PORTABLE AIR CONDITIONER (Local Air Conditioner)

Owner's Manual & Installation Manual

IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.

Safety Precautions

To prevent death or injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause death, harm or damage.

! WARNING This symbol indicates the possibility of personnel injury or loss of life.

! CAUTION This symbol indicates the possibility of property damage or serious consequences.

CAUTION

Note about Fluorinated Gasses (Not applicable to the unit using R290 Refrigerant)

  1. Fluorinated greenhouse gases are contained in hermetically sealed equipment. For specific information on the type, the amount and the CO2 equivalent in tonnes of the fluorinated greenhouse gas (on some models), please refer to the relevant label on the unit itself.
  2. Installation, service, maintenance and repair of this unit must be performed by a certified technician.
  3. Product uninstallation and recycling must be performed by a certified technician.

Sociable Remark

When using this dehumidifier in the European countries, the following information must be followed:

DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.

It is prohibited to dispose of this appliance in domestic household waste.

For disposal, there are several possibilities:

WARNING for Using R32/R290 Refrigerant

For R290

amount of refrigerant (kg) Min. room area(m²) amount of refrigerant (kg) Min. room area(m²)
>0.0836 and≤0.1045 5 >0.2090 and≤0.2299 11
>0.1045 and≤0.1254 6 >0.2299 and≤0.2508 12
>0.1254 and≤0.1463 7 >0.2508 and≤0.2717 13
>0.1463 and≤0.1672 8 >0.2717 and≤0.2926 14
>0.1672 and≤0.1881 9 >0.2926 and≤0.3135 15
>0.1881 and≤0.2090 10

Explanation of symbols displayed on the unit (For the unit adopts R32/R290 Refrigerant only):

WARNING This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.

CAUTION This symbol shows that the operation manual should be read carefully.

CAUTION This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.

CAUTION This symbol shows that information is available such as the operating manual or installation manual.

Caution: Risk of fire/flammable materials

Refrigerant Handling Procedures

  1. Transport of equipment containing flammable refrigerants: See transport regulations.
  2. Marking of equipment using signs: See local regulations.
  3. Disposal of equipment using flammable refrigerants: See national regulations.
  4. Storage of equipment/appliances: The storage of equipment should be in accordance with the manufacturer's instructions.
  5. Storage of packed (unsold) equipment: Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
  6. Information on servicing:
    1. Checks to the area: Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
    2. Work procedure: Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.
    3. General work area: All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
    4. Checking for presence of refrigerant: The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
    5. Presence of fire extinguisher: If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
    6. No ignition sources: No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.
    7. Ventilated area: Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
  7. Checks to the refrigeration equipment: Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt consult the manufacturer's technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:
    • The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
    • The ventilation machinery and outlets are operating adequately and are not obstructed;
    • If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
    • Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
  8. Checks to electrical devices: Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
    • Initial safety checks shall include: That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; That there are no live electrical components and wiring are exposed while charging, recovering or purging the system; That there is continuity of earth bonding.
  9. Repairs to sealed components:
    1. During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
    2. Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's specifications.
  10. NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
  11. Repair to intrinsically safe components: Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
  12. Cabling: Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
  13. Detection of flammable refrigerants: Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
  14. Leak detection methods: The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
  15. Removal and evacuation: When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
  16. Charging procedures: In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
  17. Decommissioning: Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
  18. a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before attempting the procedure ensure that: Mechanical handling equipment is available, if required, for handling refrigerant cylinders; All personal protective equipment is available and being used correctly; The recovery process is supervised at all times by a competent person; Recovery equipment and cylinders conform to the appropriate standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with manufacturer's instructions. h) Do not overfill cylinders. (No more than 80% volume liquid charge). i) Do not exceed the maximum working pressure of the cylinder, even temporarily. j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
  19. Labelling: Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
  20. Recovery: When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

Installation Instructions

Preparation

NOTE: All the illustrations in the manual are for explanation purpose only. Your machine may be slightly different. The actual shape shall prevail. The unit can be controlled by the unit control panel alone or with the remote controller. This manual does not include Remote Controller Operations, see the <<Remote Controller Instruction>> packed with the unit for details.

Diagram of unit components:

Design Notice

In order to ensure the optimal performance of our products, the design specifications of the unit and remote control are subject to change without prior notice.

Energy Rating Information

The Energy Rating for this unit is based on an installation using an un-extended exhaust duct without window slider adaptor (as shown in the Installation section of this manual). At the same time, the unit must be operate on the COOL MODE and HIGH FAN SPEED by remote controller.

Ambient Temperature Range For Unit Operating

MODE Temperature Range MODE Temperature Range
Cool 17-35°C (62-95°F) Heat (heat pump mode) 5-30°C (41-86°F)
Dry 13-35°C (55-95°F) Heat (electrical heat mode) ≤ 30°C (86°F)

Exhaust hose installation

The exhaust hose and adaptor must be installed or removed in accordance with the usage mode. For COOL, HEAT (heat pump type) or AUTO mode, the exhaust hose must be installed. For FAN, DRY or HEAT (electrical heat type) mode, the exhaust hose must be removed.

Choosing The Right Location

Your installation location should meet the following requirements:

Recommend Installation

Diagram showing recommended clearances around the unit.

Energy Rating Information

The energy rating and noise information for this unit is based on the standard installation using an un-extended exhaust duct without window slider adaptor (as shown in the Installation section of this manual). At the same time, the unit must be operate on the COOL MODE and HIGH FAN SPEED by remote controller.

The unit with 3 meters extended exhaust duct is running by using 2 exhaust ducts (Diameter: 150mm, Length: 1.5m + Diameter: 130mm, Length: 1.5m). The Energy rating and noise information for unit with 3 meters extended exhaust duct is not assessed. (For some models)

NOTE: We recommend that operating the unit at room temperature below 35°C. Since there is a risk that the unit with 3 meters extended exhaust duct would not work at room temperature above 35°C under some extreme conditions, such as the lower air intake be blocked for 50%.

How to Stay Cool with a New Portable Air Conditioner (For the models comply with the requirements of Department Of Energy in US)

Because of a new federal test procedure for Portable Air Conditioners, you may notice that the cooling capacity claims on portable air conditioner packaging are significantly lower than that of models produced prior to 2017. This is due to changes in the test procedure, not to the portable air conditioners themselves.

What should I look for first when purchasing a portable air conditioner?

The right air conditioner helps you cool a room efficiently. An undersized unit won't cool adequately while one that's too large will not remove enough humidity, leaving the air feeling damp. To find the proper air conditioner, determine the square footage of the room you want to cool by multiplying the room length by its width. You also need to know the air conditioner's BTU (British Thermal Unit) rating, which indicates the amount of heat it can remove from a room. A higher number means more cooling power for a larger room. (Be sure you are comparing only newer models to each other - older models may appear to have a higher capacity, but are actually the same). Be sure to "size up" if your portable air conditioner will be placed in a very sunny room, in a kitchen, or in a room with high ceilings. After you've found the right cooling capacity for your room, you can look at other features.

Why is the cooling capacity lower on newer models than on older units?

Federal regulations require manufacturers to calculate cooling capacity based on a specific test procedure, which was changed just this year. Models manufactured before 2017 were tested under a different procedure and cooling capacity is measured differently than in prior years' models. So, while the BTUs may be lower, the actual cooling capacity of the air conditioners has not changed.

What is SACC?

SACC is the representative value of Seasonally Adjusted Cooling Capacity, in Btu/h, as determined in accordance with the DOE test procedure at title 10 Code of Federal Regulations (CFR) 430, subpart B, appendix CC and applicable sampling plans.

Tools Needed

Accessories

NOTE: Items with (*) are on some models. Slight variations in design may occur.

North America

Shape Name of Accessories Qty. Shape Name of Accessories Qty.
Unit Adaptor 1 pc Security Bracket and 2 Screws 1 set
Exhaust Hose 1 pc Drain Hose 1 pc
Window Slider Adaptor 1 pc Power Cord Buckle 1 pc
Window Slider A 1 pc Bolt 1 pc/2 pc(*)
Window Slider B 1 pc Remote Controller and Battery (only for remote control models) 1 set(*)
Drain Hose Adaptor 1 pc(*) (only for heat pump mode)
Foam Seal A (Adhesive) 2 pc/4 pc(*) Exhaust Hose Adaptor 1 pc(*)
Foam Seal B (Adhesive) 2 pc Extended Exhaust Hose 1 pc(*)
Foam Seal C (Non-adhesive) 1 pc/2 pc(*)

Other Regions

Shape Name of Accessories Qty. Shape Name of Accessories Qty.
Unit Adaptor 1 pc Security Bracket and 2 Screws 1 set(*)
Exhaust Hose 1 pc Drain Hose 1 pc
Window Slider Adaptor 1 pc(*) Power Cord Buckle 1 pc
Window Slider A 1 pc(*) Bolt 1 pc(*)
Window Slider B 1 pc(*) Remote Controller and Battery (only for remote control models) 1 set(*)
Foam Seal A (Adhesive) 2 pc(*) Wall Exhaust Adaptor A (only for wall installation models) 1 pc(*)
Foam Seal B (Adhesive) 2 pc(*) Wall Exhaust Adaptor B (with cap) (only for wall installation models) 1 pc(*)
Foam Seal C (Non-adhesive) 1 pc(*) Screw and anchor (only for wall installation models) 4 set(*)
Drain Hose Adaptor (only for heat pump mode) 1 pc(*) Extended Exhaust Hose 1 pc(*)
Exhaust Hose Adaptor 1 pc(*)

Window Installation Kit

Step One: Preparing the Exhaust Hose assembly

Press the exhaust hose (or extended exhaust hose) into the window slider adaptor (or wall exhaust adaptor) and unit adaptor, clamp automatically by elastic buckles of the adaptors.

Diagram showing exhaust hose assembly for window installation.

Diagram showing exhaust hose assembly for wall installation.

Step Two: Install the Exhaust hose assembly to the unit

Push the Exhaust hose into the air outlet opening of the unit along the arrow direction.

Step Three: Preparing the Adjustable Window Slider

  1. Depending on the size of your window, adjust the size of the window slider.
  2. If the length of the window requires two or three window sliders, use the bolt(s) to fasten the window sliders once they are adjusted to the proper length.

Installation

NOTE: Once the Exhaust Hose assembly and Adjustable Window Slider are prepared, choose from one of the following two installation methods.

Type 1: Hung Window or Sliding Window Installation (For some models)

  1. Cut the adhesive foam seal A and B strips to the proper lengths, and attach them to the window sash and frame as shown.
  2. Insert the window slider assembly into the window opening.
  3. Cut the non-adhesive foam seal C strip to match the width (or height) of the window. Insert the seal between the glass and the window frame to prevent air and insects from getting into the room.

Diagram showing foam seal application for window installation.

Diagram showing window slider assembly insertion.

Diagram showing foam seal C application.

Type 2: Wall Installation (For some models)

  1. Cut a 125mm (4.9inch) hole into the wall for the Wall Exhaust Adaptor B.
  2. Secure the Wall Exhaust Adaptor B to the wall using the four Anchors and Screws provided in the kit.
  3. Connect the Exhaust Hose Assembly (with Wall Exhaust Adaptor A) to the Wall Exhaust Adaptor B.

Diagram showing wall installation setup.

NOTE: Cover the hole using the adaptor cap when not in use.

NOTE: To ensure proper function, DO NOT overextend or bend the hose. Make sure that there is no obstacle around the air outlet of the exhaust hose (in the range of 500mm) in order to the exhaust system works properly. All the illustrations in this manual are for explanation purpose only. Your air conditioner may be slightly different. The actual shape shall prevail.

Diagrams of exhaust hoses.

Operating Instructions

Control Panel Features

NOTE: The following control panels are for explanation purpose only. The control panel of the unit you purchased may be slightly different according to the models. Your machine may not contain some indicators or buttons. The actual shape shall prevail.

Diagrams of control panels.

LED display: Shows the set temperature while on cool, heat or auto mode. While on DRY and FAN modes, it shows the room temperature. Shows Error codes: E0-EEPROM error. E1-Room temperature sensor error. E2-Evaporator temperature sensor error. E3-Condenser temperature sensor error (on some models). E4-Display panel communication error. EC-Refrigerant leakage detection malfunction (on some models).

Shows protection code: P1-Bottom tray is full--Connect the drain hose and drain the collected water away. If protection repeats, call for service.

NOTE: When one of the above malfunctions occurs, turn off the unit, and check for any obstructions. Restart the unit, if the malfunction is still present, turn off the unit and unplug the power cord. Contact the manufacturer or its service agents or a similar qualified person for service.

Operation Instructions

Other features

Maintenance

Safety Precautions

Air Filter Cleaning

Diagram showing air filter removal.

CAUTION: DO NOT operate the unit without filter because dirt and lint will clog it and reduce performance.

Maintenance Tips:

Unit Cleaning

Clean the unit using a damp, lint-free cloth and mild detergent. Dry the unit with a dry, lint-free cloth.

Store the unit when not in use

Troubleshooting Tips

Problem Possible Causes Solution
Unit does not turn on when pressing ON/OFF button P1 Error Code The Water Collection Tray is full. Turn off the unit, drain the water from the Water Collection Tray and restart the unit.
In COOL mode: room temperature is lower than the set temperature Reset the temperature
E0 EEPROM error Contact the manufacturer or its service agents or a similar qualified person for service.
The air filter is blocked with dust or animal hair Turn off the unit and clean the filter according to instructions
Exhaust hose is not connected or is blocked Turn off the unit, disconnect the hose, check for blockage and reconnect the hose
Unit does not cool well The unit is low on refrigerant Call a service technician to inspect the unit and top off refrigerant
Temperature setting is too high Decrease the set temperature
The windows and doors in the room are open Make sure all windows and doors are closed
The room area is too large Double-check the cooling area
There are heat sources inside the room Remove the heat sources if possible
The unit is noisy and vibrates too much The ground is not level Place the unit on a flat, level surface
The air filter is blocked with dust or animal hair Turn off the unit and clean the filter according to instructions
The unit makes a gurgling sound This sound is caused by the flow of refrigerant inside the unit This is normal

Impedance Information

To be in compliance EN 61000-3-11, the product MPPH-08CRN7-QB6 shall be connected only to a supply of the system impedance: | Zsys|=0.451 ohms or less, the product MPPH-09CRN7-QB6G1 shall be connected only to a supply of the system impedance: | Zsys|=0.437 ohms or less. Before connect the product to public power network, please consult your local power supply authority to ensure the power network meet above requirement.

Models: CP006UI-PHTY, CP006UI-PHTY 3 In 1 10000BTU Smart Portable AC Air Conditioner, CP006UI-PHTY, 3 In 1 10000BTU Smart Portable AC Air Conditioner, Smart Portable AC Air Conditioner, Air Conditioner, Conditioner
5110b78b-aa07-4469-86db-86dc291d25ad Microsoft: Print To PDF

Related Documents

Preview Portable Air Conditioner Owner's Manual & Installation Guide
Comprehensive owner's and installation manual for Midea portable air conditioners, covering safety precautions, setup, operation, maintenance, and troubleshooting.
Preview Midea Air Conditioner and Dehumidifier Statement of Compliance for UK PSTI
GD Midea Air-conditioning Equipment Co., Ltd. declares compliance for Midea air conditioners and dehumidifiers with UK PSTI requirements, detailing standards met and product models.
Preview Portable Air Conditioner Owner's Manual & Installation Guide
Comprehensive guide for installing and operating your portable air conditioner, covering safety precautions, installation steps, operating instructions, maintenance, and troubleshooting.
Preview Midea CPPHA-09CRN7-L Mobile Air Conditioner Warranty and Service Information
Details the warranty terms, conditions, and service contact information for the Midea / Comfee CPPHA-09CRN7-L mobile air conditioner, applicable within Germany.
Preview Midea Mobile Air Conditioner Owner's Manual & Installation Guide - CP002UI-PT
User and installation manual for Midea mobile air conditioners, model CP002UI-PT. Covers safety, setup, operation, maintenance, and troubleshooting.
Preview Midea Room Air Conditioner User Manual - Models ACE-09HRFN8 IN, ACE-12HRFN8 IN, ACE-18HRFN8 IN, ACE-24HRFNX IN
Comprehensive user manual for Midea Room Air Conditioners, covering installation, operation, maintenance, and troubleshooting for models ACE-09HRFN8 IN, ACE-12HRFN8 IN, ACE-18HRFN8 IN, and ACE-24HRFNX IN.
Preview Midea Portable Air Conditioner Manual Specification Sheet
Official specification sheet and checklist for the Midea Portable Air Conditioner manual, detailing layout, technical requirements, and revision history.
Preview Midea U-Shape Window Air Conditioner Safety Recall Alert
Urgent safety recall notice for Midea U-Shape Window Air Conditioners purchased between June 2021 and May 2025. Learn about potential mold growth hazards and available remedies.