Installation Guide for CHAMBERLAIN models including: 0635 Manual DC Operators Proof 6, 0635, Manual DC Operators Proof 6, DC Operators Proof 6, Operators Proof 6, Proof 6
Chamberlain Group LLC, The 0635 HBW0635 HBW0635 0635
File Info : application/pdf, 36 Pages, 4.87MB
DocumentDocumentJDC/JHDC Installation (continued) Mount the Operator The wall or mounting surface MUST provide adequate support for the operator. The surface must: · Be rigid to prevent play between the operator and the door shaft. · Provide a level base. · Permit the operator to be fastened securely and with the drive shaft parallel to the door shaft. 1. Mount the operator to the wall or mounting plate with the appropriate hardware (not supplied). 2. Place the door sprocket on the door shaft. 3. Wrap the drive chain around the door sprocket and the drive sprocket then secure with the master link. 4. Align the door and the drive sprockets. Insert keys and fasten the sprockets with the set screws (recommended torque for the set screws is 34-45 in/lb). NOTE: It is highly recommended to add a thread adhesive to secure the set screws in place. 1 3 2 Secure the Chain Hoist 1. Fasten the door retaining bracket 4 feet (1.2 m) above the floor. NOTE: If the position of the operator causes the hand chain to hang in the door opening hook the chain to the side near the top of the door jamb. Door retaining bracket 18 Cable Tension Monitors Install the Cable Tension Monitor(s) (Optional) TWO CABLE TENSION MONITORS MAY BE CONNECTED TO THIS OPERATOR. THE CABLE TENSION MONITORS DETECT ANY SLACK THAT MAY OCCUR IN THE CABLES AND WILL RESPOND ACCORDINGLY. NOTE: ONLY USE THE LIFTMASTER CABLE TENSION MONITORS, AS THEY HAVE BEEN TESTED AND APPROVED FOR THIS SYSTEM. See "Accessories" on page 52. 1. Make sure the door cable is approximately 1"-2" (25-50 mm) from the mounting surface. Door adjustments or shimming may be required to achieve proper depth for the door cable. The bracket must be flush with the mounting surface. Cable Drum Drum Cable tension monitor 2. Position the cable tension monitor as close to the drum as possible. The optimal distance of the cable from the wall surface is no more than 2.5" (6.35 cm), and be sure the roller extends 1/8"-1/4" past the cable. Make sure the cable tension monitor and roller is free from any obstructions in all positions of operation. Approx. 1-2" 25-60cm (when door is closed) NOTE: There must be no obstructions in the installation area that prevent the cable tension monitor from closing completely when slack is detected. Cable Tension Monitor NOTE: Cable tension monitors must either be anchored to concrete, or a wood stud with appropriate fasteners. If neither are available, toggle bolt style drywall anchors with at least a 50 lbs rating are acceptable. 1/4"-3/8" (6.4-95 mm) Cable Tension Monitor Roller 3. Run bell wire to the door operator junction box, and down to SBC the control box through conduit as shown on the right. CMN 4. Once the controller is installed, connect the bell wires parallel to the CTM and CMN terminals on the terminals on CTM the controller (polarity is not important). See "Wall Controller CMN Installation" on page 22 for installation information. Once installed, follow these steps to connect the wiring. 21 22 23 24 SBC CABLE TENSION MONITORS 5. Connect the bell wires in parallel to the CTM and CMN terminals on the controller (polarity is not important). To simplify installation, the cable tension monitors can be wired together in the operator junction box, with only one pair of bell wires running down to the controller. 6. Repeat steps 1-5 for the opposite side of the door. Both cable tension monitors must be installed for proper operation. NOTE: Cable must have tension through entire door travel. Make sure there is no slack in cable on opposite side of door during normal operation. If slack occurs during door travel, adjust cables as required. OVERVIEW Cable Tension Monitors e a 19 Manual Release Emergency Disconnect System Model TDC TO DISCONNECT DOOR FROM OPERATOR The door should be in the fully closed position if possible. 1. Pull emergency release handle straight down. Emergency disconnect will open. TO RECONNECT DOOR ARM TO TROLLEY 2. Lift free end of door arm to trolley. Pull emergency release handle to allow arm to engage roll pin. Release handle. Emergency disconnect will close. 1 WARNING To prevent possible SERIOUS INJURY or DEATH from a falling door or arm: · DISCONNECT electric power to the operator BEFORE manually operating your door. · DO NOT stand under the door arm when pulling the emergency release. · If possible, use emergency disconnect ONLY when door is CLOSED. Weak or broken springs or unbalanced door could result in an open door falling rapidly and/or unexpectedly. · NEVER use emergency release handle unless doorway is clear of persons and obstructions. 2 NOTICE Emergency Disconnect System Model JHDC These operators have provisions for manually operating the door in case of emergency or power failure. These operators are equipped with a manual hoist. An electrical interlock will disable the electrical controls when the hoist is used. This operator includes Engage rope (green) and a disengage rope (red) with manual hoist to electrically disable the operator controls. 1. To disengage, pull the disconnect rope (red). 2. Operate the door in the desired direction by pulling on one side or the other of the continuous loop hoist chain. 3. Pull the engage rope (green) to operate the door again electrically. OPERATE A MANUAL HOIST 1. Pull down on the hoist engagement rope, engaging the hoist/interlock. NOTE: F96 SAFETY CIRC will be displayed. 2. Operate the door in the desired direction by pulling on one side or the other of the continuous loop chain. 3. To restore standard electrical operation to the operator, pull the hoist disengagement rope to disengage the hoist/interlock. 20 Wiring WARNING To prevent possible SERIOUS INJURY or DEATH: · ANY maintenance to the operator or in the area near the operator MUST NOT be performed until disconnecting the electrical power and locking-out the power. Upon completion of maintenance the area MUST be cleared and secured, at that time the unit may be returned to service. · Disconnect power at the fuse box BEFORE proceeding. Operator MUST be properly grounded and connected in accordance with national and local electrical codes. The operator should be on a separate fused line of adequate capacity. · ALL electrical connections MUST be made by a qualified individual. · DO NOT install ANY wiring or attempt to run the operator without consulting the wiring diagram. · ALL power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled. · ALL power and control wiring MUST be run in separately. Power and Ground Power and control wiring must be run in separate conduit to comply with national and local electrical codes. For power wiring, use the appropriate wire gauge. Use conduit knockouts, conduit fittings, and appropriate conduit fittings for wiring as indicated on the electrical box label. 1. Open the operator cover. 2. Run power wires to electrical box according to national and local electrical codes. ON THREE PHASE POWER only use two of the power legs cap off the third leg: Incoming power leads go to L1 and L2. Ground is on the EMI board. 3. Attach power and ground wires to appropriate terminals. Incoming power leads go to L1 and L2. Ground is on the EMI filter board. NOTE: The operator must be properly grounded. Failure to properly ground the operator could result in electric shock and serious injury. * Maximum wire gauge that can be connected to the operator's terminal is 12 AWG. When a larger wire gauge is required, the wire must be gauged down to 12 AWG. USE COPPER WIRE ONLY. Voltage Selection 1. Locate EMI filter board inside of the electrical box (there is one board for 120/240V and one board for 480V). Remove the sticker and plug in the connector to either the 120V or 240V depending on your line voltage. Replace the sticker once you have plugged your connector into the right location. 2. On the POWER BOARD find the appropriate receptacle matching the incoming line voltage. Remove the voltage label and apply to the inside of the electrical box for future reference. Insert the EMI power harness fully until locked in place. 21 Wall Controller Installation WARNING To prevent possible SERIOUS INJURY or DEATH from electrocution: · Be sure power is NOT connected BEFORE installing the door control. To prevent possible SERIOUS INJURY or DEATH from a closing door: · Install the door control within sight of the door, out of reach of small children, at a minimum height of 5 feet (1.5 m) above landings, steps, or any other adjacent walking surface, and away from ALL moving parts of the door. · Install the control station far enough from the door to prevent the user from coming in contact with the door while operating the controls. · Install the entrapment warning placard on the wall next to the control station in a prominent location visible from the door. · NEVER permit children to operate or play with door control push buttons or remote controls. · Activate a door ONLY when it can be seen clearly, is properly adjusted and no obstructions exists in the path the door will travel. · ALWAYS keep the door in sight until completely closed. NEVER permit anyone to cross path of a closing door. NOTE: The field wiring terminals are rated for 14-22 AWG wire Stranded and 12-22 AWG Solid. 1. Remove wall control cover from mounting bracket by loosening the four Philips screw at each corner of the housing. 2. Using appropriate mounting hardware (not supplied), fasten the mounting bracket to the wall near the 23 operator and at least 5 feet (1.5m) above floors, landings, steps, or any other adjacent walking surface. 1 3. Select the appropriate knockout and run the wires to the operator (in accordance with national and local electrical codes). 4. Connect wires to the wall controller (wall controller wires are NOT polarity sensitive) and reinstall the wall controller cover. 5. Fasten the entrapment warning placard next to the wall control. 4 5 22 Factory Wiring Diagram 23 Factory Wiring Diagram (continued) 24 Accessory Wiring Diagram CLASS 2 SUPPLY +24V Accessories may connect to the regular or switched port. Switched is turned off at loss of AC to preserve battery life. ACCESSORY POWER 24VDC, 1A Brown Blue DRY CONTACT NOTE: INTR LOCK jumper MUST be removed if switch is added. Plug transformer conne appropriate voltage tha the applied Red Black Optional Accessories: AUX Relay Card and Loop Detector. Ancillary (non-monitored) devices and dry contact inputs NO/NC. SBC OPEN CLOSE STOP NOTE: STOP - CMN jumper MUST be removed if a 3-Button Station is added. Close - Output 2 (Blue) Open - Output 1 (Green) Black 50-HERK2 CABLE TENSION MONITORS Resistive Edge White/Black To EYE/EDGE White To CMN Photo Eyes CPS-U, CPS-UN4, CPS-OPEN4, OES-RD16 LC36M Brown Blue White/Black White Tx Rx Light Curtain LC36M 25 Power Wiring Diagram Plug transformer connector into the appropriate voltage that matches the applied AC voltage 120V AC or 240V AC Red Black Optional Accessories: AUX Relay Card and Loop Detector. 480V AC on 480V model 480V comes factory wired 26 Entrapment Protection Monitored Entrapment Protection IMPORTANT INFORMATION ABOUT THE MONITORED ENTRAPMENT PROTECTION DEVICES A monitored entrapment protection device is required for most operation modes (see "Monitored Eyes/ Edge Configuration" on page 32). If a monitored entrapment protection device is not installed, constant pressure to close will be required from the wall controller. See "Accessories" on page 52 for a complete list of monitored entrapment protection devices. Three EYE/EDGE terminals are provided. Each terminal can accept ONE device. For easy identification during installation, the correct terminals are yellow. CLASS 2 SUPPLY +24V Accessories may connect to the regular or switched port. Switched is turned off at loss of AC to preserve battery life. ACCESSO RY POWER 24VDC, 1A Brown Blue White/Black To EYE/EDGE White To CMN Photo Eyes CPS-U, CPS-UN4, CPS-OPEN4, OES-RD16 LC36M Brown Blue White/Black White Tx Rx WARNING To prevent possible SERIOUS INJURY or DEATH from a closing door: · Be sure power is NOT connected to the door operator BEFORE installing the photoelectric sensor(s). · The door MUST be in the fully opened or closed position BEFORE installing the LiftMaster Monitored Entrapment Protection Device(s). To prevent SERIOUS INJURY, DEATH, ENTRAPMENT, or PROPERTY DAMAGE: · Correctly connect and align the photoelectric sensor. · Install the primary monitored photoelectric sensor beam NO HIGHER than 6" (15 cm) above the floor. · This is a required LMEP Device for B2, TS, T, and FSTS wiring types and MUST NOT be disabled. For D1, C2, and E2 wiring the installation of an entrapment protection device is recommended. · LiftMaster Monitored Entrapment Protection Devices are for use with LiftMaster Commercial Door Operators ONLY. Use with ANY other product voids the warranty. · If an edge sensor is being used on a horizontal slide door,place one or more edge sensors on both the leading and trailing edge. · If an edge sensor is being used on a vertical moving door,place edge sensors on the bottom edge of the door. Light Curtain LC36M Typical Entrapment Protection Device(s) Overview Monitored Edge Sensor mounted to the bottom of door. Monitored Photoelectric Sensor 6" (15 cm) max. above the floor. Invisible Light Beam Protection Area Monitored Photoelectric Sensor 6" (15 cm) max. above the floor. 27 Entrapment Protection (continued) Install the Monitored Light Curtain This step includes directions to install one set of monitored light curtains as a standalone primary entrapment protection device. The mounting brackets must be securely fastened to a solid surface such as a wall framing. If installing the mounting brackets in masonry construction, add a piece of wood at each location to avoid drilling extra holes in the masonry. NOTE: If the Monitored Light Curtain is installed with coil cord, the coil cord needs to be secured so it will not interrupt the light beams. 1. Fasten the mounting brackets loosely to both Monitored Light Curtain with the screws provided. 2. Measure a maximum of 6 inches above the floor. Mark this location. The lowest optical sensor of the Monitored Light Curtain must be installed at or below this point. In this application, in order to assure that the lowest optical sensor is mounted no higher than 6" above the ground, the light curtain wires must be oriented at the top of the light curtain in this application. 3. Hold the Monitored Light Curtain up to the desired mounting location with the cable end pointing upward. Secure the bottom mounting bracket to the mounting surface. 4. Make sure the Monitored Light Curtain is level and secure the upper mounting bracket to the mounting surface. 5. Tighten the screws to secure the Monitored Light Curtain to the mounting bracket. 6. Secure the other Monitored Light Curtain to the opposite side of the door following steps 25, making sure they are aligned. 7. Run wires to the operator. 8. Twist like colored wires together, brown to brown and blue to blue. POWER WIRING Do not run wiring in the same conduit with AC power. 1. Disconnect power to the operator. 2. Connect the wires from the Monitored Light Curtain LC36M to the following. d. Brown wire to + Aux24 power WARNING To prevent possible product damage and incorrect operation: · NEVER scratch or paint the optical sensors. · DO NOT drill ANY additional holes into the Monitored Light Curtain. · Correctly connect and align the Monitored Light Curtain transmitter and receiver. · DO NOT bend or twist the Monitored Light Curtain. · Oil may damage the Monitored Light Curtain cable so contamination MUST be avoided at ALL times. · DO NOT mount the Monitored Light Curtain where sunlight or other external infrared light sources will shine directly into the optical sensors of the Monitored Light Curtain receiver. If necessary, switch the mounting side of the Monitored Light Curtain transmitter and receiver. e. Blue wired to Aux24 CMN f. White wire to eye/edge input g. Black wired to eye/edge input + 3. Reconnect power to the operator. ALIGNMENT The Monitored Light Curtain transmitter and receiver must be aligned. When properly wired and aligned the amber and green LEDs will be ON. The amber LED is located on the Monitored Light Curtain Transmitter and the green LED is located on the Monitored Light Curtain Receiver. If the amber and green LEDs are not on, see the table below. 1. Open and close the door for one complete cycle to let the operator register the Monitored Light Curtain. Amber LED Green LED Status Solution OFF OFF No power Check wiring. ON Blinks · Monitored Light Curtain receiver and · Adjust the Monitored Light Curtains to transmitter are not aligned correct alignment · Obstructed light beam · Remove the obstruction · Defective Monitored Light Curtain Receiver · Replace Monitored Light Curtain receiver and transmitter (Model LC36M) NOTE: For more detailed information, please refer to Monitored Light Curtain manual 114-5541. 28 Battery Backup Wiring 1. Locate the Battery Box and the Red/Black wires. 2. Remove the circular knockout at the bottom of the E-Box, above the EMI Filter Board. Install a grommet. 3. Route the Red/Black wires through the grommet. 4. Install the Battery Box on the Operator. 5. Plug the Red wire into the Battery (+) Terminal. 6. Plug the Black wire into the Battery (-) Terminal. 29 Testing Apply power to the operator. When power is applied to the operator, the LCD display will illuminate, relay A, relay B, and the Timer Defeat. Test all Entrapment Protection Devices It is the responsibility of the specifier, purchaser, installer, and property WARNING owner to ensure that, on completion, the installation of the entrapment To avoid SERIOUS personal protection devices comply with all relevant federal, state, and local codes INJURY or DEATH: and regulations. · Disconnect electric power BEFORE performing ANY TEST THE MONITORED LIGHT CURTAIN (IF APPLICABLE) adjustments or maintenance. 1. With the door in the full open position, press the close button. · ALL maintenance MUST be performed by an Authorized 2. While the door is closing, obstruct any of the light beams on the Service Technician. Monitored Light Curtain (the green LED on the Monitored Light Curtain Receiver will blink when the light beam is obstructed). The door should stop and reverse. TEST THE PHOTOELECTRIC SENSORS (IF APPLICABLE) 1. Open the door. 2. Place an obstruction in the path of the photoelectric sensors. The LMEP LED will blink on the logic board. 3. Press and hold the CLOSE button. The door should not close. 4. Remove the obstruction. 5. Press and hold the CLOSE button. Door should close. If the LMEP is activated while closing, the door should reverse. TEST THE EDGE SENSORS (IF APPLICABLE) 1. Open the door 2. Place an obstruction in the path of the door. 3. Press and release the CLOSE button. The door should stop and/or reverse. 4. Remove the obstruction. Press and release the CLOSE button. The door should fully close. Test Wall Controller Menu Access 1. Press OPEN button. (The door should move in the open direction.) 2. Press STOP button. (The door should stop.) 3. Press and hold the CLOSE button. (The door should move in the close direction.) 4. Release CLOSE button. Door should stop if in C2 or D1 mode. Door will reverse to full open position in E2 mode. The door should continue closing in all other modes. 5. Press STOP button. (The door should stop.) Test Limit Adjustment 1. Press OPEN button. (The door should open.) 2. Allow the door to fully open. 3. Press and hold the CLOSE button. (The door should close.) 4. Allow the door to fully close. 5. If the limits are not set properly, remove power and adjust limits (see "Set Limits" on page 32). NOTE: Door travel should stop when the OPEN or CLOSE limits are reached. If door drifting is occurring, spring tension on the door. 30 Programming Quick Start Commissioning Follow the below instructions to provision the JHT operator out-of-the-box or after factory reset: Quick Start Commissioning Menu Follow device menu prompt to select DOOR HANGING Follow device menu prompt to select DOOR DRUM Follow device menu prompt to select DOOR SPROCKET (J/H ONLY) WARNING To prevent possible SERIOUS INJURY or DEATH: · Disconnect electric power BEFORE performing ANY adjustments or maintenance. · ALL maintenance MUST be performed by a trained door systems technician. · Please wait several seconds for capacitors to discharge and for display to go out. Follow device menu prompt to set OPEN LIMIT Follow device menu prompt to set CLOSE LIMIT Follow device menu prompt to LEARN WIFI The operator will be in WiFi Learn Mode for 10 minutes if "YES" is selected. Quick Exit of Menu Hold down the "UP" and red "Stop" buttons for 3 seconds until the screen goes blank and it will exit you out of the menu you are in. Quick Enter into the Menu Hold down the "Down" and red "Stop" buttons for 3 seconds until the screen goes blank and it will take you to the main menu. Manual Commissioning Program Flow IMPORTANT: All entrapment protection devices will be disconnected during the manual commissioning steps. The System Settings menus are password-protected. ENTER PROGRAMMING 1. Press the "STOP/ENTER" and "DOWN" buttons on the inside of the controller at the same time for 3+ seconds to enter the operator menu. If the controller is closed, press the "Stop" then "Close" then "Open" until the unit goes into program mode. 2. Scroll down to "SYSTEMS SETTINGS" with the "UP" and "DOWN" buttons and press "ENTER." You will be prompted to enter the password for the operator. 3. Enter 326 as the password. Door Settings DOOR SETTINGS Standard Lift DOOR SETTINGS High Lift DOOR SETTINGS Vertical Lift 31 Programming (continued) SELECT DOOR SETTINGS 1. To select Door Hanging and Cable Drum settings, navigate to the SYSTEM SETTINGS > DOOR SETTINGS submenu. 2. Select The Drum Type. Correct Drum types are needed for the correct door profile to run the system. Standard lift drum choices are: D400-144, D525-216 Full vertical lift drum choices are: d850-132, D1100-216 High lift choices are: 48° HL, D400-54, D525-54, 60 ° HL: D5575-120, 144 ° HL: D6375-165 IMPORTANT: Once you choose your drum, allow inverter parameter to update. Once the inverter is updated, you can re-enter the menu to set limits and learn force. SET LIMITS IMPORTANT: When setting limit positions, it is important that the door runs in the direction of the intended limit. Example: When setting the close limit, only use the CLOSE button. When setting the open limit, only use the OPEN button. Using the opposite direction button will cause the limit positions to drift over time. To set limits, navigate to the SYSTEM SETTING > DOOR POSITIONS submenu. Door Position Door Position Open Limit Door Position Close Limit Door Position Open Mid-Stop Door Position Close Mid-Stop MONITORED EYES/EDGE CONFIGURATION If monitored entrapment protection devices are wired to the system during the initial power-up, they will be learned to the system, and the operating mode will automatically switch to B2. If no monitored sensor is attached, the system will default to C2 mode. To manually program an entrapment protection device, navigate to the SYSTEM SETTINGS > MONITORED EYES/EDGES submenu, otherwise it will Auto-Learn the monitored device. Monitored Eyes/Edges Auto-Learn All Eye/Edge 1 XXXXX Eye/Edge 2 XXXXX Eye/Edge 3 XXXXX OPERATION MODE (RECOMMENDED) To change the operating mode from the defaults B2 or C2, navigate to the SYSTEM SETTINGS > OPERATION MODE submenu. Operation Mode Oper. Mode C2:CNST PRES Oper. Mode B2:T/TS/NO Oper. Mode D2:CNST PRES Oper. Mode E2:CNST PRES Oper. Mode B2:Timer to CONNECTIVITY (RECOMMENDED) To connect the operator to a network, navigate to SYSTEM SETTINGS > CONNECTIVITY > LEARN > LEARN WIFI submenu. See the "myQ® Smart Facility Access" on page <?> to connect your devices to myQ® Business Facility. Connectivity C2:CNST PRES Learn Remotes Learn myQ® Devices Learn Remotes Connectivity Connectivity C2:CNST PRES Unlearn Remotes Unlearn myQ® Devices Unlearn Remotes 32 Programming (continued) Hold ENTER and DOWN for three seconds to open the System Information Menu. NOTE: This menu tree is only for informational purposes. These settings cannot be changed by the user. 1. SYSTEM INFORMATION Operator HPH1 Controller Ver. VXX.XXX. Display Ver. VXX.XXX. Inverter Ver. VXX.XX VXX.XX ESARM Ver. VXX.XX Absolute Cycles XXXXX Door Maint. XXXXX Cycles System Door Hanging Cable Drum Mid Stop Door Height Oper. Mode Position Type Timer To Close Monitored Eyes/Edges Leave SYSTEM INFO. Eye/Edge 1 Eye/Edge 2 Eye/Edge 3 33 Programming (continued) Operating Modes This operator is programmed to function in one of four different operating modes. See the rest of this section for more detailed information. B2 MODE · Works with buttons on wall controller, myQ Facility®, wired 3-Button Wall Controller, and 3-Button Transmitter; momentary to open, stop,and close. · Works with Single Button Control and Single Button Transmitter; momentary to open, stop, close, and stop & reverse. · A Monitored Entrapment Protection device is required to be connected for downward movement. Monitored Safety devices are Auto-Learned or manually configured through the wall control menu.. · A Monitored Entrapment Protection device activation will reverse the door to its Open limit. An activated Monitored Entrapment Protection device can be overridden with 5 seconds of constant pressure on the Close button. Timer To Close is available in B2 Mode with two settings. The user can select a desired Timer to Close (TTC) timer under the Timers menu. See [XXX] for Timer setting details. In B2 the Car Dealer feature is available. The Car Dealer input (typically a treadle switch, loop detector, or motion sensor) will open the door to mid-stop, and TTC will be enabled. Repeated Car Dealer Input will not open the door beyond the mid-stop and will reset the TTC timer. TTC can be set either to one time close or timer secure In B2 the All Fly feature is available. (FSTS Mode) · The All Fly input (typically a mushroom button) will open the door to its Open limit, bypassing a midstop, and TTC will be enabled. · The CLOSE button immediately closes the door. · The STOP button resets the TTC timer (held button will pause, releasing the button will reset). · The OPEN button resets the TTC timer. · The controller will make infinite attempts to close the door until the safety obstruction is cleared. · TTC will be enabled after Monitored Entrapment Protection activation reverses the door to its Open limit. · Timer Defeat Input will stop TTC timer B2 / T ONE TIME CLOSE) · After the TTC timer elapses operator will close the door. · TTC Timer will be active at the Open Limit or at a defined mid-stop. · The CLOSE button immediately closes the door. · The STOP button cancels the TTC for that cycle (no automatic motion). · The OPEN button resets the TTC timer. · TTC will be disabled if the door reverses from an obstruction. · Timer Defeat Input will stop the TTC timer B2 / TS (TIMER SECURE) · After TTC timer elapses operator will close door. · TTC Timer will be active anywhere above close limit. The CLOSE button immediately closes the door. · The STOP button resets the TTC timer (held button will pause, release resets) · The OPEN button resets the TTC timer. · LMEP activation resets the timer · TTC will be enabled after Monitored Entrapment Protection device activation reverses the door to its Open limit. The controller will make infinite attempts to close the door until it reaches close limit. · Timer Defeat Input will stop the TTC timer C2 MODE (DEFAULT) · Works with buttons on wall controller, wired 3-Button Wall Controller, and 3-Button Transmitter*; momentary to open, stop, and constant pressure to close. · Works with Single Button Control and Single Button Transmitter*; momentary to open, stop, and stop & reverse. · Works without a Monitored Entrapment Protection device learned, but can operate if a Monitored Entrapment Protection device is learned and connected for downward movement. · Monitored Entrapment Protection device activation will reverse the door to its Open limit. The safety activation can be overridden with 5 seconds constant pressure on the Close button. *Constant Pressure to Close is not available from a remote control device (transmitter or myQ® BusinessTM). 34 Programming (continued) Determine Operating Mode Read the descriptions of the different wiring types to determine which setting will be correct for each application. Once the wiring type is determined, set the selector dial accordingly. LIFTMASTER MONITORED ENTRAPMENT PROTECTION (LMEP) DEVICE IS REQUIRED A LiftMaster Entrapment Protection Device is required for the following wiring types. B2 Momentary contact to open, close and stop, plus wiring for sensing device to reverse and auxiliary devices to open and close with open override. Programmable mid stop available with this wiring type. Compatible with 3-Button Station, 1-Button Station, 1 and 3-Button Remote Control. B2 / T Momentary contact to open, close, and stop, with open override and Timer-To-Close. Every device that causes the door to open, except any sensing edge input device, activates the Timer-To-Close. Auxiliary controls can be connected to open input to activate the Timer-To-Close. If the Timer-To-Close has been activated, the open button and radio control can recycle the timer. The stop button will deactivate the timer until the next command input. The Timer-To-Close will function from the programmable mid stop with this wiring type. Compatible with 3-Button Station,1-Button Station and 1 and 3-Button Remote Control. NOTE: Programmable "Car Dealer Mode" available. B2 / TS This mode will attempt to close the door from any position except when fully closed, or when a safety input is present. The stop button will not disable the Timer-ToClose at any position. To disable the Timer-To-Close in this mode, installation of a defeat switch is required (see "Power Wiring Diagram" on page 26). Momentary contact to open, close, and stop with open override and Timer-To-Close. Every device that causes door to open, including a reversing device, activates the Timer-To-Close. Auxiliary controls can be connected to open input to activate the Timer-To-Close. If the timer has been activated, the open button and radio control can recycle the timer. The Timer-To-Close will function from the programmable mid stop with this wiring type. Compatible with 3-Button Station, 1-Button Station and 1 and 3-Button Remote Control. NOTE: A Programmable "Car Dealer Mode" available. FSTS Momentary button contact for open, close and stop programming. User set mid stop. User set Timer-To-Close. The single button station opens the door to the full open limit bypassing the mid stop and activates the Timer-To-Close, putting the operator in B2/TS mode until the door reaches the down limit, or is stopped in travel. At which time the operator enters the B2 mode. Compatible with 3-Button Station, 1-Button Station, 1 and 3-Button Remote Control. A 1-Button remote control in FSTS mode will open only with the Timer-To-Close, bypassing a programmed mid stop. The Timer-To-Close will reset and reverse when closing. LIFTMASTER MONITORED ENTRAPMENT PROTECTION DEVICE IS RECOMMENDED. A LiftMaster Entrapment Protection Device is recommended for the following wiring types. C2 Momentary contact to open and stop with constant pressure to close, open override plus wiring for sensing device to reverse. Programmable mid stop available with this wiring type. Compatible with 3-Button Station and 1-Button Station. E2 Momentary contact to open with override and constant pressure to close. Release of close button will cause door to reverse (roll-back feature) plus wiring for sensing device to reverse. Compatible with 3-Button Station. D1 Constant pressure to open and close with wiring for sensing device to stop. Compatible with 2 or 3-Button Station. IMPORTANT NOTES: 1. External interlocks may be used with all functional modes. 2. Auxiliary devices are any devices that have only dry contacts. Examples: loop detector, pneumatic or electrical treadles, radio controls, one button stations, pull cords, etc. 3. Open override means that the door may be reversed while closing by activating an opening device without the need to use the stop button first. 4. When the door is in a stopped position other than fully closed,and an LMEP or EDGE input is activated, the Restricted Close(RC) feature will allow a close command when the close button is pressed and held. The operator will begin closing after 5seconds. If the close button is released the door will stop. When in E2 mode, the door will move to the fully open position. 35 Programming (continued) Determine and Set Operating Mode Select the operating mode for your application from the menu in the Wall Controller. WIRING TYPE DEVICE ACTION STATE RESPONSE Operator at OPEN limit No change in state Operator at CLOSE limit OPEN button is pressed momentarily Door opening Door closing Door at Open Mid-Stop Door opens to the OPEN limit or Mid-Stop No change in state Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit Door stopped during open or close cycle Door opens to the OPEN limit or Mid-Stop Operator at OPEN limit Door closes to the CLOSE limit CLOSE Operator at CLOSE limit button is Door opening pressed Door closing momentarily Door at Open Mid-Stop No change in state No change in state No change in state Door closes to the CLOSE limit Door stopped during open or close cycle Door closes to the CLOSE limit Operator at OPEN limit No change in state B2 Momentary contact to open,close Front panel buttons (membrane) and 3-Button Operator at CLOSE limit STOP button is pressed momentarily Door opening Door closing Door at Open Mid-Stop No change in state Door stops Door stops No change in state and stop, plus Wall Door stopped during open or close cycle No change in state wiring for Controller Operator at OPEN limit No change in state sensing device to reverse and auxiliary devices to open and close with open override. Programmable Mid-Stops available with this wiring type. Close Mid Stop available but not shown in table. Compatible with 3-Button Station, 1-Button Station, 1 and 3-Button Operator at CLOSE limit OPEN button is held Door opening (constant Door closing pressure) Door at Open Mid-Stop Door opens to the OPEN limit (bypasses MidStop) No change in state (bypasses Mid-Stop) Door will auto reverse to OPEN limit (bypasses Mid-Stop) Door opens to the OPEN limit Door stopped during open or close cycle Door opens to the OPEN limit (bypasses MidStop) CLOSE button is held (constant pressure) Operator at OPEN limit Door closes to the CLOSE limit Operator at CLOSE limit No change in state Door opening No change in state Door closing No change in state Door at Open Mid-Stop Door closes to the CLOSE limit Door stopped during open or close cycle Door closes to the CLOSE limit Operator at OPEN limit No change in state Operator at CLOSE limit OPEN button is pressed momentarily Door opening Door closing Door at Open Mid-Stop Door opens to closest OPEN limit or Mid-Stop No change in state Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit Remote Door stopped during open or close cycle Door opens to the OPEN limit Control. Monitored 3-Button Remote CLOSE Operator at OPEN limit Operator at CLOSE limit Door closes to the CLOSE limit No change in state Entrapment Protection (LMEP) Device required. Control Programmed as OPEN/ CLOSE/STOP button is pressed momentarily Door opening No change in state Door closing No change in state Door at Open Mid-Stop Door closes to the CLOSE limit Door stopped during open or close cycle Door closes to the CLOSE limit Operator at OPEN limit No change in state Operator at CLOSE limit STOP button is pressed momentarily Door opening Door closing Door at Open Mid-Stop No change in state Door stops Door stops No change in state Door stopped during open or close cycle No change in state Operator at OPEN limit Door closes to the CLOSE limit Single Button Remote Control Programmed as SBC Button is pressed Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during the open cycle Door opens to the OPEN limit or Mid-Stop Door stops Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit Door closes to the CLOSE limit Door stopped during the close cycle Door opens to the OPEN limit or Mid-Stop 36 Programming (continued) WIRING TYPE DEVICE Single Button Wall Controller (Wired) B2 (continued) myQ® Smart Facility Access ACTION STATE RESPONSE Operator at OPEN limit Door closes to the CLOSE limit Operator at CLOSE limit Door opens to the OPEN limit or Mid-Stop Door opening Door stops Button is pressed Door closing Door will auto reverse to OPEN limit or Mid-Stop Door at Open Mid-Stop Door opens to the OPEN limit Door stopped during the open cycle Door closes to the CLOSE limit Door stopped during the close cycle Door opens to the OPEN limit or Mid-Stop Button is held (constant pressure) Door Opening No change in state (bypasses Mid-Stop) Operator at OPEN limit No change in state Operator at CLOSE limit Door opens to the OPEN limit or Mid-Stop Door opening No change in state Open is pressed Door closing Door will auto reverse to OPEN limit or Mid-Stop Door at Open Mid-Stop Door opens to the OPEN limit Door stopped during open or close cycle Door opens to the OPEN limit or Mid-Stop Operator at OPEN limit Door closes to the CLOSE limit Operator at CLOSE limit No change in state Close is pressed: Door opening Door closing No change in state No change in state Door at Open Mid-Stop Door closes to the CLOSE limit Door stopped during open or close cycle Door closes to the CLOSE limit WIRING TYPE C2 Momentary contact to open and stop with constant pressure to close (wired devices ONLY), open override plus wiring for sensing device to reverse. Open Mid-Stop available with this mode type. Compatible with 3-Button Station and Single-Button Station DEVICE Front panel buttons (membrane) and 3-Button Wall Controller ACTION OPEN button is pressed momentarily CLOSE button is pressed momentarily STOP button is pressed momentarily OPEN button is held (constant pressure) CLOSE button is held (constant pressure) STATE RESPONSE Operator at OPEN limit No change in state Operator at CLOSE limit Door opens to the OPEN limit or MidStop Door opening No change in state Door closing Door will auto reverse to OPEN limit or Mid-Stop Door at Open Mid-Stop Door opens to the OPEN limit Door stopped during open or close cycle Door opens to the OPEN limit or MidStop Operator at OPEN limit Door closes and stops when button is released Operator at CLOSE limit No change in state Door opening No change in state Door closing No change in state Door at Open Mid-Stop Door closes and stops when button is released Door stopped during open or close cycle Door closes and stops when button is released Operator at OPEN limit No change in state Operator at CLOSE limit No change in state Door opening Door stops Door closing Door stops Door at Open Mid-Stop No change in state Door stopped during open or close cycle No change in state Operator at OPEN limit No change in state Operator at CLOSE limit Door opens to OPEN limit (bypasses Mid-Stop) Door opening No change in state (bypasses Mid-Stop) Door closing Door will auto reverse to OPEN limit (bypasses Mid-Stop) Door at Open Mid-Stop Door opens to the OPEN limit Door stopped during open or close cycle Door opens to the OPEN limit (bypasses Mid-Stop) Operator at OPEN limit Door closes to the CLOSE limit Operator at CLOSE limit No change in state Door opening No change in state Door closing No change in state Door at Open Mid-Stop Door closes to the CLOSE limit Door stopped during open or close cycle Door closes to the CLOSE limit 37 Programming (continued) WIRING TYPE DEVICE ACTION STATE Operator at OPEN limit Operator at CLOSE limit OPEN button is pressed momentarily Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit 3-Button Remote Control CLOSE button Programmed as is pressed OPEN/CLOSE/ momentarily STOP Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit STOP button is pressed momentarily Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Single Button Remote Control Button is Programmed pressed C2 (continued) as SBC Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open cycle Door stopped during close cycle Operator at OPEN limit Operator at CLOSE limit Single Button Wall Controller (Wired) Button is pressed Door opening Door closing Door at Open Mid-Stop Door stopped during open cycle Door stopped during close cycle Button is held (constant pressure) Door Opening Operator at OPEN limit Operator at CLOSE limit Door opening Open is pressed Door closing Door at Open Mid-Stop myQ® Smart Facility Access Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Close is pressed Door closing Door at Open Mid-Stop Door stopped during open or close cycle RESPONSE No change in state Door opens to the OPEN limit or Mid-Stop No change in state Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit Door opens to the OPEN limit or Mid-Stop No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state Door stops Door stops No change in state No change in state No change in state Door opens to the OPEN limit or Mid-Stop Door stops Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit No change in state Door opens to the OPEN limit or Mid-Stop Door closes and stops when button is released Door opens to the OPEN limit or Mid-Stop Door stops Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit Door closes and stops when button is released Door opens to the OPEN limit or Mid-Stop No change in state or Mid-Stop No change in state Door opens to the OPEN limit or Mid-Stop No change in state Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit Door opens to the OPEN limit or Mid-Stop No change in state No change in state No change in state No change in state No change in state No change in state 38 Programming (continued) WIRING TYPE DEVICE ACTION STATE RESPONSE Operator at OPEN limit No change in state OPEN Operator at CLOSE limit button is Door opening pressed Door closing momentarily Door at Open Mid-Stop Door opens to the OPEN limit or Mid-Stop No change in state Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit Door stopped during open or close cycle Door opens to the OPEN limit or Mid-Stop Operator at OPEN limit Door closes and auto reverses when button is released CLOSE Operator at CLOSE limit button is Door opening pressed Door closing momentarily Door at Open Mid-Stop No change in state No change in state No change in state Door closes and auto reverses when button is released Door stopped during open or close cycle Door closes and auto reverses when button is released Operator at OPEN limit No change in state 3-Button Wall Controller STOP Operator at CLOSE limit No change in state button is Door opening Door stops pressed Door closing Door stops momentarily Door at Open Mid-Stop No change in state Door stopped during open or close cycle No change in state Operator at OPEN limit No change in state OPEN Operator at CLOSE limit Door opens to the OPEN limit (bypasses Mid-Stop) button Door opening No change in state (bypasses Mid-Stop) is held Door closing Door will auto reverse to OPEN limit (bypasses Mid- (constant Stop) E2 Momentary contact to open with override and constant pressure pressure) CLOSE button is held (constant pressure) Door at Open Mid-Stop Door opens to the OPEN limit Door stopped during open or close cycle Door opens to the OPEN limit (bypasses Mid-Stop) Operator at OPEN limit Door closes to the CLOSE limit Operator at CLOSE limit No change in state Door opening No change in state Door closing No change in state Door at Open Mid-Stop Door closes and auto reverses when button is released Door stopped during open or close cycle Door closes and auto reverses when button is released to close. Release of close button will cause door to reverse (roll-back Operator at OPEN limit OPEN Operator at CLOSE limit button is Door opening pressed Door closing momentarily Door at Open Mid-Stop No change in state Door opens to the OPEN limit or Mid-Stop No change in state Door will auto reverse to OPEN limit or Mid-Stop Door opens to the OPEN limit feature) Door stopped during open or close cycle Door opens to the OPEN limit or Mid-Stop plus wiring 3-Button Operator at OPEN limit No change in state for sensing device to reverse. Compatible with 3-Button Station. Remote Control Programmed as OPEN/ CLOSE/ STOP CLOSE button is pressed momentarily Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit No change in state No change in state No change in state No change in state No change in state No change in state STOP Operator at CLOSE limit No change in state button is Door opening Door stops pressed Door closing Door stops momentarily Door at Open Mid-Stop No change in state Door stopped during open or close cycle No change in state Operator at OPEN limit No change in state Single Button Remote Control Button is pressed Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop No change in state No change in state No change in state No change in state Door stopped during open or close cycle No change in state Operator at OPEN limit No change in state Single Button Wall Controller (Wired) Button is pressed: Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during the open cycle No change in state No change in state No change in state No change in state No change in state Door stopped during the close cycle No change in state Operator at OPEN limit No change in state Operator at CLOSE limit Door opens to the OPEN limit myQ Door image Door opening is pressed: Door closing No change in state No change in state Door at Open Mid-Stop No change in state Door stopped during open or close cycle No change in state 39 Programming (continued) WIRING TYPE D1 Constant pressure to open and close with wiring for sensing device to stop. Compatible with 2 or 3-Button Station DEVICE ACTION STATE RESPONSE 3-Button Wall Controller 3-Button Remote Control Programmed as OPEN / CLOSE / STOP Not all transmitters will give constant pressure to close Single Button Remote Control Single Button Wall Controller (Wired) myQ Operator at OPEN limit OPEN button is Operator at CLOSE limit pressed Door opening momentarily Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit CLOSE button is pressed momentarily Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit STOP button is Operator at CLOSE limit pressed Door opening momentarily Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit OPEN button is held (constant pressure) Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle CLOSE button is held (constant pressure) Operator at OPEN limit Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit OPEN button is pressed momentarily Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit CLOSE button is pressed momentarily Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit STOP button is pressed momentarily Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Button is Door opening pressed Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Button is pressed: Door opening Door closing Door at Open Mid-Stop Door stopped during the open cycle Door stopped during the close cycle Operator at OPEN limit Operator at CLOSE limit Door image is Door opening pressed: Door closing Door at Open Mid-Stop Door stopped during open or close cycle No change in state Door opens and stops when button is released No change in state Door stops Door opens and stops when button is released Door opens and stops when button is released Door closes and stops when button is released No change in state Door stops No change in state Door closes and stops when button is released Door closes and stops when button is released No change in state No change in state Door stops Door stops No change in state Door stops only in the closed position No change in state Door opens to the OPEN limit No change in state Door stops Door opens to the OPEN limit Door stops only in the closed position Door closes to the CLOSE limit No change in state No change in state No change in state Door closes to the CLOSE limit Door stops only in the open position No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state No change in state 40 Programming (continued) WIRING TYPE DEVICE ACTION STATE Operator at OPEN limit Operator at CLOSE limit OPEN Door opening button is pressed Door closing momentarily Door at Open Mid-Stop Door stopped during open or close cycle T Momentary contact to open, close, and stop, with Operator at OPEN limit CLOSE button is Operator at CLOSE limit Door opening pressed Door closing momentarily Door at Open Mid-Stop open override and Timer-ToClose (TTC). Every device that causes the door to open, except any sensing edge Door stopped during open or close cycle Front panel Operator at OPEN limit buttons Operator at CLOSE limit (membrane) and 3-Button Wall STOP button is pressed momentarily Door opening Door closing Controller Door at Open Mid-Stop Door stopped during open or close cycle input device, activates the TTC. Auxiliary controls can be connected to open input to activate the TTC. If the TTC has OPEN button is held (constant pressure) Operator at OPEN limit Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop been activated, the open button and radio control can recycle the timer. The stop button will deactivate the timer until the next command input. The TTC CLOSE button is held (constant pressure) Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit will function from the Open limit stop and Open Mid-Stop available with this mode type. Operator at CLOSE limit OPEN button is Door opening pressed Door closing momentarily Door at Open Mid-Stop Compatible with 3-Button Station, 1-Button Station and 1 and 3-Button Remote Control. Close Mid-Stop is available but 3-Button Remote Control Programmed as OPEN/ CLOSE/ STOP CLOSE button is pressed momentarily Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop not shown in Door stopped during open or close cycle table. Operator at OPEN limit Monitored Entrapment Protection (LMEP) Device required. Operator at CLOSE limit STOP button is pressed momentarily Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Single Button Remote Control Programmed Button is pressed as SBC Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during the open cycle Door stopped during the close cycle RESPONSE No change in state (Recycle timer) Door opens to the OPEN limit or Mid-Stop (and activates TTC) No change in state Door will auto reverse to OPEN limit or Mid-Stop (and activates TTC) Door opens to the OPEN limit (and activates TTC) Door opens to the OPEN limit or Mid-Stop (and activates TTC) Door closes to the CLOSE limit No change in state No change in state No change in state Door closes to the CLOSE limit Door closes to the CLOSE limit No change in state (Deactivate timer) No change in state Door stops Door stops No change in state (Deactivate timer) No change in state No change in state (Recycle & hold timer) Door opens to the OPEN limit (bypasses MidStop) and activates TTC No change in state (bypasses Mid-Stop) Door will auto reverse to OPEN limit (bypasses Mid-Stop) and activates TTC Door opens to the OPEN limit and activates TTC Door opens to the OPEN limit (bypasses MidStop) and activates TTC Door closes to the CLOSE limit No change in state No change in state No change in state Door closes to the CLOSE limit Door closes to the CLOSE limit No change in state (Recycle timer) Door opens to the OPEN limit or Mid-Stop and activates TTC No change in state Door will auto reverse to OPEN limit or Mid-Stop and activates TTC Door opens to the OPEN limit and activates TTC Door opens to the OPEN limit or Mid-Stop and activates TTC Door closes to the CLOSE limit No change in state No change in state No change in state Door closes to the CLOSE limit Door closes to the CLOSE limit No change in state (Deactivate timer) No change in state Door stops Door stops No change in state (Deactivate timer) No change in state Door closes to the CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC Door stops Door will auto reverse to OPEN limit or Mid-Stop and activates TTC Door opens to the OPEN limit and activates TTC Door closes to the CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC 41 Programming (continued) WIRING TYPE T (continued) DEVICE ACTION STATE RESPONSE Operator at OPEN limit Door closes to the CLOSE limit Operator at CLOSE limit Door opens to the OPEN limit or Mid-Stop Door opening Door stops Single Button Wall Button is pressed Controller (Wired) Door closing Door will auto reverse to OPEN limit or Mid-Stop and activates TTC Door at Open Mid-Stop Door opens to the OPEN limit and activates TTC Door stopped during the open cycle Door closes to the CLOSE limit Door stopped during the close cycle Door opens to the OPEN limit or Mid-Stop and activates TTC Button is held (constant Door opening pressure) No change in state Operator at OPEN limit No change in state (Recycle timer) Operator at CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC Open is pressed Door opening Door closing No change in state Door will auto reverse to OPEN limit or Mid-Stop and activates TTC myQ® Smart Facility Access Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Door opens to the OPEN limit and activates TTC Door opens to the OPEN limit or Mid-Stop and activates TTC Door closes to the CLOSE limit Operator at CLOSE limit No change in state Close is pressed Door opening Door closing Door at Open Mid-Stop No change in state No change in state Door closes to the CLOSE limit Door stopped during open or close cycle Door closes to the CLOSE limit WIRING TYPE DEVICE ACTION STATE RESPONSE TS - Operator at OPEN limit No change in state (Recycle TTC) This mode will attempt to close the door from Operator at CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC any position except when fully closed, or when a safety input is present. The stop button will recycle the Timer-To-Close (TTC) at any position. To disable the TTC in this mode, installation of a defeat switch is required (see wiring diagram). OPEN Door opening No change in state button is pressed Door closing Door will auto reverse to OPEN limit or MidStop and activates TTC momentarily Door at Open Mid-Stop Door opens to the OPEN limit and activates TTC Door stopped during open or close cycle Door opens to the OPEN limit or Mid-Stop and activates TTC Operator at OPEN limit Door closes to the CLOSE limit CLOSE button is Operator at CLOSE limit Door opening No change in state No change in state Momentary contact to open, close, and stop pressed Door closing momentarily Door at Open Mid-Stop No change in state Door closes to the CLOSE limit with open override and TTC. Every device that causes door to open, including a reversing device, activates the TTC. Auxiliary controls can be connected to open input to activate the TTC. If the timer has been activated, the open button and radio control can recycle the timer. The TTC will Door stopped during open or close cycle Door closes to the CLOSE limit Operator at OPEN limit No change in state (Recycle TTC) Front panel STOP Operator at CLOSE limit No change in state buttons button is Door opening Door stops and activates TTC (membrane) and 3-Button pressed momentarily Door closing Door at Open Mid-Stop Door stops and activates TTC No change in state (Recycle TTC) Wall Door stopped during open or close cycle No change in state (Recycle TTC) Controller Operator at OPEN limit No change in state (Recycle & hold TTC) Operator at CLOSE limit Door opens to the OPEN limit (bypasses Mid-Stop) and activates TTC OPEN button Door opening No change in state (bypasses Mid-Stop) and activates TTC function from the Open limit and Open mid stop with this operating mode type. Close Mid Stop available but not shown in table. Compatible with 3-Button Station, 1-Button Station and 1 and 3-Button Remote Control. Monitored Entrapment Protection (LMEP) Device required. is held (constant pressure) CLOSE button is held (constant pressure) Door closing Door will auto reverse to OPEN limit (bypasses Mid-Stop) and activates TTC Door at Open Mid-Stop Door opens to the OPEN limit and activates TTC Door stopped during open or close cycle Door opens to the OPEN limit (bypasses Mid-Stop) and activates TTC Operator at OPEN limit Door closes to the CLOSE limit Operator at CLOSE limit No change in state Door opening No change in state Door closing No change in state Door at Open Mid-Stop Door closes to the CLOSE limit Door stopped during open or close cycle Door closes to the CLOSE limit 42 Programming (continued) WIRING TYPE TS (continued) DEVICE ACTION STATE Operator at OPEN limit Operator at CLOSE limit OPEN button is pressed momentarily Door opening Door closing Door at Open Mid-Stop 3-Button Remote Control Programmed as OPEN/ CLOSE/STOP CLOSE button is pressed momentarily STOP button is pressed momentarily Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Single Button Remote Control Programmed Button is pressed Door closing as SBC Door at Open Mid-Stop Door stopped during the open cycle Door stopped during the close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Single Button Wall Controller (Wired) Button is pressed Door closing Door at Open Mid-Stop Door stopped during the open cycle Door stopped during the close cycle Button is held (constant Door opening pressure) Operator at OPEN limit Operator at CLOSE limit Door opening Open is pressed Door closing myQ® Smart Facility Access Close is pressed Door at Open Mid-Stop Door stopped during open or close cycle Operator at OPEN limit Operator at CLOSE limit Door opening Door closing Door at Open Mid-Stop Door stopped during open or close cycle RESPONSE No change in state (Recycle TTC) Door opens to the OPEN limit or Mid-Stop and activates TTC No change in state Door will auto reverse to OPEN limit or MidStop and activates TTC Door opens to the OPEN limit and activates TTC Door opens to the OPEN limit or Mid-Stop and activates TTC Door closes to the CLOSE limit No change in state No change in state No change in state Door closes to the CLOSE limit Door closes to the CLOSE limit No change in state (Recycle TTC) No change in state Door stops and activates TTC Door stops and activates TTC No change in state (Recycle TTC) No change in state (Recycle TTC) Door closes to the CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC Door stops and activates TTC Door will auto reverse to OPEN limit or MidStop and activates TTC Door opens to the OPEN limit and activates TTC Door closes to the CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC Door closes to the CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC Door stops and activates TTC Door will auto reverse to OPEN limit or MidStop and activates TTC Door opens to the OPEN limit Door closes to the CLOSE limit Door opens to the OPEN limit or Mid-Stop and activates TTC No change in state or Mid-Stop and activates TTC No change in state (Recycle TTC) Door opens to the OPEN limit or Mid-Stop (activates TTC) No change in state Door will auto reverse to OPEN limit or MidStop and activates TTC Door opens to the OPEN limit and activates TTC Door opens to the OPEN limit or Mid-Stop and activates TTC Door closes to the CLOSE limit No change in state No change in state No change in state Door closes to the CLOSE limit Door closes to the CLOSE limit 43 Programming (continued) Programmable Inputs · The controller contains three programmable inputs that may be configured to accept several different input devices. · Navigate through the menus to SYSTEM SETTINGS (enter password) to PROG INPUTS. Select INP1, INP2 or INP3. · Select a Function from the list. Press Enter. · Select a Polarity from the list. Press Enter. Function Options: · Non-monitored Eye/Edge Input · Car Dealer Input (typically loop detector, treadle hose, card reader) · Timer Defeat · All Fly (previously known as FSTS) Radio The controller has a built in Security+ 2.0® radio receiver, that can program up to 90 remote control devices and up to 30 keyless entry devices. Programming Remote Controls and myQ® Devices 1. Select SYSTEM SETTINGS from the main menu (enter passcode.) 2. Select CONNECTIVITY. 3. Select one of: Learn myQ Devices, Wi-Fi, or Remotes. 4. The operator will indicate the selected accessory is being learned. 5. Repeat as needed for any other devices and remotes. Erasing Programmed Devices 1. Select Connectivity from the main menu (enter passcode). 2. Select Erase. 3. Select the type of device to be erased or select "Erase all". 4. Press "UP" button to erase the selected device. 5. Display will confirm erasing selected device. Reset Defaults Parameter Operating Mode Frequency Profile Open Frequency Close Frequency Limits Timer to Close Delay to Open Delay to Close INP1 Function INP1 Logic INP2 Function INP2 Logic INP3 Function INP3 Logic Eye/Edge Default Value B2 Maximum Speed 10HZ 10HZ Must Relearn Limits 120 sec. 0 0 No Function N.O. No Function N.O. No Function N.O. Unlearned Service Counter Interval 5000 Service Counter Value Is not reset Absolute Cycle Counter Is not reset NOTICE: This device complies with part 15 of the FCC rules and Innovation, Science and Economic Development Canada licenseexempt RSSs. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. This device must be installed to ensure a minimum 20 cm (8 in.) distance is maintained between users/bystanders and device. This device has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules and Industry Canada ICES standard. These limits are designed to provide reasonable protection against harmful interference in a commercial installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: · Reorient or relocate the receiving antenna. · Increase the separation between the equipment and receiver. · Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. · Consult the dealer or an experienced radio/TV technician for help. 44 Programming (continued) myQ® Smart Facility Access One Platform allows you to manage access for unlimited facilities, users and vehicles. The myQ® Smart Facility Access allows you to control all your access points in the facility from the myQ® website application from anywhere. Monitor and control your vehicular access doors, gated entry locations, and even dock positions from a universal platform. myQ® technology uses a 900Mhz signal or a Wi-Fi connection to communicate securely from your connected devices to myQ® enabled accessories or directly to a Wi-Fi network. Setup a myQ® Smart Facility Access Account NOTE: If you have an existing myQ® account, your myQ® BusinessTM account will have the same password. We have made the account setup process easier than ever. It's completely self-service. Go to Account.myQ.com and begin the process. 1. Select Country, Name, email, and create password. 2. Verify the email with a 4-digit code. 3. Select property manager or partner. 4. To create a myQ® Facility, select property type, property name, property manager information. You are now ready to access your dashboard and all other myQ® features. 5. Set up the Facility and add users and groups to provide access to the Facility (refer to the available Help in myQ® BusinessTM). 6. You will get a welcome email from LiftMaster. Accept the invitation and register or login to your account. 7. Set up the Facility and add users & groups to provide access to the Facility (refer to the available Help in myQ® BusinessTM). 8. Follow on-screen prompts to get your Variable Speed Door Operator and additional devices connected. Provisioning Wi-Fi Follow the below instructions to pair the operator: 1. Press the "STOP/ENTER" and "DOWN" buttons at the same time for 3+ seconds to enter the operator menu. 2. Scroll down to "SYSTEM SETTINGS" with the "UP" and "DOWN" buttons and press "ENTER". You will be prompted to enter the password for the operator. 3. Enter 326 as the password. 4. Scroll down to "CONNECTIVITY" and press "ENTER". 5. Press "ENTER" again to select "CONNECTIVITY LEARN". 6. Scroll down to "LEARN WIFI" and press "ENTER". The operator will now be in Learn Mode. 7. Using your own device (laptop, tablet, or smart phone) go to your device's Wi-Fi setting and search for the Wi-Fi network called myQ-nnn where the nnn is the last 3 serial numbers of your controller. Select that Wi-Fi network. 8. Once your device (laptop, tablet, or smart phone) is connected to the operator, go to setup.myqdevice.com on your device and follow the instructions. 45 Auxiliary Relays Accessory Kit ([XXXXX]) Configure the Relay Adapter This operator allows for the programming of a single mid-stop door position. To set the open mid-stop position: 1. In Programming Mode, go to Door Position => Open Mid-Stop or Close Mid-Stop. 2. Use the Up/Down buttons to move the door to the desired position. 3. Select Save = Enter To erase the mid-stop, select Erase Open Mid-Stop or Erase Close-Mid Stop option, then select Save=Enter. NOTE: Restoring defaults or resetting limits will erase the mid-stop position. RELAY ADAPTER BOARD AUXILIARY RELAYS · Aux Relay Switches: Set the AUX RELAY switches as needed to obtain the desired function as shown below. · J6 Input: Communicator bus connects control board, expansion board, or relay adapter board. · J7 Input: Communicator bus connects control board, expansion board, or relay adapter board. · AUX24: Supplies +24Vdc up to 1AMP to wired accessories. RED/GREEN LIGHT FUNCTIONALITY Red light wired to AUX RELAY 1. Green light wired to AUX RELAY 2. DOOR STATE AUX RELAY 1 SWITCHES AUX RELAY 2 SWITCHES 1 OFF 2 OFF 3 OFF 1 ON 2 ON 3 ON Closed Red light OFF* Green light OFF Opening Red light ON/Flash Green light OFF Open Red light OFF Green light ON Closing Red light ON/Flash Green light OFF Defined Mid Stop N/A N/A Undefined Mid Stop Red light ON Green light OFF Timer more than 5 seconds Red light OFF Green light ON Timer less than 5 seconds Red light ON/Flash Green light OFF * For red light ON when gate is closed, set switch 1 on AUX RELAY 1 to ON. N.O. N.C. Com Com N.C. N.O. RELAY ADAPTER BOARD 46 Loop Detector Board Need better installation images this is just a reference. Loop Mode EXIT INTERRUPT SHADOW AUXILIARY SW1 SW2 ? ? ? ? ? ? ON ON Disconnect power BEFORE making electrical connections. The Loop Detector Board (model LPEXP, not provided) combined with the LOOPDETLM, provides (What functionality) functionality that is available through the auxiliary switch setting. The LPEXP and LOOPDETLM can be purchased together as a kit (LPEXPKIT). 1. Secure the Loop Detector Board (model LPEXP) to the standoffs in the DC Logic NTX cover on the motor side with the provided screws. 2. Connect the wire harness from the Loop Detector Board to the AUX Relay Board or Main Board (Need to show images). 3. Connect the loop wires to the input on the Loop Detector Board. 4. Plug in the loop detector (model LOOPDETLM). 5. Set switches on the Loop Detector Board to desired settings (Don't know the settings). 6. Activate the loop detector to validate desired functionality. 47 Troubleshooting If an error occurs, the idle screen is replaced by a screen showing the error code and a description of the error. An example error code display is shown below. Error messages originate in one of three categories: · Inverter (power faults) · Door control codes related to the motor and encoder · Option codes related to accessories used with the MC11 or MC21 controllers. Consult the Table of Error Codes below to determine the cause and corrective action. Depending on the type of error, user interaction may be required to clear the error. The error window closes when the error has been cleared/corrected. Code UI Display Text Fault Possible Causes F01 F01 CLOSE Door has moved beyond 1. End positions not correctly set LIMIT the lower end position 2. Direction of rotation incorrect 3. Brake failure/door falls F02 F02 OPEN Door has moved beyond 1. End positions not correctly set LIMIT upper end position 2. Direction of rotation incorrect 3. Brake failure F03 F03 Door has moved in the 1. Direction of rotation incorrect DIRECTION wrong direction. 2. Sagging when starting a door with high weight. F04 F04 Obstruction or operator 1. Door moved onto obstacle. If needed check force parameters. UNAUTH. fault triggered system STOP to stop 2. Encoder malfunction (e.g. encoder no longer connected) 3. Inverter has triggered stop by itself (e.g. due to temperature, internal error) 4. Inverter has triggered stop due to over voltage, missing brake chopper on imbalanced door. 5. Door cable stretch. Reset limits. F05 F05 Door did not stop on time 1. Brake sash chain disengaged. UNAUTH. MOVE while moving or made an 2. Brake worn-out. unauthorized move while 3. Stop command not transmitted standing. 4. Encoder shows ghost movement F08 F08 NO Configuration not found. 1. No stored configuration could be found in memory. (Normal for CONFIG Was reset to factory instance with new controller, and/or after certain tests with the setting. test system.) 2. The stored configuration is outdated and no longer compatible with the current software. Can occur after update to a new version. F09 F09 Ribbon cable connecting Check to ensure that the ribbon cable from the front panel to the BUTTON front panel buttons to display board is attached properly. CABLE display is not detected. F10 F10 UP FORCE UPWARD force curve is Force sensing in UPWARD direction is activated, but force curve in missing UPWARD direction is not stored. Execute force learn. F11 F11 DOWN DOWNWARD force curve Force sensing in DOWNWARD direction is activated. But force curve FORCE is missing in DOWNWARD direction is not stored. Execute force learn. F14 F14 SET End positions are not set 1. Door positions not set due to new product. LIMITS or stored. 2. Door positions lost due to total reset. F26 F26 OVER Overvoltage on the VOLT inverter board F41 F41 EYE/ Monitored Eyes/Edge EDG1 BLK Input 1 Blocked for 3 minutes or more. The controller received a message from the inverter of overvoltage. The Monitored Eyes/Edge input 1 has a device connected and sensing blocked for 3 minutes or longer. 48 Troubleshooting (continued) Code UI Display Text Fault Possible Causes F42 F42 EYE/ Monitored Eyes/Edge The Monitored Eyes/Edge input 1 was learned to the controller, but no EDG1 MIS Input 1 learned, but no longer found. longer present F43 F43 EYE/ Command to move 1. A command to move the door was received, but the Monitored EDG1 BLK door received, but Eyes/Edge input 1 is sensing blocked. Monitored Eyes/Edge 2. Door reversed during travel due to Monitored Eyes/Edge Input 1 Input 1 blocked. blocked. F44 F44 EYE/ Monitored Eyes/Edge The Monitored Eyes/Edge input 2 has a device connected and sensing EDG2 BLK Input 2 Blocked for 3 blocked for 3 minutes or longer. minutes or more. F45 F45 EYE/ Monitored Eyes/Edge The Monitored Eyes/Edge input 2 was learned to the controller, but no EDG2 MIS Input 2 learned, but no longer found. longer present F46 F46 EYE/ Command to move 1. A command to move the door was received, but the Monitored EDG2 BLK door received, but Eyes/Edge input 2 is sensing blocked. Monitored Eyes/Edge 2. Door reversed during travel due to Monitored Eyes/Edge input 2 Input 2 blocked. blocked. F47 F47 EYE/ Monitored Eyes/Edge The Monitored input 3 has a device connected and sensing blocked EDG3 BLK Input 3 Blocked for 3 for 3 minutes or longer. minutes or more. F48 F48 EYE/ Monitored Eyes/Edge The Monitored Eyes/Edge input 3 was learned to the controller, but no EDG3 MIS Input 3 learned, but no longer found. longer present F49 F49 EYE/ Command to move 1. A command to move the door was received, but the Monitored EDG3 BLK door received, but Eyes/Edge input 3 is sensing blocked. Monitored Eyes/Edge 2. Door reversed during travel due to Monitored Eyes/Edge Input 3 Input 3 blocked. blocked. F51 F51 INP1 Device triggered for A device connected to Programmable Input 1 is triggered or blocked BLOCK 3 minutes or more on for 3 minutes or longer. Input 1. F52 F52 INP1 Command to move 1. Command to move door received, but Non Monitored device CMND door received, but triggered on Input 1. device triggered on 2. Door reversed during travel due to Programmable Input 1 blocked. Programmable Input 1. F53 F53 INP2 Device triggered for A device connected to Programmable Input 2 is triggered or blocked BLOCK 3 minutes or more on for 3 minutes or longer. Input 2. F54 F54 INP2 Command to move 1. Command to move door received, but Non Monitored device CMND door received, but triggered on Input 2. device triggered on 2. Door reversed during travel due to Programmable Input 2 blocked. Programmable Input 2. F55 F55 INP3 Device triggered for A device connected to Programmable Input 3 is triggered or blocked BLOCK 3 minutes or more on for 3 minutes or longer. Input 3. F56 F56 INP3 Command to move 1. Command to move door received, but Non Monitored device CMND door received, but triggered on Input 3. device triggered on 2. Door reversed during travel due to Programmable Input 3 blocked. Programmable Input 3. F61 F61 CTM Cable Tension FAULT monitor/s triggered 1. One or both of the cable tension monitors is not connected. 2. One or both of the cable tension monitors has faulty wiring (shorted). 3. One or both of the cable tension monitors is triggered by a slack door cable. 49 Troubleshooting (continued) Code UI Display Text Fault Possible Causes F91 F91 Error in position 1. Error in communication cable. ENCODER encoder message. Door position outside of valid range. 2. Cable shorted, cut, connector disconnected. 3. Loose encoder wires connected to controller. F92 F92 Time-out error when 1. Error in communication cable. ENCODER receiving position encoder message. Message incomplete. 2. Cable shorted, cut, connector disconnected. 3. Loose encoder wires connected to controller. F93 F93 Time-out error when 1. Error in communication cable. ENCODER receiving position 2. Cable defect / not connected. encoder message. No 3. Loose encoder wires connected to controller. signals received. F96 F96 Safety chain circuit SAFETY was interrupted. CIRC 1. Check the status of all devices connected to the INTR LOCK terminals. If no devices are connected a jumper must be placed. 2. Check that the chain hoist mechanism is fully engaged. 3. Check the Data Cable connections at Control Board and Inverter Board. Ensure S+ is connected to S+ and S- is connected to S-. 4. Check the hoist switch connection to the Inverter Board. WIRELESS EDGE FAULTS Error Code Text n/a WLESS EDGE BLOK 62 F62 WLESS BLK 63 F63 WE BLE MISS 64 F64 WE BLE MISS 65 F65 WE I2C MISS 66 F66 WE I2C MISS 68 F68 WE CRIT BATT Description Edge is triggered Edge has been triggered for 3+ minutes Wireless edge lost BLE communication with open edge Wireless edge lost BLE communication with close edge Wireless edge can't communicate with the board with an open edge Wireless edge can't communicate with the board with a close edge Wireless edge battery is critical 50 Maintenance Maintenance Schedule For use with Maintenance Alert System. Check at the intervals listed in the following chart. WARNING To avoid SERIOUS personal INJURY or DEATH: · Disconnect electric power BEFORE performing ANY adjustments or maintenance. · ALL maintenance MUST be performed by a trained door systems technician. Item Procedure Every Month Every 3 Months or 5,000 Cycles Every 6 Months or 10,000 Cycles Drive Chain · Check for excessive slack. · Check and adjust as required. · Lubricate. Sprockets Check set screw tightness. Fasteners Check and tighten as required. Manual Hoist (if Check and operate. applicable) Shafts Check for wear and lubricate. LiftMaster Monitored Check alignment and Entrapment Protection functionality. Use SAE 30 Oil (Never use grease or silicone spray) · Do not lubricate motor. Motor bearings are rated for continuous operation. Inspect and service whenever a malfunction is observed or suspected. How to order repair parts: LiftMaster.com 51 Accessories ENTRAPMENT PROTECTION DEVICES (MONITORED) CPS-U - Dual-Sided Infrared Photoelectric Sensors · NEMA 1 general purpose enclosure. · Dual-sided infrared sensors. · For indoor use. · Maximum range of 30 feet (9.1 m). K41-0157-000 - HPH1 & HPH2 Cable Tension Monitor (Right) LMWEKITU - Wireless Edge Kit · [XXX] · Approved for US/CAN/MX, Puerto Rico, Columbia, Costa Rica. LMWETXU - Wireless Edge Kit · [XXX] · Approved for US/CAN/MX, Puerto Rico, Columbia, Costa Rica. K41-0156-000 - HPH1 & HPH2 Cable Tension Monitor (Left) OES-SD16 - Optical Edge System LMTBUL - Monitored Thru-Beam Photoelectric Sensors · Max Range: 90 ft. (27.4 m) · Cable Length: 10 ft. (3 m) · Operating Temperature: -40°C to 65°C (-40°F to 149°F) 16 feet (4.9 m) Sectional 2-Wire Door Edge Kit with infrared optical sensors, rubber door edge and all mounting hardware (channel sold separately). OES-SD24 - Optical Edge System · Outdoor Rating: Nema 4X · Heater: Thermostatically controlled · Input Voltage: · Sensor: Black/red wires 6.8 VDC, 20mA · Heater: Green/white wires 10-40VDC or 8-28 VAC, 4 watts max., 170mA per pair @ 24 VDC/VAC, 340mA per pair @ 12 VDC/VAC LMRRUL - Monitored Retro-Reflective Photoelectric Sensors · Max Range: 50 ft. (15.2 m) · Cable Length: 10 ft. (3 m) · Operating Temperature: -40°C to 65°C (-40°F to149°F) · Outdoor Rating: Nema 4X · Heater: Thermostatically controlled · Input Voltage: · Sensor: Black/red wires 6.8 VDC, 20mA · Heater: Green/white wires 10-40VDC or 8-28 VAC, 4 watts max., 170mA per pair @ 24 VDC/VAC, 340mA per pair @ 12 VDC/VAC CPS-UN4 - Monitored Thru-Beam Photoelectric Sensors · Heavy-duty housing for industrial applications. · NEMA 4 enclosure protects against direct spray. · Dual-sided infrared sensors. · For indoor/outdoor use. · Maximum range of 45 feet (13.7 m). CPS-RPEN4 - Monitored Retro-Reflective Photoelectric Sensors · Polarized reflector for use in applications with highly reflective surfaces. · NEMA 4X enclosure protects against direct water spray and corrosion. 24 feet (7.3 m) Sectional 2-Wire Door Edge Kit with infrared optical sensors, rubber door edge and all mounting hardware (channel sold separately). OES-RD16 - Optical Edge System 16 feet (4.9 m) Rolling 2-Wire Door Edge Kit with infrared optical sensors, rubber door edge and all mounting hardware (door channel not required). Optical Edge System (OES) · Rubber door edge is durable, flexible and easy to install. · Premium rubber can be cut to length for exact fit. · NEMA 6 rating protects against moisture and standing water. · Infrared optical sensors eliminate the need for electrical contacts. · Maximum range of 33 feet (10 m). · Sectional and rolling door edges are also available in 50 foot (15 m) bulk rolls, along with individual components for additional savings on large installation jobs. S50, L50 - Monitored Edge Sensors [XXX] CPS-EI - Edge Interface 4-Wire Monitored For use with approved 4-wire sensing edges listed on this Accessory page. ASO Monitored 4-Wire, 2-Wire Sentir Series 45.30 · Retro-reflective sensor. [XXX] · For indoor/outdoor use. · Maximum range of 50 feet (15 m). CPS-OPEN4 - Monitored Dual-Sided Photoelectric Sensors · Flexible housings maintain alignment in areas with a high propensity for sensor contact. · NEMA 4X enclosure protects against direct water spray and corrosion. · Dual-sided infrared sensors. ASO Monitored 4-Wire, 2-Wire Sentir Series 35.55 [XXX] LC36M - Monitored Light Curtain Monitored, primary entrapment protection device that forms a 3-foot cross pattern of invisible light beams for maximum personnel and property protection. · For indoor/outdoor use. · Maximum range of 45 feet (13.7 m). 52 Accessories (continued) ENTRAPMENT PROTECTION DEVICES (NONMONITORED) 65-8202 - Vehicle Detection System Pneumatic Sensing Edge Kit with exterior air switch, 2-wire coil cord and 14 foot (4.3 m) air hose. 65-5202 - Vehicle Detection System Pneumatic Sensing Edge Kit with exterior air switch, 2-wire take-up reel (20 feet [6 m] extended) and 14 foot (4.3 m) air hose. 100MAPS - Plug-In Power Supply Provides power to the LC-36A Light Curtain. NOTE: Use if main board accessory power is consumed and additional power is required. RADIO STAR1000 - Commercial Access Control Receiver Connects up to 1000 LiftMaster® remote controls. Supports suspending and unsuspending remote controls to withhold and reinstate access. 850LM - Universal Receiver Featuring Security+ 2.0® technology. Designed for both gated communities and commercial buildings to support and manage multiple access points multiple remote controls. WALL CONTROLLER DCWALLCTL Floor Level Wall Controller with LCD display. MYQ ACCESSORIES NOTE: The door operator will only support a single DCWALLCTL display 828LM - LiftMaster® Internet Gateway Enables owners of Commercial Door Operators to open and close their doors and turn on/off lights in or around their facility using a mobile device or computer from anywhere in the world. 02-101 - 1-Button Wall Controller Steel enclosure. 02-102 - 2-Button Wall Controller REMOTE CONTROLS WITH SECURITY+ AND CONNECTIVITY 811LMX - Programmable DIP Switch Single-Button Remote Control Ideal for commercial door applications requiring a large number of remotes for a common space. Approved for US/CAN/MX, Puerto Rico, Columbia, Costa Rica. 891LMMC - Programmable DIP Switch Three-Button Remote Control Includes Red, Yellow and Green markings which Indicates Open, Close, Stop. Approved for US/CAN/MX, Puerto Rico, Columbia, Costa Rica. Steel enclosure. 02-103L - 3-Button Wall Controller Steel enclosure with Maintenance Alert System. 02-110 - Key Wall Controller Indoor flush mount, NEMA 1 with Stop button. 893LMMC - Programmable DIP Switch Three-Button Remote Control 02-401M - 1-Button Wall Controller Approved for US/CAN/MX, Puerto Rico, Columbia, Costa Rica. 877LM - Wireless Keypad Indoor/outdoor surface mount, single button to activate opening one commercial door. Able to be programmed with temporary access codes for visitors or delivery personnel. 53