If needed, you can repeat the complete procedure to program other days or sequences of days. Day Sequences are: MON. TUE. WED. THU. FRI. SAT.


File Info : application/pdf, 12 Pages, 2.73MB

PDF preview unavailable. Download the PDF instead.

RAYCHEM-IM-EU0637-GreenLeafEU-EN
Green Leaf
Programmable Thermostat for Electrical Floor Heating Installation Instruction

TABLE OF CONTENTS
1.DESCRIPTION .................................................................................................................................................................... 3 2.MOUNTING AND INSTALLATION........................................................................................................................................ 3
Mounting the Thermostat.......................................................................................................................................................................... 3 3.USING THE THERMOSTAT ................................................................................................................................................. 5
The Display ............................................................................................................................................................................................... 5 Display in manual on/off programme................................................................................................................................................... 5 Display in timer programme ................................................................................................................................................................ 5
The manual on/off programme.................................................................................................................................................................. 6 The timer programme ............................................................................................................................................................................... 6 4.SETTING THE CLOCK......................................................................................................................................................... 7 5.PROGRAMMING THE TIMER PROGRAMme........................................................................................................................ 7 6.INSTALLER MENU.............................................................................................................................................................. 8 7.TROUBLESHOOTING.......................................................................................................................................................... 9 8.TECHNICAL SPECIFICATION.............................................................................................................................................. 9
ATTENTION This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. 2 | nVent.com/RAYCHEM

1.DESCRIPTION
The nVent RAYCHEM Green Leaf Thermostat is a Programmable Thermostat designed for Electrical Floor Heating. The thermostat is designed to control your Electrical Floor Heating in order to give you the best possible comfort and the lowest possible energy usage. The Thermostat can work in 3 different temperature sensing modes: · Floor Sensing mode · Room Sensing mode · Room Sensing mode with floor temperature limiter
The Thermostat has 2 programmes to choose from: · Manual ON/OFF (Constant Single temperature) · Timer programme (4 timer events/day) To change from one programme to the other, just touch the intelligent leaf button" ".
2.MOUNTING AND INSTALLATION
Mounting the Thermostat
The installation of the Green Leaf must be performed by a qualified installer. The Green Leaf is a thermostat with protection class IP21, make sure to comply with all local regulations when installing the thermostat. Green Leaf is intended for flush mounting in a wall box. It should be positioned approximately 1.5 meters above the floor, protected from direct sunlight and draughts. All electrical conduits passing into the wall box that contain cables must also be sealed to protect the thermostat against draughts, e.g. with a piece of insulation in the conduit outlet. Step 1: Switch off the power supply Step 2: Detach the metallic support from the Thermostat using a screwdriver

nVent

nVent

nVent

Step 3: Screw the metallic support frame to the in-wall box

Step 4: Install the floor sensor (mandatory for floor sensing mode or room sensing mode with floor temperature limiter). The floor sensor should be installed in a separate flexible conduit all the way to the end, covering the end of the sensor, for easy replacement and to avoid possible signal disturbance on the sensor. For best control performance, position the floor sensor between two heating cables as close as possible to the top floor surface. Do not position the floor sensor tip closer than 3 cm to the heating cable. The floor sensor cable can be extended up to 100 m with a separate standard installation cable 2 x 1.5 mm2 (230VAC).
nVent.com/RAYCHEM | 3

Step 5: Connect the electrical power supply, the sensor and the cold lead of the electrical floor heating system to the Green Leaf according to the electrical diagram. If you connect heating cables exceeding 13A for constant wattage or 10A for self-regulating cables you must use a contactor with an integrated suppression device. For the earth connection of the floor heating, you must use a separate earth terminal connection block.
nVent
Step 6: Click the Green Leaf into the metallic support frame.
Step 7: Switch on the power again Product specific information The thermostat is compatible with nVent RAYCHEM QuickNet, T2Blue, T2Green, T2Black and T2Red heating solutions. T2Red Self-regulating heating cables have an inrush current when the floor is cold. In order to guarantee the life time of the thermostat, the maximum load of the self-regulating application in nominal conditions is limited to 10A. A 13A self-regulating load will reduce the life time of the relay contacts and the installation will not be covered by the Total Care Warranty.
4 | nVent.com/RAYCHEM

3.USING THE THERMOSTAT The Display Display in manual on/off programme
The following icons are visible in the Manual ON/OFF: Active sensor display · Floor sensing mode ( ) · Room Sensing mode ( ) · Room Sensing mode with Floor temperature limiter ( )
Heating display The heating display is flashing when the heating is on.
Temperature The temperature on the display depends on the selected sensing mode. · Floor sensing mode => Actual floor temperature on the display · Room sensing mode => Actual room temperature on the display · Room sensing with floor temperature limiter mode => Actual room temperature on the display
Remark: When touching on the " " or " " button, the set point temperature appears on the display blinking for 5 seconds
Installer Menu · Touch the M button for 5 seconds to enter the Installer Menu
Display in timer programme The following icons are visible in the Timer Programme:
Time and day The actual day is displayed on the screen with the 3 letters (MON-TUE-WED-THU-FRI-SAT-SUN). The time can be set in 24H or 12AM/PM mode (see INSTALLER MENU).
4 Event display The 4 events are displayed with the symbols:
Event 1 Event 2 Event 3 Event 4
nVent.com/RAYCHEM | 5

The manual on/off programme
When switching on the thermostat for the first time (touching the Green Leaf button for 2 seconds), it will start in MANUAL ON/ OFF programme using the floor sensing mode as a standard (see INSTALLER MENU to change the sensing mode).
You will see the following screen:
Touch " " or " " to show the set point temperature. It will blink for 5 seconds.
1. Touch " " to decrease the temperature. 2. Touch " " to decrease the temperature. To switch from Manual ON/OFF to Timer Programme, touch the " " button once. To switch off the thermostat, touch the " " button for 2 seconds.

The timer programme
The Green Leaf can be programmed with 4 events per day. Different temperatures can be maintained for each event of the day. The days can be programmed independently or per cluster of days.
The default Timer Programme is shown on the graph below. You can easily adapt the programme to your needs (see PROGRAMMING THE TIMER PROGRAMME)

25

20

15

23

23

10

16

16

16

5

0

MON-TUE-WED-THU-FRI 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00

SAT-SUN 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00

25
20
15 23
10 16
5
0
· Touch the " " button to set the clock and day of the week · Touch the " " button for 3 seconds to program the timer programme (see page 14 for more details). · Touch the " " button for 5 seconds to enter the Installer Menu · Touch the " " button to switch from Timer to Manual ON/OFF mode · Touch the " " button for 2 seconds to put the Thermostat into OFF (standby) mode · Touch " " or " " to show the set point temperature. It will blink for 5 seconds
1. Touch " " to decrease the temperature. 2. Touch " " to decrease the temperature. Remark: The adapted temperature is valid until the next timer Event.

6 | nVent.com/RAYCHEM

4.SETTING THE CLOCK
· Touch the " " button to set the clock and day of the week · Touch " " or " " to change the hours · Touch the " " button to validate · Touch " " or " " to change the minutes · Touch the " " button to validate · Touch " " or " " to change the day of the week · Touch the " " button to validate
Remark: In case of battery drainage after long period of power failure, you might have to re-programme the clock.
5.PROGRAMMING THE TIMER PROGRAMME
· Touch the " " button for 3 seconds to program the Timer Programme · Touch " " or " " to choose the day (or the sequence of days) you want to program · Touch the " " button to validate
Day Sequences are:
MON TUE WED THU FRI SAT SUN MONTUEWEDTHUFRI SAT SUN MONTUEWEDTHUFRISATSUN
For Event 1
· Touch " " or " " to change hours of Event 1 · Touch the " " button to validate · Touch " " or " " to change the minutes of Event 1 · Touch the " " button to validate · Touch " " or " " to change the temperature for Event 1 · Touch the " " button to validate
For Event 2, 3 and 4
· Repeat the actions for event 1 for the Events 2, 3 and 4 Touch the " " button, at any time during the programming, to save your changes and return to the Timer Programme. If needed, you can repeat the complete procedure to program other days or sequences of days.
nVent.com/RAYCHEM | 7

6.INSTALLER MENU

Touch the " " button for 5 seconds to enter the installer Menu

#

Description

1

Sensing mode selection

2

12 vs 24 hours display

3

Motion sensor. When getting close

to the thermostat (5cm range)

the display lights up automatically

4

Offset for floor sensor calibration

5

Room sensor calibration

6

Minimum temperature

set point for the Floor Sensor

7

Maximum temperature

set point for the Floor Sensor

8

Minimum temperature

set point for the Room Sensor

9

Maximum temperature

set point for the Room Sensor

10 Adjustable hysteresis 11 Open window function

Range Floor sensing mode Room sensing mode Room sensing mode with floor temperature limiter 12 / 24 ON / OFF

Default setting Floor Sensing mode
24 ON

Offset of 0 .. 10°C

4°C

Measured sensor temperature +/- 5°C

Measured sensor temperature

Floor sensing mode: 5 .. 15°C

5°C

Room sensing mode: OFF

OFF

Room sensing mode with floor temperature

OFF

limiter: OFF

Floor sensing mode: Minimum temperature set point floor sensor (installer menu 6) +5°C .. 35°C Room sensing mode: OFF

35°C OFF

Room sensing mode with floor temperature limiter: 27°C 10 .. 35°C

Floor sensing mode: OFF

OFF

Room sensing mode: 5 .. 15°C

5°C

Room sensing mode with floor temperature limiter: 5°C 5 .. 15°C

Floor sensing mode: OFF

OFF

Room sensing mode: Minimum temperature set point room sensor (installer menu 8)

40°C

+5°C .. 40°C

Room sensing mode with floor temperature limiter: 40°C Minimum temperature set point room sensor (installer menu 8) +5°C .. 40°C

0.5 .. 2.0°C

1.0°C

ON/OFF

ON

Floor sensor calibration
The temperature of the floor surface can differ from the temperature measured by the floor sensor due to the floor construction, the floor type and the position of the floor sensor. In order to calibrate your thermostat to this difference you can use the floor sensor calibration OFFSET in installer Menu 4. After the temperature on the floor is stabilized, place a thermometer on the floor surface in order to sense the real temperature on the surface (Tsurface). Read the floor sensor temperature (Tsensor) on the thermostat and adjust the OFFSET accordingly to the formula:
OFFSET = Tsensor - Tsurface

Tsurface
Tsensor
Room sensor calibration
If the value measured by the room sensor in the thermostat differs from the real room temperature, it is possible to calibrate the room sensor using the installer Menu 5. After the temperature in the room is stabilized, place a thermometer close to the wall in order to sense the real room temperature. If this value differs from the one shown by the thermostat, adjust Menu 5 using the " " or the " " until the thermostat shows the same value as the reference thermometer.

8 | nVent.com/RAYCHEM

7.TROUBLESHOOTING
In the event of damage or malfunction of one of the temperature sensors, the heating output cuts off (fail safe) and an error code is displayed.

Error Code ER1 ER2 ER3 ER4 ER5

Description Short circuit on floor sensor Open circuit on floor sensor / Missing floor sensor Short circuit on room sensor Open circuit on room sensor Check sensing mode

The floor sensor can be replaced by a new. In the event of malfunction of the room sensor, the entire thermostat must be replaced (Error 3 or Error 4).
Error 5 occurs if the thermostat is set in Room Sensing Mode and the floor sensor is installed.
To resolve the error change the sensing mode in Floor sensing or Room sensing with floor temperature limiter. Otherwise, remove the floor sensor to work in room sensing mode. The floor sensor has got the following temperature/resistance values:

Temperature 15°C 20°C 25°C 30°C 35°C

Resistance 15.8 k 12.5 k 10.0 k 8.0 k 6.5 k

8.TECHNICAL SPECIFICATION
Supply voltage Power consumption (Stand-by) Relay output Ambient temperature ­ operation Ambient temperature ­ transport Temperature range, floor sensor Temperature range, room sensor Switching hysteresis
Control modes
Temperature control
Protection class Terminals Floor sensor with 3 m cable Maximum length of floor sensor Cable Approvals
Type of action Control pollution degree Rated impulse voltage Temperature for the ball pressure test SELV limits realized * According to the EN 60730-1 table 1

230VAC, +10%, ­15%, 50Hz 3 VA 230V, maximum 13A resistive load (max. 3000W) 0 .. 40°C, 5-95% RH (non condensing) ­10 .. +60°C +5 .. +35°C +5 .. +40°C 1°C (Factory settings adjustable between 0.5-2.0°C) Floor sensing Room sensing Room sensing with floor temperature limiter Manual ON/OFF Timer programme IP 21 Max. 2,5 mm² NTC, 10K / 25°C 100 m, 2 x 1,5 mm² (230VAC cable type)
1.B. (39)* 2 (49)* 4kV (75)* 125°C (77)* 22 VDC (86)*

nVent.com/RAYCHEM | 9

Dimensions 86.3 86.3 86.3 48.0

41.0

16.5

79.8

60.0

49.0

10 | nVent.com/RAYCHEM

nVent.com/RAYCHEM | 11

België / Belgique Tel +32 16 21 35 02 Fax +32 16 21 36 04 salesbelux@nVent.com
Bulgaria Tel +359 5686 6886 Fax +359 5686 6886 salesee@nVent.com
Ceská Republica Tel +420 602 232 969 czechinfo@nVent.com
Danmark Tel +45 70 11 04 00 salesdk@nVent.com Deutschland Tel 0800 1818205 Fax 0800 1818204 salesde@nVent.com
España Tel +34 911 59 30 60 Fax +34 900 98 32 64 ntm-sales-es@nVent.com
France Tél 0800 906045 Fax 0800 906003 salesfr@nVent.com
Hrvatska Tel +385 1 605 01 88 Fax +385 1 605 01 88 salesee@nVent.com

Italia Tel +39 02 577 61 51 Fax +39 02 577 61 55 28 salesit@nVent.com
Lietuva/Latvija/Eesti Tel +370 5 2136633 Fax +370 5 2330084 info.baltic@nVent.com
Magyarország Tel +36 1 253 4617 Fax +36 1 253 7618 saleshu@nVent.com
Nederland Tel 0800 0224978 Fax 0800 0224993 salesnl@nVent.com
Norge Tel +47 66 81 79 90 salesno@nVent.com
Österreich Tel 0800 29 74 10 Fax 0800 29 74 09 salesat@nVent.com
Polska Tel +48 22 331 29 50 Fax +48 22 331 29 51 salespl@nVent.com
Republic of Kazakhstan Tel +7 495 926 1885 Fax +7 495 926 18 86 saleskz@nVent.com

  +7 495 926 18 85  +7 495 926 18 86 salesru@nVent.com
Serbia and Montenegro Tel +381 230 401 770 Fax +381 230 401 770 salesee@nVent.com
Schweiz / Suisse Tel +41 (41) 766 30 80 Fax +41 (41) 766 30 81 infoBaar@nVent.com
Suomi Puh0800 11 67 99 salesfi@nVent.com
Sverige Tel +46 31 335 58 00 salesse@nVent.com
Türkiye Tel +90 545 284 09 05 Fax +32 16 21 36 04 salesse@nVent.com
United Kingdom Tel 0800 969 013 Fax 0800 968 624 salesthermalUK@nVent.com

©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.
RAYCHEM-IM-EU0637-GreenLeafEU-EN-2110

nVent.com/RAYCHEM



References

Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)