Installation Guide for MICRO CONTROL SYSTEMS models including: 3507B8115 MCS-Actuator, 3507B8115, MCS-Actuator

Actuator Feedback Calibration

Application Notes

MCS-ACTUATOR Installation


File Info : application/pdf, 5 Pages, 1.29MB

PDF preview unavailable. Download the PDF instead.

APP132 - Actuator INSTALL AND WIRING
APPLICATION NOTE

APP-132

Rev. -10-07-2022

MCS-ACTUATOR
Model 3507B8115 - 120 VAC
Installation

MCS-ACTUATOR replacement for Trane Centrifugal
When installing MCS Controls on a Trane Centrifugal that has a stepper actuator type like the UPC2 or newer, it will be necessary to change this to a pulse to open/close type actuator like the earlier Trane #2970 actuator.

Part Number (VAC)
MCS ACTUATOR (MA3507B8115)

Capacity N (lb)
3500 (787)

Stroke mm (in)
153 (6.0)

Travel speed mm/sec (in/min)
6 (14)

3.04" (77.2mm)

6.18" (157.1mm)
2.93" (74.5mm)

1.02" (Ø26mm)
Ø.51" Ø13mm

®

4.10" (104.2mm)

Retracted 16.1" (410mm)
2" (Ø50.8mm)
3.42" (Ø87mm)

Retracted (A) Mm (in) 410 (16.1)
Stroke 6.0" (153mm)
Ø.45" (11.5mm)
1.12" (Ø28.6mm)
Ø.51" (Ø13mm)

3.75" 1.20" (95.4mm) (30.5mm)

8.61" (218.6mm)

1.20" (30.5mm)

MCS-ACTUATOR replacement for Trane Centrifugal
Step 1 - Determine exact mounting for replacement or new install.
TRANE UCP1
Shows Actuator piston fits between forks of bracket for moving the vane
TRANE UCP2 
Bracket for moving the vane is difference on UCP2, some installation modifications must be made when
installing MCS-ACTUATOR on this model.
DO NOT CONNECT TO MECHANICAL LOAD BEFORE VERIFYING FULL RANGE AND FUNCTION
OF MCS-ACTUATOR PISTON MOVEMENT
Step 2 - With MCS-ACTUATOR unmounted, measure the movement of the chiller vane when opened and closed and mark these measurements down.
Step 3 - Add Power to the MCS-ACTUATOR, measure the exact movement of the piston extension after the actuator is opened fully.
Step 4 - Compare the measurement of the chiller vane with the MCS-ACTUATOR piston extension when opened. Example: MCS-ACTUATOR tube is extended 6 inches when stopped. Example: Chiller vane movement measurement is 5 inches when opened.
Step 5 - MCS-ACTUATOR MUST BE CALCULATED SO THE PISTON EXTENSION MATCHES THE OPENING OF THE CHILLER VANE.
Step 6 - If the MCS-ACTUATOR piston movement is set correctly for the opening of the chiller vane, proceed to installing and wiring the MCS-ACTUATOR, IF NOT, PROCEED TO RE-CALCULATE THE LIMIT SWITCHES ON THE NEXT PAGE.

Figure 1 and Figure 2 below illustrates the limit switch components. Exercise reasonable precaution when making adjustments. Do not contact the inner tube while the motor is running.

MCS-Actuator includes limit switches, which are preset to the design limits of the unit. Customers who choose to make limit switch position adjustments must ensure the limits remain within the design limits of the actuator. Note that adjustments to the preset positions need to be made before the actuator is installed.
DO NOT CONNECT TO MECHANICAL LOAD BEFORE VERIFYING FULL RANGE AND FUNCTION
OF PISTON MOVEMENT
Limit Switch Adjustment
Limit switches on MCS Actuators are pre-set. These instructions are provided in case the pre-set positions need to be adjusted.
1. If the actuator is not already fully retracted operate the actuator until the lower limit is reached and the motor stops. If satisfied with the actuator retract dimension as positioned continue to step # 3.
2. To finely position the retract stopping location rotate the inner actuator tube until the desired stopping location is achieved. Do not rotate the inner tube in a manner to position it lower than the minimum 16.1 inches from clevis hole to clevis hole as shown in the drawing.
3. From this point on until the actuator is fully mounted in the assembly it is important not to allow the inner tube to rotate. Allowing it to rotate will alter the retracted position location and require repeating steps 1 & 2.
4. To set the upper limit switch position, secure the inner tube from rotating by either gripping it by hand or slide a screwdriver through the clevis hole and lay the actuator down flat on a suitable work surface.
5. Electrically operate the actuator until the desired extend position is reached. If the actuator stops on its own before reaching the desired position the retract position may have been set too high and the physical travel limitations of the actuator have been exceeded. To rectify this problem repeat steps 1 & 2 or modify your assembly/ structure geometry.
6. Once the desired extend position is reached. Use an Allen wrench to remove the five hex head cap screws at the base of the actuator housing, and gently pull the limit switch cover off the housing. It may be necessary to straighten the wires in the pigtail to facilitate separation. This will expose the limit switch assembly.
7. Loosen the Phillips-head screw on the limit switch cam assembly just enough so the upper cam can separate from the lower cam but not enough where the screw is removed completely. Adjust the upper cam by simultaneously pulling gently away from the lower cam and rotate until the upper cam just depresses the extend limit switch plunger. Take care not to disturb the position of the lower cam and gear.
8. Tighten the Phillips-head screw and if desired electrically retract the actuator to confirm the retracted dimension and extend to confirm the fully extended position. If satisfied continue to the next step otherwise repeat the instructions outlined above.
9. Carefully replace the cover, taking care that the gasket is in place and the wires remain tucked inside the cover. Tighten the five socket head cap screws to fasten the cover in place.
10. Once the limit switches are set, the unit can be mounted into the assembly.

2. Wiring Instructions for Motor and MCS SI

Gray Wiring to MCS SENSOR
(15ft - Red, Black and White Wires)

Black Coiled Cable (18ft - Red, Black and White cable) to Power and Earth Ground

10 K Ohm Slidewire

COM NO NC

Wiring effective 02/11/2022 RED wire to +5
BLACK wire to GND White wire to SI
+5 GND SI
SENSO

Red Black White

RELAY M-3

Open Vane

TB2

COM NO NC

TB2 RELAY M-4 Close Vane
Factory Wired: Field Wired: TB2: 120v Line TB3: 120v Neutral

CR1

5

1

43

Vane Open White Wire

CR2

5

1

43

Vane Close Black Wire

TB3
TB3 Neutral Red Wire
MCS- Actuator

Ground Green Wire

Factory Wired: Field Wired:

Revision History Date
1-16-19 05-15-2020 12-01-2021 02-11-2022 02-17-2022

Author DMC DEW DEW DEW DEW

Description Actuator Feedback Calibration
Setup for Limit Switch Added info for wiring and install
Changed wiring Changes from John on wording

Any questions regarding this release, contact: support@mcscontrols.com
Micro Control Systems, Inc. 5580 Enterprise Parkway Fort Myers, Florida 33905 (239)694-0089 FAX: (239)694-0031 www.mcscontrols.com