1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
1-1. Transportation
- Please transport the UPS system only in the original package to protect against shock and impact.
1-2. Preparation
- Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
- Do not install the UPS system near water or in moist environments.
- Do not install the UPS system where it would be exposed to direct sunlight or near heater.
- Do not block ventilation holes in the UPS housing.
1-3. Installation
- Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
- Place cables in such a way that no one can step on or trip over them.
- Do not connect domestic appliances such as hair dryers to UPS output sockets.
- The UPS can be operated by any individuals with no previous experience.
- Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
- When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.
1-4. Operation
- Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
- The UPS system features its own internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
- Prevent no fluids or other foreign objects from inside of the UPS system.
1-5. Maintenance, service and faults
- The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
- Caution -risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
- Before carrying out any kind of service or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors. WAIT 5 MINUTES BEFORE REMOVING THE COVER PROTECTIONS!
- Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
- Caution -risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
- Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
- Remove wristwatches, rings and other metal objects
- Use only tools with insulated grips and handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source and load prior to installing or maintaining the battery.
- When changing batteries, install the same number and same type of batteries.
- A battery can present a risk of electric shock and burns by high short-circuit current.
- Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces. When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
- Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
- Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
- Do not dismantle the UPS system.
- WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user many be required to take additional measures. (only for 220/230/240 VAC system)
- Only for 110/120 VAC system:
- NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
- WARNING: Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
1-6. Product Handling Guidelines
Handling guidelines based on weight:
- Less than 18 kg (<40 lb)
- 18-32 kg (40-70 lb)
- 32-55 kg (70-120 lb)
- Greater than 55 kg (>120 lb)
Visual indicators for handling:
- [Forklift icon] Heavy item handling
- [Two people carrying box icon] Two-person lift required
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
2-1. Rear panel view
Descriptions of rear panel ports for different models:
1U 1.5K / 1U 2.2K Models:
- 1: AC input
- 2: Input breaker
- 3: Programmable output receptacle
- 4: RS232 communication (DB9 or RJ45 port)
- 5: USB serial communication port
- 6: ROO/RPO function connector
- 7: Mute button
- 8: Intelligent slot (SNMP/AS400. etc)
- 9: External battery connector
- 10: CAN communication port for external battery
- 11: RS485 communication port for external battery
- 12: Output breaker for light load outlets
1U 3K Model:
The 1U 3K model shares similar rear panel port functions with the 1.5K/2.2K models, with specific cable connectors noted:
- 1: AC input (L5-30P connector)
- 3: Programmable output receptacle
- 4: RS232 communication (DB9 or RJ45 port)
- 5: USB serial communication port
- 8: Intelligent slot (SNMP/AS400. etc)
- 9: External battery connector
- 10: CAN communication port for external battery
- 11: RS485 communication port for external battery
- 12: Output breaker for light load outlets
Battery pack:
- 1: External battery connector
- 2: ID switch
- 3: Com. port (RJ11)
- 4: Com. port (RJ45)
- 5: Breaker
- 6: Ground screw
2-2. Setup the UPS
Step 1: External battery connection
Follow the chart to connect UPS and external battery pack. (Diagram shows connections between UPS units and battery packs with colored wires: blue, red, black.)
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
Step 3: UPS output connection
The 4 programmable output receptacles can be programmed via USB or RS232 port.
Step 4: Communication connection
Connect communication cables for various ports:
- RS232 port (DB9 or RJ45)
- USB port
- Intelligent slot
- Battery communication (CAN/RS485)
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable from the USB/RS-232 port to your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with an intelligent slot perfect for an SNMP card, providing advanced communication and monitoring options.
Step 4: Disable/Enable ROO/RPO function
ROO (Remote On/Off) Function:
- Contact open: UPS shuts down.
- Contact closed: UPS starts up (UPS is connected to AC power and AC power is available).
RPO (Remote Power Off) Function:
- Contact open: UPS shuts down and Fault LED (3) will be ON.
Note: The local ON/OFF control by pressing the On/Off button overrides the remote-control function.
To return to normal operation, de-activate external remote contact (Fault LED (3) will be OFF) and restart the UPS by pressing the button.
Step 5: Turn on/off the UPS
Press the ON/OFF button on the front panel for two seconds to power on the UPS.
Step 6: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert the provided CD into your CD-ROM drive. If not, follow these steps to download and install the software from the internet:
- Go to the website http://www.power-software-download.com
- Click the ViewPower software icon and then choose your required OS to download the software.
- Follow the on-screen instructions to install the software.
- When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
3. Operations
3-1. Button operation
Button | Function |
---|---|
ON/OFF Button |
|
3-2. LED Indicators
Front panel LED indicators:
- LED1
- LED2
- LED3
- LED4
- LED5
- LED6
- LED7
- LED8
- LED9
UPS Status | LED | Color | Lighting/Flashing |
---|---|---|---|
Line Mode | LED1 | Green | Lighting |
LED4 to LED7 indicate load level during line mode. | |||
LED4: > 75% load level | Green | Lighting | |
LED5: 50% ~ 75% load level | Green | Lighting | |
LED6: 25% ~ 50% load level | Green | Lighting | |
LED7: 0% ~25% load level | Green | Lighting | |
Battery Mode | LED2 | Yellow | Flashing |
LED4 to LED7 indicate battery capacity during battery mode. | |||
LED4: battery capacity > 75% | Green | Lighting | |
LED5: battery capacity > 50% | Green | Lighting | |
LED6: battery capacity > 25% | Green | Lighting | |
LED7: battery capacity > 5% | Green | Lighting | |
Low battery | LED7 | Green | Flashing |
Battery replacement | LED3 | Red | Lighting |
Fault | LED3 | Red | Flashing |
On/off status of output receptacles | LED 8: indicating on/off status of general output receptacles () LED 9: indicating on/off status of programmable outlet () | Green | Lighting |
3-3. Audible Alarm
Alarm Type | Sounding Pattern |
---|---|
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
Bypass Mode | Sounding every 10 seconds |
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom | Possible cause | Remedy |
---|---|---|
No indication and alarm even though the mains is normal. | The AC input power is not connected well. | Check if input power cord firmly connected to the mains. |
The AC input is connected to the UPS output. | Plug AC input power cord to AC input correctly. | |
The mains is normal but fault LED is flashing. The alarm is sounding every second. | The internal or external battery connection is wrong. | Please re-connect battery wires with correct polarity. |
The alarm is sounding twice every second and fault LED is flashing. | UPS is overload | Remove excess loads from UPS output. |
After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains. | Remove excess loads from UPS output first. Then, shut down the UPS and restart it. | |
The mains is normal. But the unit is on battery mode. | Battery is not fully charged. | Please charge battery at least 5 hours. If battery is still in low battery level, please contact local dealer. |
Battery defect. | Replace the battery with the same type of battery. | |
Fault LED is on and alarm is sounding continuously. | UPS fault. | Please contact local dealer directly. |
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
[Recycling symbol] [Battery symbol] Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Storage Temperature | Recharge Frequency | Charging Duration |
---|---|---|
-25°C -50°C | Every 3 months | 1-2 hours |
50°C -55°C | Every 2 months | 1-2 hours |
6. Specifications
MODEL
N1C.C1500 | N1C.C2200 | N1C.C3000 | |
---|---|---|---|
CAPACITY | 1500 VA / 1350 W | 2200 VA / 1980 W | 3000 VA / 2700 W |
INPUT
Parameter | Value |
---|---|
Rated voltage | 110/120 VAC |
Low Line Transfer Voltage | 80VAC/70VAC/60VAC/55VAC ± 5 % (based on load percentage 100% -80 % / 80 % -70 % / 70 -60 % / 60 % -0) |
Low Line Comeback Range | 85VAC/75VAC/65VAC/60VAC ± 5 % (based on load percentage 100% -80 % / 80 % -70 % / 70 -60 % / 60 % -0) |
High Line Transfer | 150 VAC ± 5% |
High Line Comeback | 140 VAC ± 5% |
Rated frequency | 60Hz or 50Hz |
Frequency Range | 40Hz ~ 70 Hz |
Phase | Single phase with ground |
Power Factor | ≥0.99 @ Nominal voltage (full load) |
AC Input Fuse/breaker | 20A breaker (N1C.C1500, N1C.C2200), 30A breaker (N1C.C3000) |
Input Cable* | 6FT with plug NEMA L5-20P or other cables with same specification (N1C.C1500, N1C.C2200) 6FT with plug NEMA L5-30P or other cables with same specification (N1C.C3000) |
OUTPUT
Parameter | Value |
---|---|
Short-Circuit Current | Approx.192A peak, 2.9A rms (N1C.C1500) Approx.250A peak, 3.9A rms (N1C.C2200, N1C.C3000) |
Output voltage | 110/120 VAC |
AC Voltage Regulation | ± 1% |
Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
Frequency Range (Bat. Mode) | 60Hz or 50 Hz± 0.3 Hz |
Overload | 100%~105%: audible warning 105%-130%: UPS shuts down in 10 seconds at battery mode or transfers to bypass mode after 2min when the utility is normal. >130%: UPS shuts down immediately at battery mode or transfer to bypass mode after 10s when the utility is normal. |
Current Crest Ratio | 5:1 for 110/120 VAC system or 3:1 for 220/230/240 VAC systems |
Harmonic Distortion | ≤3 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) |
AC Mode to Transfer Bat Mode Time | Zero |
Inverter to Bypass Time | 4 ms (Typical) |
Waveform (Bat Mode) | Pure Sinewave |
EFFICIENCY
AC Mode | ~ 92% @ 100% load (N1C.C1500) ~ 94% @ 100% load (N1C.C2200) ~ 90% @ 100% load (N1C.C3000) |
Battery Mode | ~ 88% @ 100% load (N1C.C1500) ~ 90% @ 100% load (N1C.C2200) ~ 88% @ 100% load (N1C.C3000) |
BATTERY
Parameter | N1C.C1500 | N1C.C2200 | N1C.C3000 |
---|---|---|---|
Battery Type | Lithium-iron battery, 38.4V / 6Ah | Lithium-iron battery, 48V / 5Ah | Lithium-iron battery, 48V / 5Ah |
Numbers | 1 | 1 | 1 |
Charger current | 1.5A | 1/2.5/5/8A, 2.5A as default*** | 1/2.5/5/8A, 2.5A as default*** |
Recharge Time | 4 hours recover to 90% capacity | 2 hours recover to 90% capacity | 2 hours recover to 90% capacity |
Battery fuse | 40A/58V*2PCS | 40A/58V*4PCS | 40A/58V*4PCS |
PHYSICAL
Parameter | N1C.C1500 | N1C.C2200 | N1C.C3000 |
---|---|---|---|
Dimension, D X W X H | 509 x 438 x 44 mm 20.04 x 17.24 x 1.73 in | 580 x 438 x 44 mm 22.83 x 17.24 x 1.73 in | 580 x 438 x 44 mm 22.83 x 17.24 x 1.73 in |
Net Weight | 12.4 kg / 27.34 lb | 14.2 kg / 31.3 lb | 14 kg / 30.86 lb |
ENVIRONMENT
Parameter | Value |
---|---|
Operating Temperature | 0 °C to 50 °C |
Operating Storage | 0-2000 m |
Operation Humidity | 20-90 % RH @ 0-50°C (non-condensing) |
International Protection Code | IP20 |
Applicable Power Grid Power Distribution System | TN Power System |
Pollution Degree | 2 |
Overvoltage category | II for normal mode |
Noise Level | Less than 50dBA @ 1 Meter |
MANAGEMENT
Parameter | Value |
---|---|
USB/RS-232 | Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
* When input power cord is provided, Please use incidental power cord in the package.
**When output voltage is 208Vac, the power will be derated to 80%
***If UPS connect with the external battery, the charge current will be changed to 8A.
RUNTIME TABLE
N1C.C3000
Load Percent/min | 25% | 50% | 75% | 100% |
---|---|---|---|---|
Internal battery(LIO 48005) | 17.5 | 8.5 | 5.5 | 4 |
1Battery Pack(LIO 4802) | 70 | 34 | 19 | 13 |
2Battery Pack(LIO 4802) | 140 | 68 | 39 | 27 |
3Battery Pack(LIO 4802) | 210 | 102 | 56 | 38 |
4Battery Pack(LIO 4802) | 280 | 136 | 81 | 55 |
N1C.C2200
Load Percent/min | 25% | 50% | 75% | 100% |
---|---|---|---|---|
Internal battery(LIO 48005) | 22.5 | 11 | 7 | 5.2 |
1Battery Pack(LIO 4802) | 95 | 46 | 25 | 17 |
2Battery Pack(LIO 4802) | 190 | 92 | 53 | 36 |
3Battery Pack(LIO 4802) | 286 | 139 | 76 | 51 |
4Battery Pack(LIO 4802) | 381 | 185 | 110 | 75 |
N1C.C1500
Load Percent/min | 25% | 50% | 75% | 100% |
---|---|---|---|---|
Internal battery(38.4V 6Ah) | 28 | 14.5 | 9.5 | 7 |