Hazardgard® Hazardous Location Room Air Conditioners

Engineered to perform in the harshest conditions.

UL LISTED for CLASS 1, DIV 2, GROUPS A, B, C and D.

CERTIFIED in accordance with ISA 12.12.01 and NFPA 70 (NATIONAL ELECTRIC CODE), ANSI/UL 484 Room Air Conditioners

KSA registered model tested in accordance with SASO 2681

50|60 HERTZ

FRIEDRICH 1883

HAZARDGARD MEETS T4 TEMPERATURE CLASSIFICATION

For more than 30 years, industrial professionals have trusted Hazardgard to deliver safe and reliable cooling in the most extreme conditions. Hazardgard is specifically designed to cool laboratories, control rooms, living quarters, storage areas and other enclosures situated in hazardous locations; where specific volatile flammable liquids or gases are handled or used within enclosed containers or systems.

Hazardgard® is rated for these conditions:

Model Hazardous Location Classification: Gases
SH15M30A National Electrical Code, NFPA 70 ARTICLE 501: Class 1, Division 2, Group A/B/C/D, Temperature Class T4 ARTICLE 505: Class 1, Zone 2, Group II C / IIB / IIA, Temperature Class T4 ?
SH20M30SA National Electrical Code, NFPA 70 ARTICLE 501: Class 1, Division 2, Group A/B/C/D, Temperature Class T4 ARTICLE 505: Class 1, Zone 2, Group II C / IIB / IIA, Temperature Class T4 ?
SH20M30B National Electrical Code, NFPA 70 ARTICLE 501: Class 1, Division 2, Group A/B/C/D, Temperature Class T4 ARTICLE 505: Class 1, Zone 2, Group II C / IIB / IIA, Temperature Class T4 ?
SH20M50B National Electrical Code, NFPA 70 ARTICLE 501: Class 1, Division 2, Group A/B/C/D, Temperature Class T4 ARTICLE 505: Class 1, Zone 2, Group II C / IIB / IIA, Temperature Class T4 ?
SH24N30A National Electrical Code, NFPA 70 ARTICLE 501: Class 1, Division 2, Group A/B/C/D, Temperature Class T4 ARTICLE 505: Class 1, Zone 2, Group II C / IIB / IIA, Temperature Class T4 ?

For global applications, Hazardgard cooling capacities are tested in a certified laboratory at moderate (T1*) and hot (T3*) climate conditions in accordance with SASO (Saudi Arabian Standards Organization) Standard 2681. SASO Standard 2681 is adopted from ISO Standard 5151 for testing and rating for performance of non-ducted air conditioners and heat pumps. Model SH20M30SA is KSA Registered in accordance with SAS02681 and meets SASO 2663 Energy Efficiency standard.

The Friedrich Advantage: Reliable Design Backed by Robust Engineering

Quality

Friedrich is an established player in the air conditioning industry and is known for manufacturing quality products.

Product Reliability

Used across the globe, Hazardgard is a tested and reliable product and not a quick-fix, job shop alteration.

Availability

Off the shelf models allow for efficient manufacturing, shorter lead times and standardized component parts.

Durability

Robust engineering, commercial grade components and extensive field testing provide the durability and safety required in hazardous locations.

DURABILITY & RELIABILITY

PERFORMANCE IN EXTREME CONDITIONS

COATED COILS FOR CORROSION RESISTANCE

ElectroFin® 5-stage, immersion ecoat process, or Diamonblue Advanced Corrosion Protection® on 100% of metallic surfaces on the outdoor coil provides outstanding corrosion resistance protection and extends the life of the unit, especially in coastal or corrosive environments.

Diamonblue Advanced Corrosion Protection®

ElectroFin® 5-stage, Immersion Ecoat Benefits:

MODEL SH24N30A ONLY

MEETS THE FOLLOWING:

Engineered to perform in the harshest environments

SPECIFICATIONS

Model Cooling Capacity Btu/Hr. Volts Rated Cooling Amps Cooling Capacity (KW) Circuit Rating Breaker or T - D Fuse Energy Efficiency Ratio EER Moisture Removal Pints/Hr Air Circulation CFM Refrigerant
60 HERTZ
SH15M30A 15700/15700 230/208 7.9/7.8 4.60/4.10 250V-15 9.7/9.7 4.0 375 R-410A
SH20M30B 21000/21000 230/208 10.5/9.4 6.15/6.15 250V-15 (230V) / 250V-20 (208V) 9.7/9.6 5.5 375 R-410A
SH20M30SA 19000/19000 220 8.5 5.57 250V-20 (230V) / 250V-20 (208V) 9.7/9.6 5.5 375 R-410A
SH24N30A 23500/23000 230 11.8 6.8 250V-20 9.7/8.5 8.0/7.5 385 R-410A
50 HERTZ
SH20M50B 21000/19100 240/220 11.6/10.3 6.15/6.15 250V-15 8.8/8.8 7.0/7.0 425 R-410A

INSTALLATION INFORMATION

Model Dimensions Inches Extension Inches Window Width Inches In-Wall Installation Finished Hole Inches Weight Lbs.
Height Width Depth J Box Minimum Front to Louvers Minimum Extension Outside Min. Max. Height Width Max. Depth Net Shipping
SH15M30A 15 15/16" 25 15/16" 27 3/8" 6" 3 1/16" 16 15/16" 27 7/8" 42" 16 3/16" 26 3/16" 6" 140 167
SH20M30B 17 15/16" 25 15/16" 27 3/8" 6" 3 1/16" 16 15/16" 27 7/8" 42" 18 3/16" 26 3/16" 6" 166 170
SH20M30SA 17 15/16" 25 15/16" 27 3/8" 6" 3 1/16" 16 15/16" 27 7/8" 42" 18 3/16" 26 3/16" 6" 166 170
SH20M50B 17 15/16" 25 15/16" 27 3/8" 6" 3 1/16" 16 15/16" 27 7/8" 42" 18 3/16" 26 3/16" 6" 171 175
SH24N30A 17 15/16" 25 15/16" 27 3/8" 6" 3 1/16" 16 15/16" 27 7/8" 42" 18 3/16" 26 3/16" 6" 180 185

Due to continuing engineering research and technology, specifications are subject to change without notice.

U.S. MAXIMUM outdoor ambient operating temperature is 115°F. (46°C) MAXIMUM TEMPERATURE RATING FOR CLASS 1, DIVISION 2, GROUPS A, B, C, D.

Capacity and efficiency values at each climate conditions are available upon request.

NOTE: Hazardgard unit must be hard-wired.

Manufactured under Design Patent DES 368, 306 decorative front; Utility Patent 5, 662, 058.

Sleeve Dimensions Drawing

SIDE VIEW

A: Max. Wall Depth

B: Junction Box

C: Front

FRIEDRICH

Friedrich Air Conditioning Co. | 10001 Reunion Place, Suite 500 | San Antonio, TX 78216 | 877.599.5665 | www.friedrich.com

BR_HAZ_1-23-20 Printed in USA

PDF preview unavailable. Download the PDF instead.

Hazardgard Brochure Non ATEX 2020 Adobe PDF Library 15.0 Adobe InDesign 15.0 (Windows)

Related Documents

Preview Friedrich Hazardgard Hazardous Location Room Air Conditioners
Friedrich Hazardgard room air conditioners are designed for hazardous locations, meeting UL Class 1, Division 2 standards. They offer robust cooling performance in extreme temperatures and corrosive environments, suitable for industrial applications like oil rigs and chemical plants.
Preview Friedrich Hazardgard® Air Conditioners for Hazardous Locations | Datasheet
Friedrich Hazardgard® air conditioners are engineered for extreme environments, meeting UL Class 1, Div 2 and T4 temperature classification. Designed for hazardous locations like laboratories, control rooms, and industrial sites, they offer robust reliability, durability, and corrosion resistance. Explore specifications, features, and applications for safe and effective cooling.
Preview Friedrich KCVS08B10A Room Air Conditioner Specifications
Detailed specifications for the Friedrich KCVS08B10A ENERGY STAR Certified Room Air Conditioner, including energy efficiency, cooling capacity, dimensions, and certifications.
Preview Friedrich EQ08M11-B Owner's Manual and Parts List
Comprehensive owner's manual and parts list for the Friedrich EQ08M11-B room air conditioner, including exploded diagrams and part numbers.
Preview Friedrich Chill Inverter Series Room Air Conditioners Installation and Operation Manual
This manual provides comprehensive instructions for the installation, operation, and maintenance of Friedrich Chill Inverter Series Room Air Conditioners, including models CCV15, CCV18, and CCV24. It covers safety precautions, setup, troubleshooting, and other features to ensure optimal performance and longevity of the unit.
Preview Friedrich KUHL Room Air Conditioner Limited Warranty Information
This document details the limited warranty for Friedrich KUHL Room Air Conditioners, covering parts for the first year and the sealed refrigerant system for the second through fifth years. It outlines warranty applicability, limitations, how to obtain service, and proof of purchase requirements.
Preview Friedrich KCVS16B30A Room Air Conditioner Specifications | ENERGY STAR Certified
Detailed specifications for the Friedrich KCVS16B30A ENERGY STAR certified room air conditioner, including cooling capacity, energy efficiency, dimensions, and refrigerant type.
Preview Friedrich WCVT12B30A Room Air Conditioner Specifications - ENERGY STAR Certified
Detailed specifications for the Friedrich WCVT12B30A Room Air Conditioner, an ENERGY STAR certified product. Includes information on energy usage, cooling capacity, dimensions, and refrigerant.