User Manual

NIC

N1C.C1500, N1C.C2200, N1C.C3000

Uninterruptible Power Supply System

Version: 1.1

1. Important Safety Warning

Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.

1-1. Transportation

1-2. Preparation

1-3. Installation

1-4. Operation

1-5. Maintenance, service and faults

1-6. Product Handling Guidelines

Handling guidelines based on weight:

Visual indicators for handling:

2. Installation and setup

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.

2-1. Rear panel view

Descriptions of rear panel ports for different models:

1U 1.5K / 1U 2.2K Models:

1U 3K Model:

The 1U 3K model shares similar rear panel port functions with the 1.5K/2.2K models, with specific cable connectors noted:

Battery pack:

2-2. Setup the UPS

Step 1: External battery connection

Follow the chart to connect UPS and external battery pack. (Diagram shows connections between UPS units and battery packs with colored wires: blue, red, black.)

Step 2: UPS input connection

Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.

Step 3: UPS output connection

The 4 programmable output receptacles can be programmed via USB or RS232 port.

Step 4: Communication connection

Connect communication cables for various ports:

To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable from the USB/RS-232 port to your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.

The UPS is equipped with an intelligent slot perfect for an SNMP card, providing advanced communication and monitoring options.

Step 4: Disable/Enable ROO/RPO function

ROO (Remote On/Off) Function:

RPO (Remote Power Off) Function:

Note: The local ON/OFF control by pressing the On/Off button overrides the remote-control function.

To return to normal operation, de-activate external remote contact (Fault LED (3) will be OFF) and restart the UPS by pressing the button.

Step 5: Turn on/off the UPS

Press the ON/OFF button on the front panel for two seconds to power on the UPS.

Step 6: Install software

For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert the provided CD into your CD-ROM drive. If not, follow these steps to download and install the software from the internet:

  1. Go to the website http://www.power-software-download.com
  2. Click the ViewPower software icon and then choose your required OS to download the software.
  3. Follow the on-screen instructions to install the software.
  4. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.

3. Operations

3-1. Button operation

ButtonFunction
ON/OFF Button
  • Turn on the UPS: Press and hold button for at least 2 seconds to turn on the UPS.
  • Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS. UPS will be in standby mode when utility power is normal or transfer to bypass mode if bypass mode is enabled via software.

3-2. LED Indicators

Front panel LED indicators:

UPS StatusLEDColorLighting/Flashing
Line ModeLED1GreenLighting
LED4 to LED7 indicate load level during line mode.
LED4: > 75% load levelGreenLighting
LED5: 50% ~ 75% load levelGreenLighting
LED6: 25% ~ 50% load levelGreenLighting
LED7: 0% ~25% load levelGreenLighting
Battery ModeLED2YellowFlashing
LED4 to LED7 indicate battery capacity during battery mode.
LED4: battery capacity > 75%GreenLighting
LED5: battery capacity > 50%GreenLighting
LED6: battery capacity > 25%GreenLighting
LED7: battery capacity > 5%GreenLighting
Low batteryLED7GreenFlashing
Battery replacementLED3RedLighting
FaultLED3RedFlashing
On/off status of output receptaclesLED 8: indicating on/off status of general output receptacles ()
LED 9: indicating on/off status of programmable outlet ()
GreenLighting

3-3. Audible Alarm

Alarm TypeSounding Pattern
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinuously sounding
Bypass ModeSounding every 10 seconds

4. Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table below.

SymptomPossible causeRemedy
No indication and alarm even though the mains is normal.The AC input power is not connected well.Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.Plug AC input power cord to AC input correctly.
The mains is normal but fault LED is flashing. The alarm is sounding every second.The internal or external battery connection is wrong.Please re-connect battery wires with correct polarity.
The alarm is sounding twice every second and fault LED is flashing.UPS is overloadRemove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains.Remove excess loads from UPS output first. Then, shut down the UPS and restart it.
The mains is normal. But the unit is on battery mode.Battery is not fully charged.Please charge battery at least 5 hours. If battery is still in low battery level, please contact local dealer.
Battery defect.Replace the battery with the same type of battery.
Fault LED is on and alarm is sounding continuously.UPS fault.Please contact local dealer directly.

5. Storage and Maintenance

Operation

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.

[Recycling symbol] [Battery symbol] Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.

Storage

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage TemperatureRecharge FrequencyCharging Duration
-25°C -50°CEvery 3 months1-2 hours
50°C -55°CEvery 2 months1-2 hours

6. Specifications

MODEL

N1C.C1500N1C.C2200N1C.C3000
CAPACITY1500 VA / 1350 W2200 VA / 1980 W3000 VA / 2700 W

INPUT

ParameterValue
Rated voltage110/120 VAC
Low Line Transfer Voltage80VAC/70VAC/60VAC/55VAC ± 5 % (based on load percentage 100% -80 % / 80 % -70 % / 70 -60 % / 60 % -0)
Low Line Comeback Range85VAC/75VAC/65VAC/60VAC ± 5 % (based on load percentage 100% -80 % / 80 % -70 % / 70 -60 % / 60 % -0)
High Line Transfer150 VAC ± 5%
High Line Comeback140 VAC ± 5%
Rated frequency60Hz or 50Hz
Frequency Range40Hz ~ 70 Hz
PhaseSingle phase with ground
Power Factor≥0.99 @ Nominal voltage (full load)
AC Input Fuse/breaker20A breaker (N1C.C1500, N1C.C2200), 30A breaker (N1C.C3000)
Input Cable*6FT with plug NEMA L5-20P or other cables with same specification (N1C.C1500, N1C.C2200)
6FT with plug NEMA L5-30P or other cables with same specification (N1C.C3000)

OUTPUT

ParameterValue
Short-Circuit CurrentApprox.192A peak, 2.9A rms (N1C.C1500)
Approx.250A peak, 3.9A rms (N1C.C2200, N1C.C3000)
Output voltage110/120 VAC
AC Voltage Regulation± 1%
Frequency Range (Synchronized Range)57 ~ 63 Hz or 47 ~ 53 Hz
Frequency Range (Bat. Mode)60Hz or 50 Hz± 0.3 Hz
Overload100%~105%: audible warning
105%-130%: UPS shuts down in 10 seconds at battery mode or transfers to bypass mode after 2min when the utility is normal.
>130%: UPS shuts down immediately at battery mode or transfer to bypass mode after 10s when the utility is normal.
Current Crest Ratio5:1 for 110/120 VAC system or 3:1 for 220/230/240 VAC systems
Harmonic Distortion≤3 % THD (Linear Load) ≤ 5 % THD (Non-linear Load)
AC Mode to Transfer Bat Mode TimeZero
Inverter to Bypass Time4 ms (Typical)
Waveform (Bat Mode)Pure Sinewave

EFFICIENCY

AC Mode~ 92% @ 100% load (N1C.C1500)
~ 94% @ 100% load (N1C.C2200)
~ 90% @ 100% load (N1C.C3000)
Battery Mode~ 88% @ 100% load (N1C.C1500)
~ 90% @ 100% load (N1C.C2200)
~ 88% @ 100% load (N1C.C3000)

BATTERY

ParameterN1C.C1500N1C.C2200N1C.C3000
Battery TypeLithium-iron battery, 38.4V / 6AhLithium-iron battery, 48V / 5AhLithium-iron battery, 48V / 5Ah
Numbers111
Charger current1.5A1/2.5/5/8A, 2.5A as default***1/2.5/5/8A, 2.5A as default***
Recharge Time4 hours recover to 90% capacity2 hours recover to 90% capacity2 hours recover to 90% capacity
Battery fuse40A/58V*2PCS40A/58V*4PCS40A/58V*4PCS

PHYSICAL

ParameterN1C.C1500N1C.C2200N1C.C3000
Dimension, D X W X H509 x 438 x 44 mm
20.04 x 17.24 x 1.73 in
580 x 438 x 44 mm
22.83 x 17.24 x 1.73 in
580 x 438 x 44 mm
22.83 x 17.24 x 1.73 in
Net Weight12.4 kg / 27.34 lb14.2 kg / 31.3 lb14 kg / 30.86 lb

ENVIRONMENT

ParameterValue
Operating Temperature0 °C to 50 °C
Operating Storage0-2000 m
Operation Humidity20-90 % RH @ 0-50°C (non-condensing)
International Protection CodeIP20
Applicable Power Grid Power Distribution SystemTN Power System
Pollution Degree2
Overvoltage categoryII for normal mode
Noise LevelLess than 50dBA @ 1 Meter

MANAGEMENT

ParameterValue
USB/RS-232Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Optional SNMPPower management from SNMP manager and web browser

* When input power cord is provided, Please use incidental power cord in the package.

**When output voltage is 208Vac, the power will be derated to 80%

***If UPS connect with the external battery, the charge current will be changed to 8A.

RUNTIME TABLE

N1C.C3000

Load Percent/min25%50%75%100%
Internal battery(LIO 48005)17.58.55.54
1Battery Pack(LIO 4802)70341913
2Battery Pack(LIO 4802)140683927
3Battery Pack(LIO 4802)2101025638
4Battery Pack(LIO 4802)2801368155

N1C.C2200

Load Percent/min25%50%75%100%
Internal battery(LIO 48005)22.51175.2
1Battery Pack(LIO 4802)95462517
2Battery Pack(LIO 4802)190925336
3Battery Pack(LIO 4802)2861397651
4Battery Pack(LIO 4802)38118511075

N1C.C1500

Load Percent/min25%50%75%100%
Internal battery(38.4V 6Ah)2814.59.57
Models: N1C.C1500, N1C.C2200, N1C.C3000, C3000 Uninterruptible Power Supply System, C3000, Uninterruptible Power Supply System, Power Supply System, Supply System

File Info : application/pdf, 14 Pages, 969.31KB