ANTRACK V1 Product Manual
Published: May. 2025
Manufacturer: BITMAIN TECHNOLOGIES INC.
Website: www.bitmain.com
Product Description: Industrial cooling system for mining hardware.
Specification
Product Glance
Category | Value |
---|---|
Model | ANTRACK |
Version | V1 |
Capacity | 4 units ANTMINER (Hydro) |
Maximum load, kW | 24 |
Detailed Characteristics
Hardware configuration
Description | Value |
---|---|
Size (Length*Width*Height), mm (without package) | 1000*600*2100 |
Size (Length*Width*Height), mm (with package) | 2260*1130*780 |
Net weight, kg (without package) | 195 |
Gross weight, kg (with package) | 290 |
Network connection mode | RJ45 Ethernet 10/100M |
Power supply
Description | Value |
---|---|
Power supply AC input voltage, Volt | 380~415V AC |
Power supply AC input frequency range, Hz | 50~60 |
Maximum power supply AC input current, Amp | 80 |
Fan
Description | Value |
---|---|
Rated power, W | 120 |
Noise, dBA@1m | 68 |
Size (Length*Height*Thickness), mm | 280*280*80 |
Pump
Description | Value |
---|---|
Rated power, W | 450 |
Noise, dBA@1m | 55 |
Size (Length*Width* Height), mm | 360*210*268 |
Plate heat exchanger
Description | Value |
---|---|
Maximum heat exchange power, kW | 30 |
Size (Length*Width* Height), mm | 305*106*64 |
Diameter of water pipe connector, mm | DN25 |
Environment requirements
Description | Value |
---|---|
Ambient temperature, °C | 15~45 |
Water flow, L/min | 32.0~40.0 |
Water pressure, bar | ≤3.5 |
Working fluid | Antifreeze (10%) |
Liquid PH | 7.8~8.5 |
Storage temperature, °C | -20~70 |
Operation humidity(non-condensing), RH | 10~90% |
Notes
(1-1) Caution: Wrong input voltage may cause server damaged.
(1-2) Three-phase AC input.
(1-3) If the water conductivity is ≥100 µs/cm, the fluid must be replaced. The water conductivity is less than 20 µs/cm when the system is running at the first time. The recommended replacement intervals for pure water, antifreeze, and corrosion inhibitor are every 1–2 months, 3–6 months, and approximately 12 months, respectively.