WALL MOUNT LED STROBES

FS-400

Description
Mircom's FS-400 wall mount strobes offer a visual solution that deliver exceptional energy efficiency in a compact design. Utilizing advanced LED technology, the FS-400 strobes provide a lower current draw which allows for more devices on a NAC circuit while reducing the number of external power supplies required.
The FS-400 strobes can be field-configured for 15, 15/75, 30, 75, 110, 185 cd. The candela setting is displayed through the front window for easy identification. The device settings are located on the back of the unit to prevent tampering.
The FS-400 strobes can be synchronized using a control panel with the Mircom sync protocol or the SDM240 synchronization module.
The FS-400 strobes utilize a universal mounting plate that allows for mounting to a single gang, double gang, octagon, 4" junction or 4" square electrical box. The back plate allows the installer to mount the plate and connect the wire connections. The device attaches to the mounting plate and is secured by a single mounting screw. In addition, the FS-400 can mount to the Mircom BB-400 Series back box for surface mount applications.
Compliance
· UL 1971 · UL 1638 · ULC-S526 · NFPA 72 2016 Edition

Features
· Compact Design · Advanced LED technology provides superior
current draw performance · Lower power consumption per device allows
for more notification appliances per circuit and reduces the need for external power supplies · Standard and High candela settings in one unit to meet virtually any application
- 15, 15/75, 30, 75, 110, 185 cd · Device settings are located on the back of the
unit to prevent tampering
· Includes shorting clip that allows installers to test the wiring before the device is installed
· Supports 12 to 22 AWG
· Mount to Mircom BB-400 surface mount back box, single gang, 4-inch square, double gang, octagon and 4-inch junction boxes
· All units include universal mounting plate · Red or white finish · For indoor applications
Engineering Specifications
The strobe shall be a Mircom FS-400 notification appliance for wall mount applications. The strobe shall be of a low current draw design and operate at 24 VDC regulated or full wave rectified. The strobe shall incorporate a Light Emitting Diode (LED) as the light source and have six field selectable settings of 15, 15/75, 30, 75, 110, 185 candela. The candela selection shall be in a visible location. The candela settings shall be tamper resistant. The strobe shall be synchronized using a control panel with the Mircom sync protocol or the SDM-240 sync module. The strobe shall utilize a mounting plate that allows the installer to pre-wire the mounting plate. The mounting plate shall mount on a single gang, double gang, octagon, 4-inch square box or Mircom's BB-400 series back box. The strobe shall be listed to UL standard 1638, Visible Signaling Devices for Fire Alarm and Signaling Systems and standard 1971, Signaling Devices for the Hearing Impaired. In addition, the strobe shall be listed to ULC S526, Visible Signal Devices for Fire Alarm Systems.

S5375

S5375 7125-1477:0501

5274 CATALOG NUMBER
NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.

firealarmresources.com

Specifications

General Specifications

Light Output Dispersion

Operating temperature

0°C to 50°C (32°F to 122°F)

Humidity range

0% to 93%

Strobe flash rate

1 Hz

Nominal Voltage

Regulated 24 VDC / 24 VFWR

Operating Voltage Range (RMS) 16 to 33

Input terminal wire gauge

22 AWG to 12 AWG

Installation environment

For indoor use only

FS-400 Wall Strobe Operating RMS Currents (mA)

Candela

Regulated 24 VDC Regulated 24 VFWR

15

25

64

30

39

106

75

102

189

15/75

93

189

110

105

189

185

179

241

Degrees
±0 ±5 ±10 ±15 ±20 ±25 ±30 ±35 ±40 ±45 ±50 ±55 ±60

% of Candela Rating

Horizontal Dispersion

Vertical Dispersion, Wall to Floor

149

148

146

149

143

153

138

135

134

104

128

101

123

94

116

92

106

84

99

75

92

68

87

65

82

61

Candela Settings

±65

78

58

±70

75

54

±75

73

49

±80

72

43

±85

81

40

±90

53

30

Compound ±45°

42

CandCealnadeslaestettitningg sswwitcihtch
Dimensions 1 /" (50 mm)
4 / " (123 mm)

Note: The values are shown as percentages of the rated light output at any candela setting.

4 / " (117 mm)

BB-400 Surface Mount Back Box
4 / " (123 mm)

4 /" (123 mm)

4 /" (120 mm)

4 /" (123 mm)

Height and width (all models)

Wall Mount Strobes & Horn/Strobes
(FS-400 & FHS-400)

Ordering Information

Model Number

Description

FS-400-RR

Wall Mount Strobe, Red

FS-400-WW BB-400R BB-400W SDM-240

Wall Mount Strobe, White Surface Mount Back Box, Red Surface Mount Back Box, White Synchronization Module

Mounting Plate

Knockout dimensions: 1 / " (27 mm)

NOT TO BE USED FOR INSTALLATION PURPOSES. Distributed by:

Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113

U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113

Web page: http://www.mircom.com Email: mail@mircom.com

firealarmresources.com

1 /" (46 mm)
CAT. 5274 Rev. 0

