UniStream 15.6" Built-in: PLC Controller HMI I/Os by Unitronics


File Info : application/pdf, 23 Pages, 1.58MB

PDF preview unavailable. Download the PDF instead.

UG USx-B1 TR22 T24
User Guide

UniStream®
Built-in

US5-B5-B1, US5-B10-B1, US5-B5-TR22, US5-B10-TR22, US5-B5-T24, US5-B10-T24, US5-C5-B1, US5-C10-B1, US5-C5-TR22, US5-C10-TR22, US5-C5-T24, US5-C10-T24
US7-B5-B1, US7-B10-B1, US7-B5-TR22, US7-B10-TR22, US7-B5-T24, US7-B10-T24, US7-C5-B1, US7-C10-B1, US7-C5-TR22, US7-C10-TR22, US7-C5-T24, US7-C10-T24

US10-B5-B1, US10-B10-B1, US10-B5-TR22, US10-B10-TR22, US10-B5-T24, US10-B10-T24, US10-C5-B1, US10-C10-B1, US10-C5-TR22, US10-C10-TR22, US10-C5-T24, US10-C10-T24

This guide provides basic installation information for specific UniStream® models with built-in I/O. Technical specifications may be downloaded from the Unitronics website.

General Features

Unitronics' UniStream® Built-in series are PLC+HMI All-in-One programmable controllers that comprise a built-in CPU, an HMI panel, and built-in I/Os.

The series is available in two versions: UniStream Built-in and UniStream Built-in Pro.

Note that a model number that includes:

· B5/C5 refers to UniStream Built-in

· B10/C10 refers to UniStream Built-in Pro. These models offer additional features, detailed below.

HMI

 Resistive Color Touch-screens

 Rich graphic library for HMI design

Power Features

 Built-in Trends and Gauges, auto-tuned PID, data tables, data sampling, and Recipes  UniAppsTM: Access & edit data, monitor, troubleshoot & debug and more ­ via HMI or remotely via
VNC  Security: Multi-level password protection  Alarms: Built-in system, ANSI/ISA standards

I/O Options

 Built-in I/O configuration, varies according to model  Local I/O via UAG-CX series I/O expansion adapters and standard UniStream Uni-I/OTM modules  Remote I/O using UniStream Remote I/O or via EX-RC1

COM Options
COM Protocols

 Built-in ports: 1 Ethernet, 1 USB host, 1 Mini-B USB device port  Serial and CANbus ports may be added via UAC-CX modules
 Fieldbus: CANopen, CAN Layer2, MODBUS, EtherNetIP and more. Implement any serial RS232/485, TCP/IP, or CANbus third-party protocols via Message Composer
 Advanced: SNMP Agent/Trap, e-mail, SMS, modems, GPRS/GSM, VNC Client, FTP Server/Client

Programming Software

All-in-One software for hardware configuration, communications, and HMI /PLC applications, available as a free download from Unitronics.

Unitronics

1

User Guide

Comparison table

Feature System Memory

Audio Jack

Video/RSTP Support

Web Server

SQL Client

Before You Begin Before installing the device, the user must:
 Read and understand this document.  Verify the Kit Contents.

B5/C5 3GB No No No No

B10/C10 (Pro) 6GB Yes Yes Yes Yes

Alert Symbols and General Restrictions When any of the following symbols appear, read the associated information carefully.

Symbol

Meaning

Description

Danger

The identified danger causes physical and property damage.

Warning

The identified danger could cause physical and property damage.

Caution

Caution

Use caution.

 All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples.

 Please dispose of this product according to local and national standards and regulations.

 This product should be installed only by qualified personnel.

 Failure to comply with appropriate safety guidelines can cause severe injury or property damage.

 Do not attempt to use this device with parameters that exceed permissible levels.

 Do not connect/disconnect the device when power is on.

Environmental Considerations
 Ventilation: 10mm space is required between the device top/bottom edges and the enclosure's walls
 Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance with the standards and limitations given in the product's technical specification sheet.
 Do not place in water or let water leak onto the unit.  Do not allow debris to fall inside the unit during installation.  Install at maximum distance from high-voltage cables and power equipment.

2

Unitronics

UniStream® Built-in
UL Compliance
The following section is relevant to Unitronics' products that are listed with the UL.
The following models are UL listed for Hazardous Locations: US5-B5-B1, US5-B10-B1, US7-B5-B1 and US7-B10-B1
The following models are UL listed for Ordinary Location:
 USL followed by -, followed by 050 or 070 or 101, followed by B05  US followed by 5 or 7 or 10, followed by -, followed by B5 or B10 or C5 or C10, followed by -,
followed by B1 or TR22 or T24 or RA28 or TA30 or R38 or T42 Models from series US5, US7 and US10 that include "T10" or "T5" in the model name are suitable for mounting on the flat surface of Type 4X enclosure. For examples: US7-T10-B1, US7-T5-R38, US5-T10RA22 and US5-T5-T42.
UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on the flat surface of Type 1 or 4X enclosures
UL Ratings, Programmable Controllers for Use in Hazardous Locations, Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Nonhazardous locations only.  Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having jurisdiction.  WARNING--Explosion Hazard--substitution of components may impair suitability for Class I, Division 2.  WARNING ­ EXPLOSION HAZARD ­ Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.  WARNING ­ Exposure to some chemicals may degrade the sealing properties of material used in Relays.  This equipment must be installed using wiring methods as required for Class I, Division 2 as per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to meet the UL Haz Loc standard, panel-mount this device on the flat surface of Type 1 or Type 4X enclosures.
Communication and Removable Memory Storage
When products comprise either USB communication port, SD card slot, or both, neither the SD card slot nor the USB port are intended to be permanently connected, while the USB port is intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the battery unless the power has been switched off, or the area is known to be non-hazardous.
Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data when changing the battery while the power is switched off. Date and time information will also need to be reset after the procedure.

Unitronics

3

User Guide
UL des zones ordinaires:
Pour respecter la norme UL des zones ordinaires, monter l'appareil sur une surface plane de type de protection 1 ou 4X
Certification UL des automates programmables, pour une utilisation en environnement à risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention  Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et D, ou dans Non-dangereux endroits seulement.
 Le câblage des entrées/sorties doit être en accord avec les méthodes de câblage selon la Classe I, Division 2 et en accord avec l'autorité compétente.
 AVERTISSEMENT: Risque d'Explosion ­ Le remplacement de certains composants rend caduque la certification du produit selon la Classe I, Division 2.
 AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est reconnue pour être non dangereuse.
 AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés des matériaux utilisés pour l'étanchéité dans les relais.
 Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I, Division 2 NEC et /ou CEC.
Montage de l'écran:
Pour les automates programmables qui peuvent aussi être monté sur l'écran, pour pouvoir être au standard UL, l'écran doit être monté dans un coffret avec une surface plane de type 1 ou de type 4X.
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les deux, ni le port SD, ni le port USB ne sont censés être utilisés en permanence, tandis que l'USB est destiné à la programmation uniquement.
Retrait / Remplacement de la batterie
Lorsqu'un produit a été installé avec une batterie, retirez et remplacez la batterie seulement si l'alimentation est éteinte ou si l'environnement n'est pas dangereux.
Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les informations sur la date et l'heure devront également être réinitialisées après la procedure.

Kit Contents
 1 PLC+HMI controller  4,8 mounting brackets (US5/US7, US10)  1 panel mounting seal  2 panel supports (US7/US10 only)

 1 power terminal block  2 I/O terminal blocks (provided only with models
comprising built-in I/Os)  1 Battery

4

Unitronics

Product Diagram

UniStream® Built-in

1

Screen

Protection

2

Battery Cover

3

Power Supply

Input

4

microSD Slot

5

USB Host port

6

Ethernet port

7

USB Device

8

I/O Expansion

Jack

9

Audio Jack

10 Built-in I/O
11 Uni-COMTM CX Module Jack

Front and Rear View
A plastic sheet attached to the screen for protection. Remove it during installation of the HMI Panel.
The battery is supplied with the unit, but must be installed by the user.
Connection point for the controller power source. Connect the Terminal Block supplied with the kit to the end of the power cable.
Supports standard microSD cards.
Provides the interface for external USB devices.
Supports high-speed Ethernet communications.
Use for application download and direct PC-UniStream communication.
Connection point for an I/O Expansion Port. Ports are supplied as part of I/O Expansion Model Kits. Kits are available by separate order. Note that UniStream® Built-in is compatible only with adapters from the series UAG-CX.
Pro models only. This 3.5mm Audio jack enables you to connect external audio equipment.
Model-dependent. Present in models with built-in I/O configurations.
Connection point for up to 3 stack-on modules. These are available by separate order.

Installation Space Considerations Allocate space for:
 the controller  any modules that will be installed  access to ports, jacks, and the microSD card slot For exact dimensions, please refer to the Mechanical Dimensions shown below.

Unitronics

5

Mechanical Dimensions

UniStream 5"

User Guide

UniStream 7"

6

Unitronics

UniStream 10.1"

UniStream® Built-in

NOTE Allow space for modules to be snapped onto the back of the controller, if required by your application. Modules are available by separate order.

Panel Mounting

NOTE

 Mounting panel thickness must be less or equal to 5mm (0.2").  Ensure that the space considerations are met.

1. Prepare a panel cut-out according to the dimensions as shown in the previous section. 2. Slide the controller into the cut-out, ensuring that the Panel Mounting Seal is in place as shown
below. 3. Push the mounting brackets into their slots on the sides of the panel as shown below. 4. Tighten the bracket screws against the panel. Hold the brackets securely against the unit while
tightening the screws. The torque required is 0.35 N·m (3.1 in-lb). When properly mounted, the panel is squarely situated in the panel cut-out as shown below.

Caution

 Do not apply torque exceeding 0.35 N·m (3.1 in-lb) of torque to tighten the bracket screws. Using excessive force to tighten the screw can damage this product.

UniStream 5"

Unitronics

7

UniStream 7"

User Guide

UniStream 10.1"

\
Battery: Back-up, First Use, Installation, and Replacement
Back-up
In order to preserve back-up values for RTC and system data in the event of power off, the battery must be connected.
First Use
The battery is protected by a removable cover on the side of the controller. The battery is supplied installed inside the unit, with a plastic tab preventing contact which must be removed by the user.

8

Unitronics

UniStream® Built-in
Battery Installation and Replacement
 Use proper precautions to prevent Electro-Static Discharge (ESD) while servicing the battery.
Caution  To preserve back-up values for RTC and system data during battery replacement, the controller must be powered.
 Note that disconnecting the battery halts the preservation of back-up values and causes them to be deleted.
1. Remove the battery cover from the controller as shown in the accompanying figure: - Press the tab on the module to disengage it. - Slide it up to remove it.
2. If you are replacing the battery, remove the battery from its slot on the side of the controller.
3. Insert the battery, ensuring that the polarity is aligned with the polarity marking as shown in the accompanying figure.
4. Replace the battery cover. 5. Dispose of the used battery according to local and
national standards and regulations.

Panel Support Installation
1. Insert the Panel Support tabs into their location. Note that the exact location varies according to the panel model.
2. Pull on the Panel Support until it locks (clicks) into it's place.

Wiring
 This equipment is designed to operate only at SELV/PELV/Class 2/Limited Power environments.  All power supplies in the system must include double insulation. Power supply outputs must be
rated as SELV/PELV/Class 2/Limited Power.  Do not connect either the `Neutral' or `Line' signal of the 110/220VAC to device's 0V point.  Do not touch live wires.  All wiring activities should be performed while power is OFF.  Use over-current protection, such as a fuse or circuit breaker, to avoid excessive currents into
the power supply connection point.  Unused points should not be connected (unless otherwise specified). Ignoring this directive may
damage the device.  Double-check all wiring before turning on the power supply.

Unitronics

9

User Guide

Caution

 To avoid damaging the wire, use a maximum torque of 0.5 N·m (4.4 in-lb).  Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to
break.  Install at maximum distance from high-voltage cables and power equipment.

Wiring Procedure Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm2 ­3.31 mm2 )

1. Strip the wire to a length of 7±0.5mm (0.250­0.300 inches). 2. Unscrew the terminal to its widest position before inserting a wire. 3. Insert the wire completely into the terminal to ensure a proper connection. 4. Tighten enough to keep the wire from pulling free.

Wiring Guidelines In order to ensure that the device will operate properly and to avoid electromagnetic interference:  Use a metal cabinet. Make sure the cabinet and its doors are properly earthed.  Use wires that are properly sized for the load.  Use shielded twisted pair cables for wiring High Speed and Analog I/O signals. In either case, do not use the cable shield as a signal common / return path.  Route each I/O signal with its own dedicated common wire. Connect common wires at their respective common (CM) points at the controller.  Individually connect each 0V point and each common (CM) point in the system to the power supply 0V terminal, unless otherwise specified.  Individually connect each functional ground point ( ) to the earth of the system (preferably to the metal cabinet chassis). Use the shortest and thickest wires possible: less than 1m (3.3') in length, minimum thickness 14 AWG (2 mm2).  Connect the power supply 0V to the earth of the system.
 Earthing the cables' shield:  Connect the cable shield to the earth of the system (preferably to the metal cabinet chassis). Note that the shield must be connected only at one end of the cable; it is recommended to earth the shield at the PLC-side.  Keep shield connections as short as possible.  Ensure shield continuity when extending shielded cables.
NOTE For detailed information, refer to the document System Wiring Guidelines, located in the Technical Library in the Unitronics' website.

Wiring the Power Supply The controller requires an external power supply.
 In the event of voltage fluctuations or non-conformity to voltage power supply specifications, connect the device to a regulated power supply.
Connect the +V and 0V terminals as shown in the accompanying figure.

10

Unitronics

Connecting Ports  Ethernet
 USB Device
 USB Host
Connecting Audio  Audio-Out

UniStream® Built-in

CAT-5e shielded cable with RJ45 connector Use the proprietary programming cable supplied with the device Standard USB cable with Type-A plug

Use 3.5mm stereo audio plug with shielded audio cable Note that only Pro models support this feature.
Audio Pinout

1

Headphone Left Out (Tip)

2

Headphone Right Out (Ring)

3

Ground (Ring)

4

Don't connect (Sleeve)

Note that below, the letters "xx" that is used in the model numbers means that the section refers both to B5/C5 and B10/C10 models.

US5-xx-TR22, US5-xx-T24 US7-xx-TR22, US7-xx-T24 US10-xx-TR22, US10-xx-T24 I/O Connection Points
The IOs for these models are arranged in two groups of fifteen points each, as shown in the figures to the right.
Top group Input connection points
Bottom group Output connection points
The function of certain I/Os may be adapted via wiring and software settings.

US5-xx-TR22, US7-xx-TR22, US10-xx-TR22 US5-xx-T24, US7-xx-T24, US10-xx-T24

Wiring the Digital Inputs
All 10 digital inputs share the common point CM0. The digital inputs may be wired together as sink or source.

Input wiring, sink

Input wiring, source

NOTE Use sink input wiring to connect a sourcing (pnp) device. Use source input wiring to connect a sinking (npn) device.

Unitronics

11

User Guide

Wiring the Analog Inputs
Both inputs share the common point CM1.

NOTE

 The inputs are not isolated.  Each input offers two modes: voltage or current. You can set each input independently.  The mode is determined by the hardware configuration within the software application.  Note that if, for example, you wire the input to current, you must also set it to current in the software application.

Voltage

Differential

Single-ended

Current

2-wire

3-wire

4-wire

12

Unitronics

UniStream® Built-in
Wiring the Relay Outputs (US5-xx-TR22, US7-xx-TR22, US10-xx-TR22)  To avoid risk of fire or property damage, always use a limited current source or connect a current limiting device in series with the relay contacts
The relay outputs are arranged in two isolated groups: O0-O3 share the common return CM2. O4-O7 share the common return CM3.
Increasing Contact Life Span To increase the life span of the relay contacts and protect the controller from potential damage by reverse EMF, connect:  a clamping diode in parallel with each inductive DC load,  a RC snubber circuit in parallel with each inductive AC load

Wiring the Sink Transistor Outputs (US5-xx-TR22, US7-xx-TR22, US10-xx-TR22)  Connect a current limiting device in series with outputs O8 and O9. These outputs are not short-circuit protected.
 Outputs O8 and O9 can independently be configured as either normal digital outputs or as high speed PWM outputs.
 Outputs O8 and O9 share the common point CM4.

Normal Transistor Output

High Speed PWM Output

Unitronics

13

Wiring the Source Transistor Outputs (US5-xx-T24, US7-xx-T24, US10-xx-T24)
Output's power supply
The use of any of the outputs requires an external 24VDC power supply as shown in the accompanying figure.
Outputs Connect the +VO and 0VO terminals as shown in the accompanying figure.
O0-O11 share common return 0VO.

User Guide

Installing Uni-I/OTM & Uni-COMTM Modules Refer to the Installation Guides provided with these modules.
 Turn off system power before connecting or disconnecting any modules or devices.  Use proper precautions to prevent Electro-Static Discharge (ESD).
Uninstalling the Controller
1. Disconnect the power supply. 2. Remove all wiring and disconnect any installed devices according to the device's installation guide. 3. Unscrew and remove the mounting brackets, taking care to support the device to prevent it from
falling during this procedure.

14

Unitronics

UniStream® Built-in

UniStream® Built-in
Technical Specifications
US5-B5-B1, US5-B10-B1, US5-B5-TR22, US5-B10-TR22, US5-B5-T24, US5-B10-T24, US5-C5-B1, US5-C10-B1, US5-C5-TR22, US5-C10-TR22, US5-C5-T24, US5-C10-T24
US7-B5-B1, US7-B10-B1, US7-B5-TR22, US7-B10-TR22, US7-B5-T24, US7-B10-T24, US7-C5-B1, US7-C10-B1, US7-C5-TR22, US7-C10-TR22, US7-C5-T24, US7-C10-T24
US10-B5-B1, US10-B10-B1, US10-B5-TR22, US10-B10-TR22, US10-B5-T24, US10-B10-T24, US10-C5-B1, US10-C10-B1, US10-C5-TR22, US10-C10-TR22, US10-C5-T24, US10-C10-T24

Unitronics' UniStream® Built-in series are PLC+HMI All-in-One programmable controllers that comprise built-in HMI and built-in I/Os.
UniStream connects directly to UniCloud, Unitronics' IIoT cloud platform using built-in UniCloud connectivity. More information about UniCloud is available at www.unitronics.cloud.

Model numbers in this document

US 5 - B 5 - B1

B1 TR22 T24

· No built-in I/Os
· 10 x Digital inputs, 24VDC, sink/source · 2 x Analog inputs, 0÷10V / 0÷20mA, 12 bits · 2 x Transistor outputs, npn,
including 2 High speed PWM output channels · 8 x Relay outputs
· 10 x Digital inputs, 24VDC, sink/source · 2 x Analog inputs, 0÷10V / 0÷20mA, 12 bits · 12 x Transistor outputs, pnp,
including 2 PWM output channels

5

Standard

10

Pro, offers additional features, detailed below

B

With UniCloud enabled functionality

C

With built-in 5 years UniCloud start-up subscription with no additional payment required for this period.

5

5" 800x480 (WVGA) display

7

7" 800x480 (WVGA) display

10

10.1" 1024x600 (WSVGA) display

Installation Guides are available in the Unitronics Technical Library at www.unitronicsplc.com.

Unitronics

15

Power Supply

Input voltage

Permissible range

Max.

US5

current

consumption US7

US10

Isolation

USx-xx-B1
12VDC or 24VDC
10.2VDC to 28.8VDC
0.7A@12VDC 0.4A@24VDC
0.79A@12VDC 0.49A@24VDC 0.85A@12VDC 0.52A@24VDC None

USx-xx-TR22 24VDC 20.4VDC to 28.8VDC 0.44A@24VDC
0.53A@24VDC
0.56A@24VDC

User Guide
USx-xx-T24 24VDC 20.4VDC to 28.8VDC 0.4A@24VDC
0.49A@24VDC
0.52A@24VDC

Display LCD type Backlight type
Luminous intensity (brightness) Backlight longevity
(1)
Resolution (pixels)
Size Viewing area
Color support Surface treatment Touch screen
Actuation force (min)

UniStream 5" TFT
White LED
Typically 350 nits (cd/m2), at 25°C 30k hours

UniStream 7"
Typically 400 nits (cd/m2), at 25°C

800 x 480 (WVGA)

5"

7"

Width x Height (mm) 108 x 64.8
65,536 (16bit)

Width x Height (mm) 154.08 x 85.92

Anti-glare Resistive Analog

> 80 g (0.176 lb)

UniStream 10.1"
Typically 300 nits (cd/m2), at 25°C
1024 x 600 (WSVGA) 10.1" Width x Height (mm) 222.72 x 125.28

General
I/O support Built-in I/O Local I/O expansion
Remote I/O Communication ports
Built-in COM ports Add-on Ports

Up to 2,048 I/O points According to model To add local I/Os, use UAG-CX I/O Expansion Adapters (2). These adapters provide the connection point for standard UniStream Uni-I/OTM modules. You can connect up to 80 I/O modules to a single controller using these adapters. Up to 8 UniStream Remote I/O Adapters (URB)
Specifications are provided below in the section Communications
Add up to 3 ports to a single controller using Uni-COMTM UAC-CX Modules (3).

16

Unitronics

Internal memory
Ladder memory External memory Bit operation Battery

UniStream® Built-in

Standard (B5/C5) RAM: 512MB ROM: 3GB system memory
1GB user memory

Pro (B10/C10) RAM: 1GB ROM: 6GB system memory
2GB user memory

1 MB

microSD or microSDHC card Size: up to 32GB, Data Speed: up to 200Mbps

0.13 µs

Model: 3V CR2032 Lithium battery (4) Battery lifetime: 4 years typical, at 25°C Battery Low detection and indication (via the HMI and via System Tag).

Audio (Pro B10/C10 models only)

Bit Rate Audio compatibility Interface
Impedance Isolation

192kbps Stereo MP3 files 3.5mm Audio-out jack - use shielded audio cable of up to 3 m (9.84 ft) 16, 32 None

Video (Pro B10/C10 models only)

Supported Formats

MPEG-4 Visual , AVC/H.264

Communication (Built-in Ports)

Ethernet port Number of ports Port type Auto crossover Auto negotiation Isolation voltage Cable
USB device (5) Number of ports Port type Data rate Isolation Cable
USB host Number of ports Port type Data rate

1 10/100 Base-T (RJ45) Yes Yes 500VAC for 1 minute Shielded CAT5e cable, up to 100 m (328 ft)
1 Mini-B USB 2.0 (480Mbps) None USB 2.0 compliant; < 3 m (9.84 ft)
1 Type A USB 2.0 (480Mbps)

Unitronics

17

Isolation
Cable
Over current protection

None USB 2.0 compliant; < 3 m (9.84 ft) Yes

Digital Inputs Number of inputs Type Isolation voltage
Input to bus Input to input Nominal voltage Input voltage Sink/Source
Nominal impedance Filter

10 Sink or Source
500VAC for 1 minute None 24VDC @ 6mA
On state: 15-30VDC, 4mA min. Off state: 0-5VDC, 1mA max. 4k 6ms typical

User Guide

Analog Inputs Number of inputs
Input range (6) (7)
Absolute maximum rating Isolation Conversion method Resolution Accuracy (25°C / -20°C to 55°C) Input impedance Noise rejection Step response (9) (0 to 100% of final value)

2

Input Type

Nominal Values

Over-range Values *

0 ÷ 10VDC

0  Vin  10VDC

10 < Vin  10.15VDC

0 ÷ 20mA

0  in  20mA

20 < in  20.3mA

* Overflow (8) is declared when an input value exceeds the Over-range boundary.

±30V (Voltage), ±30mA (Current)

None Successive approximation 12 bits ±0.3% / ±0.9% of full scale

541k (Voltage), 248 (Current) 10Hz, 50Hz, 60Hz, 400Hz

Smoothing

Noise Rejection Frequency

None Weak Medium Strong

400Hz 2.7ms 10.2ms 20.2ms 40.2ms

60Hz 16.86ms 66.86ms 133.53ms 266.86ms

50Hz 20.2ms 80.2ms 160.2ms 320.2ms

10Hz 100.2ms 400.2ms 800.2ms 1600.2ms

18

Unitronics

Update time (9)
Operational signal range (signal + common mode) Cable Diagnostics (8)

Noise Rejection Frequency

Update Time

400Hz

5ms

60Hz

4.17ms

50Hz

5ms

10Hz

10ms

Voltage mode ­ AIx: -1V ÷ 10.5V ; CM1: -1V ÷ 0.5V
Current mode ­ AIx: -1V ÷ 5.5V ; CM1: -1V ÷ 0.5V (x=0 or 1)

Shielded twisted pair

Analog input overflow

Relay Outputs (USx-xx-TR22)

Number of outputs 8 (O0 to O7)

Output type

Relay, SPST-NO (Form A)

Isolation groups

Two groups of 4 outputs each

Isolation voltage Group to bus Group to group Output to output within group
Current
Voltage Minimum load Switching time Short-circuit protection Life expectancy (10)

1,500VAC for 1 minute 1,500VAC for 1 minute None
2A maximum per output (Resistive load) 250VAC / 30VDC maximum 1mA, 5VDC 10ms maximum None
100k operations at maximum load

Sink Transistor Outputs (USx-xx-TR22)

Number of outputs Output type Isolation
Output to bus Output to output Current Voltage
On state voltage drop

2 (O8 and O9) Transistor, Sink
1,500VAC for 1 minute None 50mA max. per output Nominal: 24VDC Range: 3.5V to 28.8VDC 1V max

Unitronics

UniStream® Built-in 19

Off state leakage current Switching times
High speed outputs PWM Frequency
Cable

10µA max
Turn-on: 1.6s max. )4k load, 24V) Turn-off: 13.4s max. )4k load, 24V)
0.3Hz min. 30kHz max. )4k load( Shielded twisted pair

Source Transistor Outputs (USx-xx-T24)

Number of outputs 12

Output type

Transistor, Source (pnp)

Isolation voltage

Output to bus

500VAC for 1 minute

Output to output None

Outputs power supply to bus
Outputs power supply to output
Current

500VAC for 1 minute None 0.5A maximum per output

Voltage

See Source Transistor Outputs Power Supply specification below

ON state voltage drop

0.5V maximum

OFF state leakage current

10µA maximum

Switching times

Turn-on: 80s maximum, Turn-off: 155s maximum (Load resistance < 4k(

PWM Frequency (11)

O0, O1: 3kHz max. (Load resistance < 4k)

Short-circuit

Yes

protection

Source Transistor Outputs Power Supply (USx-xx-T24)

Nominal operating voltage

24VDC

Operating voltage 20.4 ­ 28.8VDC

Maximum current consumption

30mA@24VDC Current consumption does not include load current

Environmental Protection
Operating temperature

Front face : IP66, NEMA 4X Rear side: IP20, NEMA1 -20°C to 55°C (-4°F to 131°F)

20

User Guide Unitronics

UniStream® Built-in

Storage temperature
Relative Humidity (RH)
Operating Altitude
Shock
Vibration

-30°C to 70°C (-22°F to 158°F)
5% to 95% (non-condensing)
2,000 m (6,562 ft) IEC 60068-2-27, 15G, 11ms duration IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration

Dimensions
US5-xx-B1 US5-xx-TR22 US5-xx-T24 US7-xx-B1 US7-xx-TR22 US7-xx-T24 US10-xx-B1 US10-xx-TR22 US10-xx-T24

Weight 0.31 Kg (0.68 lb) 0.37 Kg (0.81 lb) 0.35 Kg (0.77 lb) 0.62 Kg (1.36 lb) 0.68 Kg (1.5 lb) 0.68 Kg (1.5 lb) 1.02 Kg (2.25 lb) 1.08 Kg (2.38 lb) 1.08 Kg (2.38 lb)

Size Refer to the images on page 7
Refer to the images on page 8
Refer to the images on page 8

UniStream 5"

Unitronics

21

UniStream 7"

User Guide

UniStream 10.1"

22

Unitronics

UniStream® Built-in
Notes:
1. The HMI panel's backlight longevity is the typical operating time after which the brightness drops to 50% of its original level.
2. UAG-CX Expansion Adapter Kits comprise a Base unit, an End unit, and a connecting cable. You plug the Base Unit into the controller's I/O Expansion Jack and connect standard UniStream UniI/OTM modules. For more information, refer to the product's installation guide and technical specifications.
3. Uni-COMTM CX modules plug directly into the Uni-COMTM CX Module Jack on the back of the controller. UAC-CX modules may be installed in the following configurations: - If a module comprising a serial port is snapped directly into to the back of UniStream, it may be followed only by another serial module, for a total of 2. - If your configuration includes a CANbus module, it must be snapped directly to the back of UniStream. The CANbus module may be followed by up to two serial modules, for a total of 3. For more information, refer to the product's installation guide and technical specifications.
4. When replacing the unit's battery, make sure that the new one has environmental specifications that are similar or better than the one specified in this document.
5. The USB device port is used to connect the device to a PC.
6. The 4-20mA input option is implemented using 0-20mA input range.
7. The analog inputs measure values that are slightly higher than the nominal input range (Input Over-range).
Note that when the input overflow occurs, it is indicated in the corresponding I/O Status tag while the input value is registered as the maximum permissible value. For example, if the specified input range is 0 ÷ 10V, the Over-range values can reach up to 10.15V, and any input voltage higher than that will still register as 10.15V while the Overflow system tag is turned on.
8. The diagnostics results are indicated in the system tags and can be observed through the UniAppsTM or the online state of the UniLogicTM.
9. Step response and update time are independent of the number of channels that are used.
10. Life expectancy of the relay contacts depends on the application that they are used in. The product's installation guide provides procedures for using the contacts with long cables or with inductive loads.
11. Outputs O0 and O1 can be configured as either normal digital outputs or as PWM outputs. PWM outputs specifications apply only when outputs are configured as PWM outputs.

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
UG_US5_7_10-Bx-B1_TR22_T24.pdf 10/22