2-WIRE LOOP TEST/MAINTENANCE MODULE

i3 SERIES

Features
· Allows all 2-wire i3TM detectors to be used on any compatible 2 or 4-wire fire alarm control panel
· Interprets the i3 remote maintenance signal · Provides visual indication and an output relay
when a detector on the loop requires cleaning · Initiates the EZ Walk loop test · Provides Style D wiring on IDC loops · Green, red, and yellow LEDs indicate
­ Loop communication status ­ Maintenance alert ­ Freeze trouble ­ Alarm ­ EZ Walk test enabled ­ Wiring fault · Mounts to 4"-square back box · Durable terminal blocks with SEMS screws

Description
The 2W-MOD2 two-wire loop test/maintenance module maximizes the benefits of the i3TM series smoke detectors, by offering detector remote maintenance signaling and EZ Walk loop testing capabilities.
Installation Ease The 2W-MOD2 mounts to a 4"-square back box for quick and easy installation. Terminal blocks with durable SEMS screws assure a reliable connection.
Intelligence The 2W-MOD2 allows communication to 2-wire i3 detectors with any listed fire alarm control panel. This in turn enables i3 detectors to initiate a remote maintenance signal when they are in need of cleaning, and to provide a visual indication of this condition at the module and at the panel. The 2W-MOD2 also features the EZ Walk loop test for 2-wire i3 series detectors. This function verifies the entire initiating loop wiring with just the press of a button.

Engineering Specifications
Loop test/maintenance module shall be an i3 series model number 2W-MOD2, listed to Underwriters Laboratories UL 864 for Control Units for Fire Protection Signaling Systems. The module shall include provisions for mounting to 4-inch square back boxes. Wiring connections shall be made by means of SEMS screws. The module shall provide three LED indicators which will blink or illuminate to indicate communication status, maintenance alert, alarm or freeze trouble conditions, and EZ Walk loop test mode. The module shall allow communication to 2-wire i3 detectors with any UL listed fire alarm control panel. The 2W-MOD2 shall offer provisions for Style D wiring on IDC loops, and shall provide a loop testing capability to verify the initiating loop wiring.
Mounting

Instant Inspection The 2W-MOD2 includes three LEDs -- green, red, and yellow -- that provide status indication for the loop. These LEDs indicate the following:
­ Loop communication status ­ Maintenance alert ­ Alarm ­ Freeze trouble ­ EZ Walk test enabled ­ Wiring fault

The 2W-MOD2 mounts directly to 4" square electrical boxes.
MEA
approved

5129 CATALOG NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES. Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.

firealarmresources.com

Electrical Specifications
Operating Voltage Nominal: 12/24 V Min.: 8.5 V power limited Max.: 35 V power limited Maximum Ripple Voltage 30% of nominal (peak to peak)

Maximum Standby Current 30 mA Maximum Alarm Current 90 mA Max. Maintenance Current 53 mA

Alarm Contact Ratings 0.5 A @ 36VDC, Resistive Maintenance Contact Ratings 2 A @ 30VDC, Resistive

LED Modes
LED Color Status

Green LED Red LED

On
Blinking 1 sec. on / 1 sec. off Off On
Blinking 1 sec. on / 1 sec. off

On Yellow LED
Blinking 0.5 sec. on / 0.5 sec. off

Condition Power on. Detectors on loop do not have communication capability. Power on. Detectors on loop are communicating normally. Power not applied or module not in operation. Detector on loop in alarm. One or more detector on loop is in need of maintenance or is in freeze trouble. Loop wiring fault exists. EZ Walk test mode.

Power Up Sequence for LED Indication
Condition Initial LED status indication EZ Walk test available

Duration 2 minutes 6 minutes after reset

Physical Specifications
Operating Temperature Range 14°F­122°F (­10°C to 50°C) Operating Humidity Range 0 to 95% RH non-condensing Input Terminals 14­22 AWG

Dimensions Height: 4.5 inches (114 mm) Width: 4.0 inches (101 mm) Depth: 1.25 inches (32 mm) Weight 8 oz. (225 grams)

Mounting 4-inch square back box

Ordering Information

Model 2W-MOD2

Description 2-wire loop test/maintenance module for 2-wire i3 Series standard, sounder and Form C relay smoke detectors

NOT TO BE USED FOR INSTALLATION PURPOSES. Distributed by:

Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113

U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113

Web page: http://www.mircom.com Email: mail@mircom.com

firealarmresources.com

CAT. 5129 Rev. 4

