IAQ Wiring Supplement 105917 005 JAN25
IAQ Sensor
Supplemental Wiring Manual for Accessories
EV-Series SL-Series EV Premium HE-Series LE-Series

IAQ-D

IAQ-W

ACCESSORY IAQ Sensor

1.0 OVERVIEW

3

2.0 DIMENSIONS

3

2.1 IAQ-W .................................................................................................................3 2.2 IAQ-D .................................................................................................................3

3.0 ELECTRICAL

4

3.1 WIRING SCHEMATICS...........................................................................................4

4.0 FACTORY ASSISTANCE

7

TABLE OF SCHEMATICS
Figure 3.1.0 Wiring Schematic for EV90, EV90P, EV130, EV200, EV240, EV300 Units Only ........................ 4 Figure 3.1.1 Wiring Schematic for EV Premium and SL75 Units ................................................................. 4 Figure 3.1.2 Wiring Schematic for HE1.5IN Units without ECM................................................................... 5 Figure 3.1.3 Wiring Schematic for HE1.5RT, LE-Series, and all HE2X and larger Units without VFDs
or ECM ................................................................................................................................ 5 Figure 3.1.4 Wiring Schematic for HE- and LE-Series units with Factory-Installed VFDS ............................ 5 Figure 3.1.5 Wiring Schematic for HE1.5 Units with ECM and Terminal Block............................................. 6 Figure 3.1.6 Wiring Schematic for HE05, HE07, HE10, and HE1.5 Units with ECM and Circuit Board ........... 6 Figure 3.1.7 Wiring Schematic for HE05, HE07, HE10, and HE1.5 Units with ECM, Circuit Board,
and Timer............................................................................................................................. 7

2 1.800.627.4499

e dims Ttahkeesne fdriommTshGteasrkeeeydnsitmforonsmetamkGearnneuyfrsaotlomKnMeGmCreayJnUstuLoan1l9eKmMaCnuJUalLK1M9 C JUL19

IAQ Sensor

OVERVIEW ACCESSORY

1.0 OVERVIEW
The Indoor Air Quality (IAQ) monitor uses an advanced MEMS metal oxide semiconductor sensor to detect poor air quality. The sensor reacts quickly to detect a broad range of VOCs such as smoke, cooking odors, bio-effluence, outdoor pollutants, and from human activities. The sensor captures all VOC emissions that are completely invisible to CO2 sensors and provides a linear analog signal output of 4­20 mA, 0­5, or 10­10 VDC and a Normally Open (NO) relay to control an alarm or ventilation fan in various ways.

2.0 DIMENSIONS
2.1 IAQ-W

.3"

3.3"

3.3"

1.15"

1.15" 1.15"

2.3"

4"
3.5"
2.3"

2.3"

4.7"

5.7"

4.7"

4.7"

Conduit/EMT Connection Ø 0.875"

4.5"

3.25"Mounting 3H.o2le5s"
(X4) Ø 0.200"

3.25"

2.2 IAQ-D
4" 3.5"

5.7"

4.5"

9.5"

2.5"

7.0"

Vent Holes

1"

Conduit/EMT Connection Ø 0.875"

Mounting Holes (X4) Ø 0.200"

Vent Holes

9.5"

2.5"

7.0"

Vent Holes

1"

1.800.627.4499 3

ELECTRICAL ACCESSORY

IAQ Sensor

3.0 ELECTRICAL
3.1 WIRING SCHEMATICS

FIGURE 3.1.0 WIRING SCHEMATIC FOR EV90, EV90P, EV130, EV200, EV240, EV300 UNITS ONLY
In this example, the IAQ Controller turns the Energy Recovery Ventilator (ERV) on at High speed when the IAQ sensor level exceeds IAQ Controller Relay setting.
LCD

OP1/LINEAR OP /A5O COM PWR

N.O. Relay
24VAC HIGH COM DAMPER Unit Wiring Terminals

120COM 120VAC

Control Board

SF_ECM_SIGNAL 1 2 3

WHT 1 RD 2 BK 3 YL 4

SF_ECM_POWER 1 2
EF_ECM_POWER EF_ECM_SIGNAL

21

22 1

FIGURE 3.1.1 WIRING SCHEMATIC FOR EV PREMIUM AND SL75 UNITS

4 1.800.627.4499

IAQ Sensor

ELECTRICAL ACCESSORY

FIGURE 3.1.2 WIRING SCHEMATIC FOR HE1.5IN UNITS WITHOUT ECM FIGURE 3.1.3 WIRING SCHEMATIC FOR HE1.5RT, LE-SERIES, AND ALL HE2X AND LARGER UNITS WITHOUT VFDS OR ECM

FIGURE 3.1.4 WIRING SCHEMATIC FOR HE- AND LE-SERIES UNITS WITH FACTORY-INSTALLED VFDS

1.800.627.4499 5

ELECTRICAL ACCESSORY

IAQ Sensor

FIGURE 3.1.5 WIRING SCHEMATIC FOR HE1.5 UNITS WITH ECM AND TERMINAL BLOCK
In this example, the IAQ Controller turns the ERV on at speed set by potentiometers when the IAQ sensor level exceeds IAQ Controller Relay setting.
LCD

1

OP1/LINEAR OP /ASO CO PWR

N.O. Relay

Doorkill Switch RD BK

RD 24VAC BK COM YL EN PU VAR

DOORKILL1

24VAC COM

DOORKILL2 1

OA/FA 2

1

3

2

4

3

4

1

5

Circuit Board EA/RA 2

6

3

OR EF10V

4

CW

YL PU

EFW EFGND

EF

OR SF10V

1
BYPASS 2 3

YL SFW

SF

4

PU SFGND

BYPASSCOM

CW

J1

EF

SF

FIGURE 3.1.6 WIRING SCHEMATIC FOR HE05, HE07, HE10, AND HE1.5 UNITS WITH ECM AND CIRCUIT BOARD

6 1.800.627.4499

IAQ Sensor

FACTORY ASSISTANCE ACCESSORY

In this example, the ERV does not run while unoccupied, set by timer. During occupancy, the ERV runs at variable Speed. IAQ Controller sets speed based on IAQ sensor levels. Remove the potentiometers by cutting the wires at the potentiometer. Cap the orange and purple wires from the potentiometer with wire nuts.

LCD

5

OP1/L1N-AR OP2/ASO COM PWR
2 1 TC7D Timer

N.O. Relay

Doorkill Switch RD BK

RD 24VAC BK COM YL EN PU VAR
1 2 3 4 5 6
OR YL PU OR SF10V YL SFW PU SFGND

DOORKILL1 24VAC COM

DOORKILL2

1
OA/FA 2 3 4

1

2

3

SF

4

BYPASSCOM J1

FIGURE 3.1.7 WIRING SCHEMATIC FOR HE05, HE07, HE10, AND HE1.5 UNITS WITH ECM, CIRCUIT BOARD, AND TIMER
4.0 FACTORY ASSISTANCE
In the unlikely event that you need assistance from the factory for a specific issue, make sure that you have the information called for in the Unit Records page in the Owner Information section of the unit manual. The person you speak with at the factory will need that information to properly identify the unit and the installed options.
To contact RenewAire Customer Service: Call 800-627-4499 Email: RenewAireSupport@RenewAire.com

1.800.627.4499 7

About RenewAire
For over 40 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size. This is achieved while maximizing sustainability through our fifth-generation, static-plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and decrease operational expenses by minimizing equipment needs, resulting in significant energy savings. Our ERVs are competitively priced, simple to install, easy to use and maintain and have a quick payback. They also enjoy the industry's best warranty with the lowest claims due to long-term reliability derived from innovative design practices, expert workmanship and Quick Response Manufacturing (QRM).
As the pioneer of static-plate core technology in North America, RenewAire is the largest ERV producer in the USA. We're committed to sustainable manufacturing and lessening our environmental footprint, and to that end our Waunakee, WI plant is 100% powered by wind turbines. The facility is also one of the few buildings worldwide to be LEED and Green Globes certified, as well as having achieved ENERGY STAR Building status. In 2010, RenewAire joined the Soler & Palau (S&P) Ventilation Group in order to provide direct access to the latest in energyefficient air-moving technologies. For more information, visit: renewaire.com