VertivTM Liebert® XDC System (kW)

Equivalent Pipe Length L (m)
0-20

35A50

20-40

40-60

0-20

50 <A65

20-40

40-60

Suction Pipe L3 - OD (m) 25 28 32 28 32 35

Table 2-10 Diameter of Branch Gas Pipe and Branch Liquid Pipe

Rated Cooling Capacity of Terminal (kW)

Equivalent Pipe Length - L (m)
0-20

Branch Liquid Pipe L4 - OD (m)
12.7

Branch Gas Pipe L5 - OD (m)
19

XDV010

20-40

12.7

22

40-60

16

22

0-20

16

22

XDO020

20-40

16

25

40-60

19

28

0-20

16

22

XDH030

20-40

16

25

40-60

19

28

The wall thickness requirements of copper piping at site are shown in Table 2-11.

Table 2-11 Wall Thickness Requirements of Piping

Piping Size (Outer Diameter mm)

Wall Thickness (mm)

16

1

19

1

22

1

25

1.1

28

1.2

32

1.5

35

1.5

Note: The sizes of copper piping are shown in Table 2-11, it must be a hard pipe (Y) specified in the national standard GB/T18033-2007. If a semi-hard or soft copper pipe is used at the site, consult Vertiv technical team for the wall

23

Mechanical Installation

thickness selection, otherwise it may cause system leakage or pipe burst. Improper selection of the piping material may cause system leakage or piping burst, contact Vertiv local representative for more details.
2.8.3. Branch Manifold
As shown in Figure 2-15 and Figure 2-16, when connecting the main piping and the branch piping, a branch manifold installation is required. If the branch manifold is not available then a T-shaped 3-way connector with suitable pipe diameter can be used. Before connecting the branch manifold, cut the branch manifold according to the pipe diameter of the branch pipe.
Figure 2-15 Branch Manifold of Suction Pipe
Figure 2-16 Branch Manifold of Liquid Return Pipe After selecting the appropriate pipe diameter, use a micro cutter to break the piping according to the actual piping on site, refer Figure 2-17 for better understanding.

ITEMS DESCRIPTION

1

Interrupt according to the actual situation on site

Figure 2-17 Branch Manifold Processing

Note: Remove the residual burrs after cutting the piping to avoid choking in the piping.

VertivTM | Liebert® XDC | User Manual

24

2.8.4. Connecting Refrigerant Piping
When connecting the refrigerant pipeline, the following requirements must be strictly observed: 1. Before brazing all the copper pipes, release the air present in the piping by opening each ball valves at least for 15min to
avoid absorption of moisture with the compressor's lubricating oil. 2. All refrigeration pipe joints must be silver brazed; 3. During pipe brazing, if necessary pipe support fixture is required, fill the pipe with nitrogen, preventing excessive
oxidation during brazing and forming an oxide film on the inner wall of the pipe. 4. Ensure a certain inclination when installing the pipeline. 5. When installing the branch manifold, ensure that the branch piping are in horizontal, as shown in Figure 2-18; 6. Corresponding labels are affixed to the pipe joints. Avoid burning the labels when brazing;

ITEMS DESCRIPTION

1

Suction distributor

ITEMS DESCRIPTION

2

Liquid distributor

Figure 2-18 Horizontal Placement of Branch Manifold

When brazing, fill the refrigerant piping with nitrogen to prevent the formation of the oxide scaling due to brazing process that may damage the compressor.

25

Mechanical Installation

2.8.5. Air Tightness Test
After completion of the brazing of piping, the nitrogen gas must be used for leak detection and to ensure that the system does not have any sign of leakage. The system must strictly follow the segmented leak detection:
1. According to the valve labeling (refer Figure 2-6), close the suction and discharge ball valves of the two VertivTM Liebert® XDC systems, a total of 4 Nos; open all the ball valves at theVertivTM Liebert® XD cooling terminal.
Once all ball valves are open, each system is divided into two sections: a) The inside of Liebert XDC is the low-pressure section. Check the pipeline for the sign of leakage which including compressor, oil separator and connecting piping. b) The outside of Liebert XDC is the high-pressure section. Check the pipeline for the sign of leakage, including the condenser, all cooling terminals and connecting piping.
2. To detect the sign of leakages in the low pressure section, pressurize the schrader valve2 to 31 bar.
3. To detect the sign of leakages in the high pressure section, simultaneously pressurize schrader valve3 and schrader valve4 to 40 bar.
4. At the mentioned pressure, if there is no leakage in the system, retain the pressure for 24 hours then the leak detection process is completed; otherwise, fixed the leak point and repeat the Step 2, Step3 and Step 4.
5. After the leak detection is completed, release the nitrogen gas and add refrigerant oil.
Note: Ensure the pressure of the leak detection in the low pressure section must not exceed the value higher than 32.8 bar, otherwise the compressor will be damaged.
After the leak detection is completed, the nitrogen pressure must be released slowly and the pressure must be released at the designated location to prevent the nitrogen from carrying out the lubricating oil in the system.

2.8.6. Charging Refrigerant Oil
The Liebert XD system must be recharged with refrigerant oil as per the requirement before commissioning the unit for the first time. The amount of refrigerant oil added must be according to the actual length of the connecting piping on site.
1. Select the correct type of refrigerant oil.
2. The addition of refrigerant oil must as per to the actual length of the liquid return piping, not the equivalent length.
3. When the actual length of the liquid return piping is less than or equal to 30 m, each system needs to be supplemented with 1.5 Liters of refrigerant oil.
4. When the actual length of the liquid return piping is more than 30 m then calculate the amount of refrigerant oil to be added according to the actual piping length and piping diameter, as provided in Table 2-12.
5. Recharge the refrigerant oil for each system through the schrader valve reserved on the branch manifold, as shown in Figure 2-19.
Table 2-12 Additional Amount of Refrigerant Oil

Liebert XDC130

Actual Pipe Length < 30 m

Actual Pipe Length > 30 m

Each system:

Each system must be supplemented

with refrigerant oil of 1.5 Liter

Charged amount of refrigerant oil = 1.5 Liter + (the actual length of the liquid

return pipe - 30 m) * the amount of refrigerant charged per unit length x 6%

VertivTM | Liebert® XDC | User Manual

26

ITEMS DESCRIPTION

1

Access valve

Figure 2-19 Oil Injection Schrader Valve

Charged amount of refrigerant oil = 1.5L + (the actual length of the liquid return pipe-30m) x the amount of refrigerant charged per unit length x 6%

Table 2-13 provides the amount of refrigerant charged per unit length as per the diameter and the length of return piping. Table 2-13 Amount of Refrigerant Charged per Unit Length

Outer Diameter of Liquid Return Pipe (mm) 16 19 22 25

Charged Amount of Refrigerant per Unit Length (kg/m) 0.169 0.238 0.315 0.415

Note: Before commissioning the Liebert XD system for the first time, it must be recharged with refrigerant oil as per the requirement. The lack of refrigerant oil will cause the damage to the compressor.
Note: Ensure to select the appropriate refrigerant oil recommended by manufacturer, otherwise the compressor will be damaged. Note: For refrigerant oil charging details of other VertivTM Liebert® XDC systems, contact Vertiv local representative.
For any consequences resulting from inferior quality refrigerant, Vertiv does not assume warranty responsibility. Select the type of lubricant oil in accordance with the compressor manufacturer's specification.

27

Mechanical Installation

2.9. Remove Transportation Fixing Plate of Compressor
Damping cushions are added to the base of the compressor to reduce vibration and noise during operation. However, such method cannot resist the vibration while transporting the unit and may result in loosening connections and wearing of certain parts. Hence to ensure the rigidity of the compressor during transportation, three U-shaped fixing plates are added to the compressor base.
Note1: Remove the three U-shaped fixing plates after installation, and then restore the bolts and washers in reverse sequence of the disassembly process.
Note2: The fastening torque of the bolts is (12±1) Nm.

ITEMS DESCRIPTION

1

U-Shape Plate

Figure 2-20 "U"-shaped Fixing Plate

VertivTM | Liebert® XDC | User Manual

28

2.10. Mechanical Installation Checklist
Initiate the inspection checks after the mechanical installation is completed. Pre-check and confirm that there are no discrepancies or faults. Ensure that all the points in the checklist (refer Table 2-14 for installation checklist) are complying accordingly..
Table 2-14 Mechanical Installation Checklist

Check Items
Leave enough space around the installed unit to facilitate unit maintenance.
The unit is placed vertically, and the installing fasteners are firmly fixed. The piping connecting the indoor and outdoor units have been installed properly, and the ball valves of the condenser, the Liebert XDC unit, and the terminal have been fully opened. The cold drain pipe at the cooling terminal is firmly connected.
All piping joints are tightened and leak proof.
All supporting fasteners used for transportation have been removed. After the unit is installed, the debris inside or around the unit has been removed (such as transportation materials, mechanical parts, materials, tools, etc.)

Results

Everything is checked and verified, follow the electrical installation.

29

Mechanical Installation

3 Electrical Installation
This chapter introduces the electrical installation of VertivTM Liebert® XDC unit, including brief introduction of key components, installation notes, cabling and electrical inspection for the unit.
Note: Liebert XDC unit is a professional equipment, used in industrial, commercial or other professional environment, and is not sold to the general public. Note: Its total rated power is greater than 1 kW and complies to the IEC61000-3-12 standard. It is necessary to provide an interface between the user's power supply and the grid with a short-circuit ratio greater than or equal to 350. Note: The user needs to obtain permission from the local power supply department to ensure that the air conditioner is connected to the power supply with short-circuit ratio greater than or equal to 350.
3.1. Installation Tasks and Cautions
3.1.1. Cabling Connection at the Site
1. Liebert XDC unit power cables and control cables. 2. Outdoor unit (air-cooled): control signal cable and power cable. 3. Unit input and output control cables.
3.1.2. Installation Notes
1. The connection of all power cables, control cables, and ground cables must comply with the national and local electrician regulations.
2. For full load current, refer to the unit's nameplate. The cable size should comply with local cabling/wiring regulations. 3. Main power supply requirement: 380 V to 415 V (-10% to +6%)V, 50 Hz, 3 N~. 4. The power supply cord adopts Y-type connection. If the power supply cord is damaged, it must be replaced by
professional maintenance personnel. 5. The electrical installation and maintenance must be performed by authorized and trained professionals. 6. Before connecting the circuit, use a voltmeter to measure the input power voltage, and ensure the power supply is off. 7. The unit needs to be fixed firmly with screws, guide rails or other methods during installation to avoid shaking during
startup or operation. 8. The emergency power supply off and emergency stop requirements of the air conditioner should be considered in the
power distribution system, and a suitable all-pole disconnection device for disconnection of the power supply should be provided. 9. Appropriate RCD should be installed according to the actual installation situation. 10. Without the confirmation of Vertiv technical personnel, the user cannot install electrical devices, such as electric meters, in the unit.

VertivTM | Liebert® XDC | User Manual

30

3.2. Cabling of the Unit
3.2.1. Electrical Interface Location of the Unit
The user's power supply inlet cables should be connected firmly according to the position and labels of the cable shown in Figure 3-1.

ITEMS 1

DESCRIPTION Input access cable should be fixed
Figure 3-1 Electrical Control Box and User Cabling

Open the front door of VertivTM Liebert® XDC unit and the user can see the specific distribution position of the low-voltage components. The detailed distribution information of low-voltage electrical components is provided according to the labels attached to the cabinet, as shown in Figure 3-2.

31

Electrical Installation

ITEMS 1 2 3

DESCRIPTION Terminal blocks Transformer breaker Compressor breaker 1

ITEMS DESCRIPTION

4

Compressor breaker 2

5

Main breaker

6

Condenser breaker

Figure 3-2 Unit Electric Control Box

3.2.2. Connection of Unit Power Supply Cables
The specific location of the power supply interface of the VertivTM Liebert® XDC unit is shown in Figure 3-2. L1~L3, N and PE are connected to the corresponding ends of the external power supply terminals respectively. A certain margin for the incoming cable should be provided to fix it on the cable fixing clamp, which is fixed on the inner panel of the unit.
Refer to the rated full load current value (FLA) of the unit for the selection of cabling model, Table 3-1 provides the FLA values of the unit.
Table 3-1 Full Load Current Value of the Unit (unit: A)

Model
XDC1309N1LAC XDC1309N1RAC

Current (Amp)
75

Note: The cable size should comply with local and national regulations. Note: The above full load current value does not include the outdoor unit and Liebert XD terminal.

VertivTM | Liebert® XDC | User Manual

32

3.3. Control Cables Connections
Figure 3-3 shows the location of the cabling terminals used for field cabling/wiring.
Before connecting the control cables, the person who carries out cabling work must take corresponding anti-static measures.

ITEMS 1 2 3

DESCRIPTION Customized Alarm Remote On/Off Common Alarm

ITEMS DESCRIPTION

4

RS-485 interface

5

RS-485 to condenser

6

CAN to cooling modules

Figure 3-3 Field Cabling Terminal

33

Electrical Installation

· Communication cables
CAN communication is used between the VertivTM Liebert® XDC unit and the cooling terminal, and the user needs to connect the cables on site. The communication cables are from the CANH/CANL terminal of the unit and further connected in series with the CANH/CANL on each terminal block of the terminal.
RS485 communication is used between the Liebert XDC unit and the condenser, and the user needs to connect the cables on site, lead the cables from the host RSA/RSB terminal, and then connect in series with the J11 terminal of the condenser.
The connection of the communication cable should a series connection, as shown in Figure 3-4.

Figure 3-4 Control Cable Connection Note: The communication cable must be a shielded twisted pair, away from strong interference sources, and ensure that both ends of the shielding layer are grounded. Note: The communication cables and power cables must be routed separately.
· Remote shutdown
Figure 3-3 shows the terminals 37# and 38# that can be connected to the remote shutdown switch. The terminals have been short-circuited in the factory. When a remote shutdown is required, remove the short-circuit cables.
Note: When the 37# and 38# terminals are disconnected, the unit will shut down.
· Self-defined alarm terminal
Terminals 50#, 51#, 55# can be connected to 3 kinds of sensor inputs, and terminal 24# is a common terminal. It can also be defined as a fire sensor, etc. After the external alarm signal is connected to the self-defined terminal, the corresponding selfdefined alarm content needs to be set in the Liebert PACC controller. Refer to the Liebert PACC self-defined alarm setting in Appendix II.
When the contact is disconnected and there is no external alarm, the self-defined terminal input state is On. When the contact is closed, after an external alarm occurs, the self-defined terminal input is in a short-circuit state, the air conditioning system will sound an alarm, and the Liebert PACC controller LCD display will display the corresponding alarm content.
A smoke alarm switch can be connected between the 50# and 24# terminals.
Remote alarm can be connected between 37# and 38# terminals.
· External general alarm terminals
The external general alarm can be connected to the 75# and 76# terminals, and its output is used to trigger the external alarm devices, such as alarm lights. When a major alarm occurs, the contact is closed. This can be used to send out remote alarms, signal to the building management system or automatically dial the paging system. The user needs to provide the power supply of the external public alarm system circuit.
For other terminal definitions, refer Appendix I Liebert XDC Circuit Diagram.

VertivTM | Liebert® XDC | User Manual

34

3.4. Electrical Inspection Checklist

After the electrical installation is completed, check and confirm according to Table 3-2.

Check Items

Table 3-2 Electrical Installation Checklist

The power supply voltage is the same as the rated voltage on the unit's nameplate

Results

There is no open or short circuit in the electrical circuit of the system

The power supply and ground cables are firmly connected to the disconnect switches

The rated value of the circuit breaker or fuse is correct

The control cable is connected

All cables and circuit connectors have been tightened, and the tightening screws are not loose

After confirming the above points, user can start the commissioning.
Users are prohibited from powering on the unit before the professional and technical personnel authorized from Vertiv have checked and confirmed the electrical connections.

35

Electrical Installation

4 System Startup and Commissioning
This chapter introduces the system startup and commissioning, including the position of the MCB and the specific operation steps for startup and commissioning the unit.
4.1. Startup and Commissioning
4.1.1. Preparation Before Commissioning
· Mechanical Part 1. According to the instruction label at the valve, ensure that all valves of the VertivTM Liebert® XDC unit and all cooling
terminals are open. 2. The refrigerant piping system has passed the air tightness test and confirmed that there is no leakage. 3. The drainage pipe system at the cooling terminal has been reliably connected and leak-checked in accordance with the
specified material requirements. 4. The compressor heating belt has been preheated for more than 12hours. 5. The temperature of the equipment room is above 20 °C and has a certain thermal load. If not available, other heating
devices should be used to preheat the environment of the equipment room to ensure the necessary thermal load for the commissioning.
· Electrical Parts 1. Confirm that the input voltage of the main power supply is within the nominal range of rated voltage
380 V t0 415 V (-10% to +6%) V; the power isolation switch of the outdoor unit air-cooled condenser is closed. 2. Confirm that all electrical or control connections are correct, and firmly fixed all electrical and control connections. 3. Confirm that the power supply cables and low-voltage control cables are arranged separately.
4.1.2. Vacuuming
As Liebert XDC unit and the cooling terminal are connected and used together to form a system, both should be powered on, started, and commissioned at the same time. 1. Release the pressure-holding nitrogen and open all the ball valves in the system 2. Ensure that the air switches of compressor 1 and compressor 2 of the unit are disconnected to prevent the starting of the
compressor by mistake 3. Power on the unit and all terminals at the same time, and keep them in ready state 4. Ensure that the unit enters the vacuuming mode and the electronic expansion valve at the terminal is open; 5. The positions of the schrader valve for vacuuming are schrader valve 3, schrader valve 4, as shown in Figure 2-6; 6. The #1 and #2 systems need to be vacuumed separately to ensure that the vacuum time of each system is more than
3hours and the vacuum degree reaches -1 bar. Note: During the vacuuming process, if the unit exits the vacuuming mode, ensure that the system enters the vacuuming mode again through the settings. Note: If the vacuum cannot reach -1 bar, it is necessary to stop vacuuming and check the system for any sign of leakages. Note: If it is not possible to ensure that the unit is powered on during vacuuming, ensure that the schrader valves 1, 2 and the two schrader valves of the inlet and outlet pipes at the terminal are simultaneously vacuumed at the four positions.

VertivTM | Liebert® XDC | User Manual

36

4.2. MCB Position
The positions of the main isolation switch and MCB of the dual system unit are shown in Figure 3-2, distinguish them according to the label instructions on the actual cabinet.
4.3. Static Refrigerant Charge
After the vacuuming is completed, the refrigerant can be charged statically: 1. Ensure that the air switches of compressor 1 and compressor 2 of the unit are disconnected to prevent the starting of the
compressor by mistake. 2. Power on the unit and all terminals at the same time, and keep them in ready state. 3. Ensure that the unit enters the vacuum mode. 4. Ensure that the position of the schrader valve for static refrigerant charging is at schrader valve 3, as shown in Figure 2-6. 5. Carry out static refrigerant charge for #1 and #2 systems respectively. 6. Until the refrigerant cannot be charged into the system, the static charging ends. Note: The hose connected to the composite pressure gauge must be vented. Note: Ensure to charge the refrigerant statically at the required position, and avoid static charge of the refrigerant at the compressor suction port. Note: In the process of static refrigerant charging, if the unit exceeds the vacuum mode, user must ensure that the system enters the vacuum mode again through the settings. Note: The longer on-site connecting pipe, the greater the requirement for static charging. Note: After the static charging is finished, ensure that the compressor crankcase heating belt is preheated for more than 12 hours before starting up, or use a dryer to heat the lower part of the compressor shell for about 30minutes.
4.4. Dynamic Refrigerant Charging
After completing the static charging of refrigerant, and after preheating the compressor as required, dynamic refrigerant charging can be performed: 1. Close the compressor MCB to make the unit enter the running state. 2. The position of the schrader valve for dynamic refrigerant charging is at schrader valve 4, as shown in Figure 2-6. 3. Perform dynamic refrigerant charging for #1 and #2 systems respectively 4. After the unit is stably operating, ensure that the sight glasses of the #1 and #2 systems are free of bubbles, and the
subcooling in front of the valve reaches above 6 °C. 5. After the operation is stable, ensure that the exhaust superheat of the unit is within the range of 25 °C to 40 °C . 6. If there is no problem with the above commissioning, the whole unit debugging is completed. Note: The hose connected to the composite pressure gauge must be vented. Note: After the dynamic refrigerant charging is completed, the subcooling in front of the valve must be ensured, otherwise the system may run abnormally.

37

System Startup and Commissioning

4.5. Commissioning Inspection Checklist
After debugging, check and confirm according to Table 4-1. Table 4-1 Commissioning Inspection Checklist
Inspection Items All output functions are automatic The temperature and humidity settings and control accuracy are correct Whether there is any abnormal alarm Other settings are correct

Results

VertivTM | Liebert® XDC | User Manual

38

5 Color Display Screen Operating Instructions
This chapter introduces the characteristics, appearance, main interface, alarm menu, and system settings of the display color screen of VertivTM Liebert® XDC unit.
5.1. Features
The 7-inch color screen display has the following characteristics: 1. The LED screen uses menu-style operation to monitor and display the operating status of precision cooling and air
conditioner unit, so that the control environment is maintained within the set range. 2. Provide power-down self-recovery function, as well as high and low voltage protection, phase failure protection, reverse
phase protection and other functions. 3. Through the menu operation, user can accurately understand the main parameters and operating status of the system. 4. Expert level troubleshooting system, that can automatically display the current fault content, which is convenient for
maintenance personnel to maintain the unit. 5. It can store up to 1000 PCS historical alarms. 6. The unit has a CAN interface and adopt CAN communication protocol. Note: The color display screen used by Liebert XDC unit is a resistive screen. When the user touches the screen to perform related operations, if the screen does not respond in time, thus user needs to use fingertips to try again.
5.2. Appearance
Figure 5-1 shows the appearance of the 7-inch display color screen.

Figure 5-1 Color Screen Appearance

39

Color Display Screen Operating Instructions

5.3. Color Screen Interface
5.3.1. Startup Interface
After the unit is powered on, the color screen displays the startup interface, as shown in Figure 5-2.
Figure 5-2 Startup Interface
5.3.2. Main Interface of the Color Screen
· The display color screen defaults setting is in Chinese. Click the unlock button and enter the user password to unlock, then the setting button and power on/off button will appear for parameter setting and power on/off setting.
· The top half of the color screen displays the home button, alarm status, setting button, time & date, and the power on/off keys, and unlock keys.
· The middle part displays the main operating status of the unit; the rightmost part displays the output status of the main adjustment components of the unit (such as compressor, outdoor unit), as shown in Figure 5-3 and Figure 5-4.

Figure 5-3 Color Screen Interface-locked

VertivTM | Liebert® XDC | User Manual

40

Figure 5-4 Color Screen Interface-unlocked
· When browsing the menu, tap the corresponding menu key to view related parameters. The function description of each touch key on the interface is provided in Table 5-1. Table 5-1 Touch Key Function Description

Touch Key Main interface button Set button
On/Off button
Lock button

Function Description
Click this button to enter the main interface and learn about the main data readings of the system.
This button will be displayed after unlocking, click this button to enter the temperature and humidity setting page, user can set the temperature and humidity of the system, and the control mode.
This button will be displayed after unlocking, the unit is in shutdown state, click this button for at least 2sec, the unit will turn on; the unit is running, click this button for at least 2sec, the unit will shut down.
Click this button and enter the user password to unlock. After unlocking, the setting button and power on/off button will appear, and then parameter settings, and power on/off settings can be performed.

Connection status Display the connection status between the unit and the terminals.

Alarm status

Display the alarm status of the unit.

Status bar

Display the output status of the compressor and outdoor unit.

Outdoor unit status Display the relevant status of the outdoor unit.

Main unit status

Display the relevant status of the main unit.

Terminal status

Display the relevant status of the terminal.

41

Color Display Screen Operating Instructions

5.3.3. Operation Example
Example 1: Enter the password to enter the main menu. After powering on, user can enter the main menu through the following operations in the normal interface. 1. Click the unlock button to enter the password interface. 2. Enter the user login password in the password interface. 3. After entering correct password, access the main interface to modify the corresponding parameters of the unit. Example 2: Modify parameters Take the setting of the Supply Air High Temperature alarm value menu item in the Alarm Value setting menu as an example. 1. Click the Setting button on the main unit interface. 2. Enter the alarm menu interface, turn the page to the Alarm Setting interface. 3. In the alarm setting interface, set according to the corresponding alarm value. 4. After the parameters are selected, press ENTER to confirm, then the parameter takes effect. 5. Press the exit key to return to the previous menu interface. Note: After changing the parameters, if user does not press ENTER to confirm, the supply air high temperature alarm value will keep the original parameters. Password Interface Click the unlock icon in the upper right corner to display the password interface, as shown in Figure 5-5.

Figure 5-5 Password Interface

The password to enter the menu has only one level, and the specific description is shown in Table 5-2. Table 5-2 Password Level

Password Level User

Level 1

Ordinary operator

Initial Password 1490

Remark
Can browse all menu information. Can only set the temperature and humidity, and cannot change other values and settings.

For the specific operation of password input, refer to Section 5.3.3 Operation Example. If the wrong password is entered, the operator can press the CLR (clear) key to change.

Note: In the password interface, directly press the enter key without typing any password, user can view the set value of each menu, but user cannot change any parameters.

VertivTM | Liebert® XDC | User Manual

42

5.4. Other Interfaces
5.4.1. Alarm Status
Click the Alarm Status icon to enter the interface shown in Figure 5-6, including current alarms and historical alarms.
· Active alarm The Active Alarm page is used to monitor the current alarm status record of the air-conditioner unit, prompting no alarm or specific alarm status information. The specific alarm status information includes serial number, alarm content, and alarm occurrence time.
· Historical alarm The Historical Alarm page is used to query the historical alarm information of the air conditioner unit, including the serial number, alarm occurrence time, alarm elimination time, and alarm content.

Figure 5-6 Alarm Status & History Interface

43

Color Display Screen Operating Instructions

5.4.2. Main Unit Menu
Click the Main Unit icon to enter the interface shown in Figure 5-7 and Figure 5-8, the unit icon on the left is lit, user can view the main unit operating status and set related parameters.
Figure 5-7 Menu Setting Interface

Figure 5-8 Run Information Interface

VertivTM | Liebert® XDC | User Manual

44

5.4.3. Terminal Menu
Click the Terminal icon to enter the interface shown in Figure 5-9, Figure 5-10, and Figure 5-11. The left terminal icon is lit, user can view the running status of the terminal and set related parameters.
Figure 5-9 Basic Terminal Status Interface

Figure 5-10 Terminal Run Status Interface

45

Color Display Screen Operating Instructions

Figure 5-11 Terminal Alarm Setting Interface
5.4.4. Run Time
Figure 5-13 shows the RUN Time interface of the unit.

Figure 5-12 Run Time Interface

VertivTM | Liebert® XDC | User Manual

46

5.4.5. About
Figure 5-14 shows the About interface of the unit.
Figure 5-13 About Interface

47

Color Display Screen Operating Instructions

6 System Operation and Maintenance
Regular system maintenance is essential to ensure product reliability and effectiveness. This chapter introduces the operation and maintenance of VertivTM Liebert® XDC unit, including routine maintenance inspections, system troubleshooting tests, and maintenance of filter net, fan components, cooling systems, and drainage systems.
· It is recommended that the load of Liebert XDC system should not be less than 30%. If the load is lower than the requirement, consult Vertiv local representaive.

· During the operation of Liebert XDC precision air conditioner, lethal voltage may exist in the unit. Prior to operating, ensure to read all notes and warning information on the parts and also those which are mentioned in the manual, otherwise it may cause casualties.

· Only qualified and authorized repair and maintenance personnel can perform system maintenance.

6.1. Routine Maintenance Inspection (Monthly)
Check the system components monthly, focusing on checking whether the system functions normally and whether the components have any sign of wear. Refer to Table 6-1 for the monthly routine maintenance inspection items.
Table 6-1 Monthly Routine Inspection Items List

Parts

Compressor part

Liebert XDC unit

Cooling cyclic system

Cooling terminal

Electronic expansion valve
Fan
Water pump filter net

Filter net

Outdoor unit

Air-cooled condenser (air-cooled unit)

Inspection Items Check for any sign of leakages Listen to the running sound and observe the running vibration Check the suction pressure Check exhaust pressure Check the refrigerant line Check the moisture contents of the system (observe through sight glass) Whether the refrigerant pressure and temperature detection are accurate Check if it is blocked or stuck Whether the fan is running with abnormal noise Check if there is any foreign matter in the drip tray Check the water pump filter Check whether the filter net is damaged or blocked Clean the filter net Cleanliness of condenser fins Whether the fan installation base is firm Whether the fan cushion is aged or damaged The refrigerant pipeline is properly supported

Remark

VertivTM | Liebert® XDC | User Manual

48

6.2. Routine Maintenance Inspection (Semi-annual)
Table 6-2 provides the details of semi-annual routine maintenance and inspection items of VertivTM Liebert® XDC unit. Table 6-2 Semi-annual Routine Inspection Items List

Parts

Inspection Items Check for any sign of leakages

Remark

Compressor part

Check and tighten circuit connectors

Liebert XDC unit

Listen to the running sound and observe the running vibration
Check the suction pressure
Check exhaust pressure Cooling cyclic system
Check the refrigerant line

Check the moisture content of the system (observe through sight glass)

Check fuse and MCB

Electrical control

Electrical control part

Check and tighten circuit connectors Check control program

Electronic expansion valve

Check the closing condition of the contactor
Whether the refrigerant pressure and temperature detection are accurate
Check if it is blocked or stuck

Cooling terminal

Fan Water pump filter

Whether the fan impeller is deformed Check and tighten circuit connectors Check if there is any foreign matter in the water pan Check the water pump filter

Filter

Check whether the filter is damaged or blocked Clean the filter

Cleanliness of condenser fins

Whether the fan installation base is firm

Outdoor unit

Air-cooled condenser (air-cooled unit)

Whether the fan cushion is aged or damaged Speed controller adjustment function Whether temperature and pressure detection are accurate

The refrigerant pipeline is properly supported

Check and tighten circuit connectors

49

System Operation and Maintenance

6.3. System Troubleshooting Test
The microprocessor controller has a manual mode, which provides on-site troubleshooting functions for manually opening and closing various components to detect the status of system functional components,
6.4. Electrical Connection Inspection
6.4.1. Electrical Maintenance
1. Perform visual inspection and treatment to electrical connections according to the following items: 2. Electrical insulation test of the whole system: Find defective contacts and correct the defects. During the test, disconnect
the fuse or MCB of the control section to avoid damage to the control panel due to high voltage. 3. Statically check whether each contactor is flexible and jammed. 4. Use a brush or dry compressed air to remove dust from electrical and control components. 5. Check whether the contacts of the contactor are drawn for arcing and have burn marks. If it is serious, replace the
corresponding contactor. 6. Fasten the electrical connection terminals. 7. Check whether the fan's quick-to-plug terminals are in good contact. If any looseness is found, replace the terminals. 8. If the power cord is damaged, in order to avoid danger, it must be replaced by a professional from the manufacturer's
maintenance department.
6.4.2. Control Maintenance
Perform visual inspection, simple function inspection and processing of the control part according to the following items: 1. Check the appearance of the transformer and check the output voltage. 2. Check the appearance of the terminal transformer and power supply module, and check the output voltage. 3. Check the control interface board, control board, temperature and humidity sensor board, fuse board and other surfaces
for obvious sign of aging. 4. Clean the dust and dirt on the electrical control components and control panel, and clean it up with a brush and
electronic dust remover. 5. Check and tighten the output and input plugs of the control interface board, including the connection between the
control board and the control interface board and the connection between the control interface board and each sensor. 6. Check the connection between the user cabling terminals (such as A/B, H/L, etc.) and the control terminal block. 7. Check the output connection of the control interface board to each contactor, and the input connection of the high
voltage switch, exhaust temperature sensor, high pressure sensor, etc. Pay special attentions to the high-voltage switches and other plug-in terminals. If there is looseness, poor contact, failure, etc., they should be replaced immediately. 8. Replace the control fuse (or MCB), control board and other electrical components that have detected problems. 9. Check the specifications and aging conditions of the control cable or power cable of the main unit, and replace the cable if necessary. 10. Adjust the setpoints, and detect the action of each functional component according to the control logic. 11. Simulate and detect the running status of the protection units such as the VertivTM Liebert® XDC unit. 12. Check whether the cabling and numerical display of each sensor are normal.

VertivTM | Liebert® XDC | User Manual

50

6.5. Cooling System
1. Check the refrigerant pipes and fixing brackets every six months; the refrigerant pipes must have proper brackets, and it is not allowed to lean against the wall, the floor or the fixed frame where it vibrates; at the same time, it is necessary to check whether the pipe insulation cotton is damaged. If any, cotton needs to be refilled in time.
2. The components of the cooling system must be inspected monthly to see if the system is functioning properly and for signs of wear. Since the device failure or damage is often accompanied by corresponding failures, regular inspections are the main means to prevent most system failures.
3. The refrigerant pipeline must have proper support, and it is not allowed to lean against the wall, floor or fixed frame vibration. Check the refrigerant pipeline and fixing brackets every six months.
4. Each system is equipped with a sight glass, which is convenient to observe the flow of liquid refrigerant and the moisture content of the system. When the moisture content in the system exceeds the standard, the background color of the sight glass changes from green to yellow. When there are too many bubbles in the sight glass, the refrigerant charge may be insufficient.
5. When the refrigeration system fails, the fault can be judged according to some parameters of the system operation.

6.5.1. Suction Pressure

When the suction pressure drops below the protection value set by the low pressure sensor, it may cause the compressor to stop. On the other hand, too high suction pressure will also reduce the cooling of the compressor motor by the refrigerant, which may cause damage to the compressor. The minimum (low pressure alarm setting) and the maximum (design operation) suction pressure settings are shown in Table 6-3.

System

Table 6-3 Suction Pressure
Minimum pressure kPa (PSIG), R410A

Maximum pressure kPa (PSIG), R410A

Air cooling (speed controller stepless speed regulation)

370 (53.7)

1580 (229)

6.5.2. Exhaust Pressure

The exhaust pressure may increase or decrease due to load conditions or condenser efficiency. When the exhaust pressure reaches the set value of the pressure switch, the action of the high pressure switch will stop the compressor. Refer Table 6-4 for more details.

Table 6-4 Exhaust Pressure

System Design High pressure switch action value

kPa (PSIG) 4100 (595)

6.6. Terminal Electronic Expansion Valve
The automatic adjustment of the electronic expansion valve ensures that enough refrigerant is supplied to the evaporator to meet the requirements of loading conditions. By observing and measuring the temperature of superheat and the opening of the electronic expansion valve , user can determine whether the electronic expansion valve is operating normally.
Note: The temperature of suction superheat has a greater impact on the compressor life. If the compressor has run for a long time under the condition of low or no suction superheat, it may cause the compressor to produce "liquid impact" and break the scroll of the scroll compressor.
Note: If abnormal opening or adjustment of the electronic expansion valve is found at the application site, contact Vertiv local representative and Vertiv technical support.

51

System Operation and Maintenance

6.7. Terminal Fan
Regular inspections include the running status of the motor, the status of the fan impeller, the fixing of fan components, and the clearance between the fan and the air guide ring, etc.
Pay special attention to whether the fan assembly and the air guide ring are firmly installed, and whether there is the possibility of touching the nearby sheet metal parts when the blades rotate. At the same time, any abnormal airflow channel blocking factors should be eliminated in time to avoid the any damage to the cooling system and other system components from the reduction of airflow volume.
The terminal fan needs to input the main power of 48 Vac, and at the same time rely on the 0 V to 10 V DC analog signal output by the control board to adjust the speed. When the fan is abnormal or does not rotate, check the analog signal, main power supply, and filter net blockage.
The steps to replace the fan are as follows:
1. Cut off the power supply of the whole unit.
2. Remove the screws fixing the fan mounting plate, and remove the fan.
3. Reinstall the replaced fan. During the installation process, pay attention to the terminal corresponding relationship and check if the contacts are firmly connected.
Note: Do not maintain the fan during the operation of the fan to avoid injury.
Note: During the operation of the unit, it is forbidden to touch the fan net cover to prevent mechanical damage caused by the operation of the fan.
6.8. Air-cooled Condenser
Refer to the related information in Maintenance in "VertivTM Liebert® LVC Condenser User Manual".
6.9. Compressor
The VertivTM Liebert® XDC units use variable capacity compressors, which are highly reliable and require engineering construction to strictly follow correct procedures.
· The compressor motor is rarely burned out due to insulation failure. In the event that the motor is indeed burned out, most are caused by poor mechanical or lubrication, that is, high temperature and overheating.
· If the problems that may cause compressor failure can be detected and corrected early, most compressor failures can be avoided. The maintenance personnel should regularly conduct maintenance and inspection of abnormal operation conditions that may occur. Instead of replacing the compressor after a failure, it is better to take the necessary steps to ensure the normal operation of the system. This is not only easier but also much cheaper.
When troubleshooting the compressor, check whether all electrical components of the compressor are operating normally:
1. Check all fuses and circuit breakers.
2. Check the operation of the high voltage switch and low pressure sensor.
3. If the compressor malfunctions, find out whether the compressor malfunction is caused by an electrical failure or a mechanical failure.
When replacing the compressor, avoid skin contact or contact with refrigerant and lubricating oil. If contact with refrigerant or lubricating oil, it can cause severe burns or frostbite to the skin. Wear long-sleeved gloves when handling contaminated parts.

VertivTM | Liebert® XDC | User Manual

52

6.10. Mechanical Failure
The mechanical failure of the compressor cannot be determined by burning smell. User should try to rotate the motor. If a mechanical failure is confirmed, the compressor must be replaced. If the motor is burned out, eliminate the factors that caused the motor to burn out and clean the system.
Pay high attention to the compressor motor burnout, that is usually caused by improper system cleaning.
6.11. Electrical Failure
Electrical failure can be determined by the obvious pungent smell. If severe burns occur, the lubricant will turn black and become acidic. In the event of electrical failure and the complete burnout of the compressor motor, measures must be taken to clean the system to eliminate acidic substances in the system and avoid such failures in the system in the future.
Note: The replacement of the compressor needs to be carried out under the guidance of professionals. For replacement, contact Vertiv technical support engineer.
Note: The damage caused to the compressor due to improper cleaning will not be covered in the warranty and related details are mentioned in the warranty clause.
When the compressor is completely burned out, the compressor should be replaced along with the filter, and followed by checking of the electronic expansion valve at the terminal. If the electronic expansion valve fails, it should be replaced. Prior to the replacement, it is necessary to clean the system. If user are not sure about the cleaning method, consult the Vertiv local representative.

53

System Operation and Maintenance

7 Troubleshooting
This chapter introduces troubleshooting and fault handling of VertivTM Liebert® XDC unit.
Certain circuits have lethal high voltages, and only professional technicians are allowed to operate the unit. You must be especially careful when troubleshooting with power on.

Note: When using jumpers for troubleshooting, always remember to remove the jumpers after the repair work is completed. The remaining connected jumpers may overrun the control function and cause equipment damage.

Table 7-1 provides the troubleshooting and treatment of each component of Liebert XDC unit. Table 7-1 Troubleshooting Compressor and Cooling System

Symptom
Compressor cannot start

Possible Cause
No power (shutdown)
MCB tripped due to overload Loose circuit connection Compressor coil is short-circuited and burned out

Items to be Checked or Handling Method Check the main power switch, fuse or circuit breaker and connecting wires
Manual reset, check the average current
Fasten the circuit connector Check the motor windings, if any defect is found, replace them immediately

No cooling demand output

Check the PACC controller status

High voltage switch action

The contactor is not closed and the compressor is not running

Contactor failure
Low pressure sensor failure (11 minutes after shutdown)

Motor drive failure (11 minutes after shutdown)

Motor drive communication failure (11 minutes after shutdown)

Check the high voltage switch, whether there is a high voltage alarm
Check the contactor, check whether there is 24Vac between the terminals of J18-3 (compressor 1) and J20-1 (compressor 2) and G
Check whether the low-pressure sensor wiring of the system is intact and the reading is normal
Check whether the wiring is normal, whether the current is too large, check whether the ventilation of the motor drive is normal Check whether the wiring of the RS458 communication line of the motor drive is intact, then re-power on and reset or the panel will eliminate this fault alarm

VertivTM | Liebert® XDC | User Manual

54

Symptom

Possible Cause MCB tripped

Items to be Checked or Handling Method
Check the line voltage after checking the circuit breaker and contactor

Compressor built-in protector disconnected

Check whether the compressor coil is open. If open, wait for the coil to cool down and reset automatically

The contactor is closed, the compressor is not running

Detect exhaust air temperature sensor
Detect low pressure sensor Low pressure sensor failure (11 minutes after shutdown)

Is there an alarm for low exhaust air superheat/high temperature
Check whether there is a low voltage alarm in the history alarm
Check whether the low-pressure sensor wiring of the system is intact and the reading is normal

Motor drive failure (11 minutes after shutdown)
Motor drive communication failure (11 minutes after shutdown)

The compressor stops after running for 5 minutes

Refrigerant leak, low pressure detection is too low/abnormal

Dirty condenser Inlet water temperature is too high or water flow is too small (water cooling)
Condenser equipment does not operate

Check whether the wiring is normal, whether the current is too large, check whether the ventilation of the motor drive is normal Check whether the wiring of the RS458 communication line of the motor drive is intact, then re-power on and reset or the panel will eliminate this fault alarm
· Check the suction pressure;
· Check the circuit where the low-pressure sensor is located;
· Check whether the reading of the low pressure sensor and the actual pressure are within ±0.3bar (the value of the high and low pressure sensor can be read in the maintenance menu/troubleshoot setting and displayed as absolute pressure)
Clean the condenser or change the plate type exchanger; Check the water system (water cooling)
Air cooling system, check the condenser fan; Water cooling system, check the water system

High pressure protection

Excessive refrigerant charge

Improper adjustment of electric ball valve (water cooling)

Low exhaust pressure

The water flow is too large or the inlet water temperature is too low (water cooling)
Refrigerant leak

Check whether the subcooling is too high
· It is necessary to check whether the reading of the high pressure sensor and the actual value are within the range of ±0.6bar (the value of the high and low pressure sensor can be read in the maintenance menu/troubleshoot setting and displayed as absolute pressure);
· It is necessary to check whether the electric ball valve of the plate type heat exchanger is operating normally
Check the water system
Check for leaks and repair and add refrigerant

55

Troubleshooting

Symptom
Low exhaust pressure
After starting, there is no change in suction and exhaust pressure

Possible Cause
The outdoor fan speed controller is faulty, and the output voltage is always full load voltage, and does not change with the change of condensing pressure (air cooling)

Items to be Checked or Handling Method
If defects are found, replace the speed controller immediately

Compressor runs reversely or internal air blistering

If the compressor runs reversely, replace any two L wires of the compressor (inverter output terminal); if internal air leakage occurs and cannot be recovered, the compressor needs to be replaced

Insufficient refrigerant in the system

Check for leaks. If yes, repair and add refrigerant

Filter net of the terminal is too dirty

Replace the filter net

Clogged dry filter

Replace the dry filter

Low suction pressure or liquid backflow

Improper setting of the superheat of the electronic expansion valve of the terminal
Electronic expansion valve device of the terminal failure

Operate strictly in accordance with the design superheat of the unit
Replace electronic expansion valve

Poor air distribution

Check the air supply and air return system

Condensing pressure is too low

Check the condenser

Liquid backflow

See "Low suction pressure or liquid backflow" handling method

Compressor noise is too loud

Poor lubrication

Add lubricant

Compressor overheated

The compressor transportation fixture is not removed
Compression ratio is too high

Remove the transportation fixture
· Check the settings of the high pressure and low pressure switches, check whether the condenser is dirty or blocked;
· Check whether the evaporator and condenser fan of the terminal are operating normally

Suction superheat is too high

Adjust the setting of the electronic expansion valve of the terminal or add a proper amount of refrigerant

VertivTM | Liebert® XDC | User Manual

56

Appendix I: Circuit Diagram of VertivTM Liebert® XDC

8

7

6

5

4

3

FACTORY MOUNTED MAIN UNIT SWITCH

SEE UNIT NAMEPLATE FOR MAIN SUPPLY WIRE SIZING

LINE VOLTAGE 3 PHASE SUPPLY

L1 L2

5

L3

NEUTRAL

D
10

BK

BK

BK

POWER DETECT

BL

BK

4-1

BK

4-3

BK

4-5

BK

4-7

L3 L2 L1

T1

24V

T2 24V
24V

CMN

3-2

TS1 3-1

COM

TS2

1-7 1-8
TS1 CMN

CAN 7" UNIT DISPLAY
24V
PE

2-1

TH/HU

TEMP/HUMID

2-6

SENSORS

77 78 12V GND

SEE NOTE 6 SIC CARD
(OPTIONAL )

FCCF RTHS

485

485

12V GND

53

GN/Y

54

55

58

59

GN/Y

EIM1,2 VFD1,2 (B) 8-1

J33

485 (A) 8-2

15

DB9

CONNECT

SERVICE

82-1

DEVICE

82-3

77

(B) 7-1

SEE NOTE 5

78

(A) 7-2

20

COMMON

76

ALARM

75

CONNECTION 12V

9-2

9-1

9-3

69-1

GND

69-2

RSB RSA

(B) 89-1
(A) 89-2
CANH CANL

68-1 68-2

80

SEE NOTE 6

81

SDT

C

25

CUSTOMER CONNECTIONS ALSO SEE LINES34,37,40,41,44,45,46

30

35

EARTH GROUND CONNECTION

N

40
B
45
50
55

3P RC1,2

CCH1
COMPRESSOR NO.1 BK

5C1 4C1
VFD1 UR

BR

VS

GY

WT

CCH2 COMPRESSOR NO.2
BK

5C2 4C2
VFD2 UR

BR

VS

GY

WT

BK
BK FLT1 LOAD LINE 1C1 BK L1' L1
2C1 BK L2' L2
3C1 BK L3' L3
BK
BK FLT2 LOAD LINE 1C2 BK L1' L1
2C2 BK L2' L2
3C2 BK L3' L3

A

60

L1 L2 L3

L1 L2 L3

SHADED AREAS MAY BE FUSES(

)

OR CIRCUIT BREAKERS (

)

65

5-3 11-1 11-3 12-1 12-3 12-5 12-7

U7-1 U7-2 U7-3 U7-4 U7-5 U7-6

27-1 BK 27-3 BK

28-1 BK 28-3 BK

5-1
7C1 BK BK

HPT1

29-1 BK 29-3 BK

HPT2

30-1 BK 30-3 BK (OPTIONAL )

7C2
LPT1 LPT2

24V

5-2

5-4

BK

11-2

BK

11-4

12-2

12-4

12-6

12-8

24-1 BK 24-2 BK 24-3 BK 24-4 BK

DLTS1 DLTS2

13-1 13-3 13-5 13-7 14-1 14-3

U6-1 U6-2 U6-3 U6-4 U7-7 U7-8

17-1 17-3

U6-5 U6-6

17-5 17-7
12-1

U6-7 U6-8

12-3

16-1 16-3

U4-3 U4-2

HWA

BK

BK

51 BK
50 BK

WUF

24 BK

55 BK BK 56

HTS BK
BK

BK SPD
BK

LP1

BK

BK

LP2

BK

BK

4H

BK

BK

37

RSD

38

BK

BK

BK SEE NOTE 3

13-2 13-4 13-6 13-8 14-2 14-4
17-2 17-4
17-6 17-8
12-2
12-4 16-2 16-4

29-1 BK 29-3 BK
30-1 BK 30-3 BK

HPT3 HPT4

85-1 BK 85-2 BK 85-3 BK 85-4 BK

DLTS3 DLTS4

44-1 BK

BK
1CR1 BK
1CR2 BK

21-4

21-5

K1 18-1

K2

18-2 BK

H

BK

K3

HP1

18-3 BK

BK

G

EIM1,2

1 J32 4

BK

C1

BK

C2

BK

HS3 BK

SEE NOTE 3

CR1

BK

2EM1

K4

HP2

20-1 BK

BK

CR2

BK

K5

LLSV1/LTSV1

SEE NOTE 4

20-2 BK

BK

K6

20-3 BK

LLSV2/LTSV2 BK

SD BK 1

3

5

2

6

BK BK BK
SDT BK
R BK BK BK BK

BK

5 50 24 90

G5

1

93 BK

2

3

RESET

4

SDC

92 BK
91 BK

(OPTIONAL )

93

92

SEE NOTES 1&7

91

85-1 BK

85-2 BK

85-3 BK

85-4 BK

GND

BK

12V

BK

SAS1

SAS2

81-3

SP

BK 81-2

EEV11 EEV12

EEV21 EEV22

1 2 345 J34
EIM1

1 2345 J35 1 J38 2
1 Po 2
3

TS1
P1 1
3 2

1 2345 J34
EIM2

1 2345 J35
1 J38 2
1 Po 2
3

TS2
P2 1
3 2

8

7

6

5

4

3

2

1

NOTES :

1. ALL FIELD WIRING TO BE PER LOCAL CODES. USE COPPER CONDUCTORS ONLY.

2. SEE INSTALLATION AND USER MANUAL(S). 3. JUMPER TO BE REMOVED WHEN OPTIONAL COMPONENT IS USED.

5

4. LLSV IS ONLY OPTIONAL FOR LONG PIPE APPLICATION AS ONE OF THE COMPONENTS OF EXTENSION KITS.

5. ON UNITS WITH NO SIC CARD,C ONNECTION 485 OF PLUGS 7-1 AND 7-2 TO ALTERNATE CONNECTIONS AT SCREW TERMINALS 77 AND 78.

6. OPTIONAL SMOKE DETECTOR: FLA WILL SUPPLIED TERMINALS, IN FIELD WIRING

COMPARTMENT FOR REMOTE INDICATION. FIELD TO CONNECT 24V MAX.

D

7. TERMINALS ONLY FOR FACTORY SUPPLIED.
10

STANDARD DEVICES

NOMENCLATURE LINE OPTIONAL DEVICES

LINE

15

FCCF - FREQUENCY CONVERTER CONDENSOR FAN

9 HTS - HIGH TEMPERATURE STAT

40

HU - HUMIDITY SENSOR

3

RSD - REMOTE SHUTDOWN DEVICE 46

K3,4 - COMPRESSOR NO.1,2 RELAY 25,27

(75VA MIN. RATING)

K5 - LIQUID LINE SOLENOID 1 RELAY 29 SIC - SMART INTELLISLOT CARD

10

/ HOT GAS BYPASS 1 RELAY

SP - STATIC PRESSURE SENSOR

55

K6 - LIQUID LINE SOLENOID 2 RELAY 30

/ HOT GAS BYPASS 1 RELAY

20

WUF - WATER UNDER FLOOR

34

RC - REMOTE CONDENSOR

33 COMPRESSOR

RTHS - REMOTE TEMPERATURE & HUMIDITY SENSOR
T1 - UNIT CONTROL TRANSFORMER
T2 - ISOLATION TRANSFORMER

LPT1,2 - LOW PRESSURE

27

TRANSDUCER 1,2

23,25

LLSV1,2 - LIQUID LINE SOLENOID 1,2 29,30

3

LTSV1,2 - LOW TEMPERATURE

29,30

6

SOLENOID VALVE 1,2

TH - TEMPERATURE SENSOR

25

SAS1,2 - SUPPLY AIR SENSOR

COMPRESSOR

3

50,52 SMOKE DETECTOR SD - SMOKE DETECTOR

C 42

SDC - SMOKE DETECTOR CONTROL 45

C1,C2 - COMPRESSOR CONTACTOR 45,56 SDT - SMOKE DETECTOR TROUBLE 42

CCH1,2 - CRANKCASE HEATER NO.1,244,51

RELAY

CR1,CR2 - COMPRESSOR RELAY

25,27

VFD1,2 - COMPRESSOR FREQUENCY 9,46

30

CONVERTER

53

DLTS1,2 - DISCHARGE LINE

23,25

TEMPERATURE SENSOR 1,2

DLTS3,4 - PLATE LIQUID

50,55

TEMPERATURE SENSOR 1,2

FLT1,2 - FILTER1,2

46,53

HP1,2 - HIGH PRESSURE SWITCH NO.1,2

25,27

LP1,2 - LOW PRESSURE SWITCH

43,45

35

NO.1,2

HPT1,2 - HIGH PRESSURE

23,25

TRANSDUCER 1,2

HPT3,4 - PLATE LIQUID PRESSURE 50,55 TRANSDUCER 1,2

ELECTRONIC EXPANSION VALVE

EIM1,2-EEV CONTROLLER

15,9

61

40

EEV11,12,21,22- ELECTRONIC

59

EXPANSION VALVE 11,12,21,22

TS1,2 - SYSTEM1,2 TEMPERATURE 62

SENSOR

P1,2 - SYSTEM1,2 PRESSURE

64

SENSOR

B

WIRING LEGEND

FACTORY SUPPLIED LINE VOLTAGE WIRING

45

FIELD SUPPLIED LINE VOLTAGE WIRING

VOLTAGE WIRING IN OPTIONS

FACTORY SUPPLIED 24 VOLT WIRING

FIELD SUPPLIED 24 VOLT WIRING

CONTROL BOARD INTERNAL WIRING - 24 VOLT MAX

WIRING AND DEVICES INCLUDED IN OPTIONS

K

ELECTRONIC SWITCH (RELAY) K1-K12

50

INLINE QUICK DISCONNECT INLINE BLOCK DISCONNECT

OPEN CONTROL BOARD CONNECTION

PLUG CONNECTION ON CONTROL BOARD

TERMINAL STRIP CONNECTION FOR FIELD WIRING

TERMINAL BLOCK CONNECTION ON CONTROL BOARD

CIRCUIT CONNECTION TO ELECTRONICS

GROUND CURRENT DETECTOR CIRCUIT

PLUG CONNECTION ON VSC BOARD

55

WIRE COLOR CODE

OR - ORANGE R - RED BR - BROWN P - PURPLE GN - GREEN

Y - YELLOW BL - BLUE BK - BLACK W - WHITE GY - GREY

INSULATION COLOR

GN / Y

TITLE

60

TRACER COLOR ATTENTION

A

WIRING COLOUR CODES ARE FOR GUIDANCE

ONLY WIRE ID MARKINGS TAKE PRECEDENCE

WIRING DIAGRAM

XDC

THIS DOCUMENT CONTAINS CONFIDENTIAL AND

PROPRIETARY INFORMATION OF VERTIV AND

NEITHER IT NOR THE INFORMATION CONTAINED

65

THEREIN SHALL BE DISCLOSED TO OTHERS OR

DUPLICATED OR USED WITHOUT THE EXPRESS DRAWING NO WRITTEN CONSENT OF VERTIV

REV
A00

2

1

VertivTM | Liebert® XDC | User Manual

57

Appendix II: Alarm Output Menu

Parameter

Min

Default

Max

Hysteresis

Alarm attribute

0

-

2

-

High pressure alarm value (Bar)

-

42.0

-

9

Low pressure alarm value (Bar)

-

3.7

-

1.9

Exhaust high temperature alarm value 110.0

120.0

130.0

50.0

(°C)

Low exhaust superheat alarm value

5.0

(°C)

10.0

20.0

-

Power frequency deviation alarm value -

3.0

-

1.5

(Hz)

Power overvoltage alarm value (V)

-

415Vx(1+6%)

-

380Vx3%

Power supply undervoltage alarm value (V)

380Vx(1-10%)

-

380Vx3%

Low voltage alarm start delay (s)

30

180

600

-

Low exhaust superheat alarm

30

activation delay (s)

300

600

-

Self defined 1 type

0

0

2

-

Self defined 2 type

0

0

2

-

Self defined 3 type

0

0

2

-

Self defined 1 polarity

NC

NO

NO

-

Self defined 2 polarity

NC

NO

NO

-

Self defined 3 polarity

NC

NO

NO

-

Remote shutdown polarity

NC

NC

NO

-

Common alarm polarity

NC

NC

NO

-

Reset alarm lock

N

N

Y

-

Clear alarm history

N

N

Y

-

Remarks: Self defined type: 0: other; 1: smoke alarm; 2: fire alarm. Except for "Others", the self defined alarm input type cannot be repetitive.

VertivTM | Liebert® XDC | User Manual

58

Appendix III: Hazardous Substance Content

Date: _____________________________ Prepared by: ____________________________ Model: _____________________________ Serial No.: ______________________________

Filter net of terminal: ___ 1. Check if the filter net is damaged or blocked ___ 2. Check the filter net blockage switch ___ 3. Clean the filter net Terminal fan part ___ 1. Whether the fan impeller is deformed ___ 2. Whether the bearing is worn ___ 3. Is the fan running sound abnormal? Compressor part ___ 1. Check for leaks ___ 2. Listen to the running sound and observe the running vibration ___ 3. Compressor drive Air-cooled condenser ___ 1. Cleanliness of condenser fins ___ 2. Whether the fan mounting base is firm ___ 3. Whether the fan cushion is aged or damaged ___ 4. Whether the lightning protection board is still effective (if there is a lightning protection board. It is best to check once a week for the thunderstorm season) __ 5. The refrigerant pipeline is properly supported _

Cooling cyclic system ___ 1. Check the suction pressure
___ 2. Check the exhaust pressure
___ 3. Check the refrigerant pipeline
___ 4. Check the moisture content of the system (observe through sight glass)
___ 5. Check the terminal electronic expansion valve

Signature_________________________________________________________ Note: Please copy this form for record archive.

59



Appendix IV: List of Maintenance Inspection Items (Semi-annual)

Date: _____________________________

Prepared by: ____________________________

Model: _____________________________

Serial No.: ______________________________

Filter net of terminal: ___ 1. Check if the filter net is damaged or blocked ___ 2. Check the filter net blockage switch ___ 3. Clean the filter net

Water-cooled condenser (if used) ___ 1. Cleaning the water piping system ___ 2. Check the function of the electric ball valve ___ 3. Check the water system for leakage

Terminal fan part ___ 1. Whether the fan impeller is deformed ___ 2. Whether the bearing is worn ___ 3. Is the fan running sound abnormal? ___ 4. Check and fix the circuit connectors
Compressor part ___ 1. Check for leaks ___ 2. Listen to the running sound and observe the running vibration ___ 3. Check and fix the circuit connectors ___ 4. Compressor drive
Air-cooled condenser ___ 1. Cleanliness of condenser fins ___ 2. Whether the fan mounting base is firm ___ 3. Whether the fan cushion is aged or damaged ___ 4. Whether the lightning protection board is still effective (if there is a lightning protection board. It is best to check once a week for the thunderstorm season) ___ 5. Speed controller voltage regulation function ___ 6. The temperature switch is at the specified setting value ___ 7. The refrigerant pipeline is properly supported ___ 8. Check and fix the circuit connector

Cooling cyclic system ___ 1. Check the suction pressure and superheat ___ 2. Check the exhaust pressure and condensing supercooling ___ 3. Check the refrigerant pipeline ___ 4. Check the moisture content of the system (observe through sight glass) ___ 5. Check the terminal electronic expansion valve ___ 6. Check if you need to add refrigerant (observe through sight glass)
Electrical control part ___ 1. Check the fuse and MCB ___ 2. Check and tighten circuit connectors ___ 3. Check the control program ___ 4. Check the closing condition of the contactor

Signature_________________________________________________________ Note: Please copy this form for record archive.

VertivTM | Liebert® XDC | User Manual

60

Appendix V: Toxic and Hazardous Substances or Elements

Parts Name
Cabinet Cooling parts Electronic control unit Display screen Copper tube Cables

Lead
Pb   x x  

Toxic and Hazardous Substances or Elements

Mercury

Cadmium

Hexavalent Polybrominated

Chromium

Biphenyl

Hg

Cd

Cr6+

PBB

















































Polybrominated Diphenyl Ether
PBDE      

O: Indicates that the content of this toxic and hazardous substance in all homogeneous materials of this part is below the limit requirement specified in SJ/T-11363-2006;
X: Indicates that the content of the toxic or hazardous substance in at least one of the homogeneous materials of the part exceeds the limit requirement specified in SJ/T11363-2006.

Vertiv is committed to the design and manufacture of environmentally friendly products. We will continue to reduce and eliminate toxic and hazardous substances in our products through continuous research. The following components or applications contain toxic and hazardous substances that are limited to the current state of the art and cannot be reliably replaced or have no mature solutions:
Reasons for lead contained in the above components: lead in high temperature solder in diodes; lead in resistor glass uranium (exempt); lead in electronic ceramics (exempt)

Description of the environmental protection use period: The environmental protection use period of this product (identified on the product body) refers to a period from the date of production, in which the toxic and hazardous substances contained in this product does not seriously affect the environment, person and property under normal use conditions and compliance with the safety precautions of this product.

Scope of application: VertivTM Liebert® XDC Series Air Conditioner

61



Connect with Vertiv on Social Media
https://www.facebook.com/vertiv/ https://www.instagram.com/vertiv/ https://www.linkedin.com/company/vertiv/ https://www.twitter.com/vertiv/

Vertiv.com
© 2021 Vertiv Group Corp. All rights reserved. VertivTM and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional offers are subject to change at Vertiv's sole discretion upon notice.


Adobe PDF Library 15.0 Adobe InDesign 16.2 (Windows)