nVent RAYCHEM NGC-40-HTC & NGC-40-HTC3 Installation Instructions

Control and monitoring modules for use with nVent RAYCHEM NGC-40 system

Approvals and Certifications

Hazardous Locations:

  • Class I, Div. 2, Groups A,B,C,D T4
  • Class I, Zone 2, AEx nC IIC T4 IP20
  • Ex nL nC IIC T4 X
  • -40°C ≤ Ta ≤ +65°C

Conforms to:

  • FM Class Number 3600 (11/98)
  • FM Class Number 3611 (10/99)
  • ANSI/UL STD. 60079-15-2009
  • UL STD. 61010-1

Certified to:

  • CAN/CSA STD. C22.2 No. 213-M1987 (R2004)
  • CAN/CSA STD. C22.2 No. 61010-1:2004
  • EN 61010-1 (2001)
  • CAN/CSA STD. E60079-15:02 (R2006)

IEC Ex Markings:

  • IEC Ex ETL17.0062X
  • Ex ec nC IIC T4 Gc

ATEX Markings:

  • ITS17ATEX402833X
  • II 3 G Ex ec nC IIC T4 Gc

Description

The nVent RAYCHEM NGC-40-HTC (for single-phase heaters) and NGC-40-HTC3 (for three-phase heaters) modules are used to control either an external solid-state relay or a contactor within the NGC-40 control and monitoring system. These modules also have one alarm output and one digital input. The alarm output can be used to activate an external annunciator. The digital input is programmable and may be used for various functions such as forcing outputs on and off. Other features include ground-fault and line current sensing for both HTC and HTC3. The front panel of the HTC modules has LED indicators for various status conditions. The front panel also provides a ground-fault and heater test button.

Tools Required

  • Small flat-blade screwdriver

Additional Materials

  • Power supply 24 Vdc @100 mA per NGC-40-HTC/HTC3
  • Custom built CAN cables with RJ-45 connections
  • CAN Termination Resistor

Kit Contents

ItemQtyDescription
A1NGC-40-HTC module (single-phase heaters)
B1NGC-40-HTC3 module (three-phase heaters)

Special Conditions of Use

  • The overall equipment is evaluated to type of protection "ec". Sealed devices in the form of relays are additionally present in module NGC-40-HTC and NGC-40-HTC3 and comply with requirements for the type of protection nC.
  • For full connection details see these installation instructions.
  • The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/EN 60664-1.
  • The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP54 in accordance with IEC/EN 60079-0.
  • Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.

Warning

This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. For technical support, call nVent at (800) 545-6258.

General Specifications

ParameterValue
Supply voltage24 Vdc ± 10%
Internal power consumption< 2.4 W per NGC-40-HTC/HTC3 module
Ambient operating temperature-40°C to 65°C (-40°F to 149°F)
Ambient storage temperature-55°C to 75°C (−67°F to 167°F)
EnvironmentPD2, CAT III
Max. altitude2,000 m (6,562 ft)
Humidity5 – 90% noncondensing
MountingDin Rail – 35 mm

Electromagnetic Compatibility

CategoryStandard
EmissionsEN 61000-6-3 Emission standard for residential, commercial and light industrial environments
ImmunityEN 61000-6-2 Immunity standard for industrial environments

Temperature Sensors

ParameterSpecification
Type100 Ω platinum RTD, 3-wire, α = 0.00385 ohms/ohm/°C. Can be extended with a 3-conductor shielded cable of 20 Ω maximum per conductor.
Type100 Ω, Ni-Fe, 2-wire. Can be extended with a 2-wire shielded cable of 20 Ω maximum per conductor.
QuantityOne per NGC-40-HTC/HTC3 module

Alarm Relay

Dry contact relay (voltage free): Relay contact rated 250 V / 3 A 50/60 Hz (CE) and 277 V / 3 A 50/60 Hz (cSAus). Alarm relay is programmable. NO and NC contacts available.

Contactor Output Relay

Relay contact rated 250 V / 3 A 50/60 Hz (CE) and 277 V / 3 A 50/60 Hz (c-CSA-us).

Digital Input

Multi-purpose input for connection to external dry (voltage-free) contact or DC voltage. May be user programmable for: not used / force off / force on functions. It can be configured to be active open or active closed.

CAN Networking Port

ParameterSpecification
Type2-wire isolated CAN-based peer to peer network. Isolated to 24 Vdc – verified by 500 Vrms dielectric withstand test
ConnectionTwo 8-pin RJ-45 connectors (both may be used for Input or Output connections)
ProtocolProprietary NGC-40
TopologyDaisy chain
Cable length10 m (33 ft) maximum
QuantityUp to 80 HTC/HTC3 and IO modules per network segment
AddressUnique, factory assigned

Connection Terminals

Wiring terminals: Cage clamp, 0.5 to 2.5 mm² (24 to 12 AWG)

Housing

Size: 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep

Line Current Sensors

ParameterValue
Max current63 A
Accuracy± 2% of reading

Ground-Fault Sensor

ParameterValue
Range10 – 250 mA
Accuracy± 2% of range

Outputs

SSR output: 12 Vdc @ 45 mA max per output

System Components

Module Overview

The NGC-40-HTC and NGC-40-HTC3 modules are compact electronic units designed for DIN rail mounting. They feature a front panel with various status LEDs and control buttons.

Front Panel Layout

The front panel includes the following status indicators and controls:

  • STATUS LED: Indicates the overall status of the HTC/HTC3 module.
    • Off: No power.
    • Green: Normal operation, no internal faults.
    • Yellow: Module is in Factory mode.
    • Red: Indicates HTC/HTC3 operating status.
    • Flash R: Indicates an internal fault.
    • Flash R/G: Indicates factory status.
    • Flash R/Y: Indicates an internal fault has been detected.
  • NETWORK LED: Indicates CAN network activity.
    • Off: No network activity.
    • Green: Flicker indicates receipt of network data.
    • Yellow: Flicker indicates transmission of network data.
    • Flash R: Indicates network communication failure.
  • INPUT LED: Shows the status of the digital input.
    • Off: Input is inactive (open).
    • Green: Input is active (shorted).
    • Flash R: Indicates external input source failure.
  • OUTPUT LED: Shows the status of the contactor or SSR.
    • Off: Output is off.
    • Green: Follows the output state.
  • HEATER LED: Indicates the heater's alarm status.
    • Off: No alarm.
    • Red: High or low current or resistance alarm.
    • Flash R: Overcurrent trip alarm.
  • TS LED: Indicates the temperature alarm status.
    • Off: No alarm.
    • Red: High or low temperature alarm.
    • Flash R: Temperature sensor failure.
  • GFI LED: Indicates ground-fault status.
    • Off: No alarm.
    • Red: High or low ground-fault alarm.
    • Flash R: Ground-fault trip alarm.
  • SWITCH LED: Indicates contactor/SSR switch status.
    • Off: No alarm.
    • Red: Contactor cycle count alarm.
    • Flash R: Switch failed shorted on.
  • Buttons:
    • TEST: Initiates a heater test.
    • RESET: Resets the module or fault conditions.

Wiring Terminals

The modules feature a terminal block for various connections:

  • Terminal 1: Alarm relay N.O. (Normally Open)
  • Terminal 2: Alarm relay COM (Common)
  • Terminal 3: Alarm relay N.C. (Normally Closed)
  • Terminal 4: Not used
  • Terminal 5: SSR Out +
  • Terminal 6: SSR Out -
  • Terminal 7: Digital In +
  • Terminal 8: Digital In -
  • Terminal 9: Line In
  • Terminal 10: Line Out
  • Terminal 11: Coil Out
  • Terminal 13: TS COM (White wire)
  • Terminal 14: TS Sense (Red wire)
  • Terminal 15: TS Source (Red wire)
  • Terminal 16: Not used

WARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

Mounting

Each NGC-40-HTC/HTC3 mounts on a standard 35 mm DIN rail.

  • Mounting: Insert the rear bottom of the module into the DIN rail, then push up and inwards to engage the clip.
  • Removal: Push the module upwards to disengage the clip, then rotate the module toward you.

Power Supply and CAN Networking

The power supply and CAN bus connection utilize an RJ-45 connector. The CAN termination device must be installed in the unused port of the last module in the network chain. Connections are identical for both HTC and HTC3 modules.

Diagram Description: A module is shown with an RJ-45 port. One port is labeled for connection to "Cable from another module or power supply". The other port is labeled "CAN termination here if last one in chain".

RTD Input Connections

North American Installation Technique

For all RTD terminations, the RTD field wires must be terminated on a panel-mounted terminal block. Connections are the same for the HTC3.

Diagram Description: An HTC module's terminal block area is shown. Terminals 13-16 are labeled: TS COM (White), TS Sense (Red), TS Source (Red), and Not used. "HTC RTD Wiring" connects from a "Terminal block" to these terminals, and the terminal block connects to an "RTD".

European Installation Technique

For all RTD terminations, the RTD field wires must be terminated on a panel-mounted terminal block. The RTD cable shield from the field terminal block to the HTC module should be terminated at the earth ground bar located near the module. Connections are the same for the HTC3.

Diagram Description: Similar to the North American setup, but explicitly shows an "Earth grounding bar located at the HTC module" where the shield is terminated. The connection is from a "Field terminal block" to the "RTD".

Contactor Output Wiring

HTC3 Relay Output to Contactor - Three-Phase

Terminals 9 and 11 switch voltage to the contactor coils. The internal pilot relay switches the supply voltage (up to 277 V) to the contactor coil. Refer to the NGC-40 CAN bus connection diagrams for detailed wiring.

Note: Exposure to some chemicals may degrade the sealing properties of the relay output. Periodically inspect the relay output for degradation and replace if necessary.

Diagram Description: A three-phase circuit breaker (L3, L1, L2, N) is connected to the HTC3 module. Output terminals (9, 11) from the HTC3 are wired to a "Contactor" coil. A connection for "To heat tracing" is also shown.

HTC Single-Phase Wiring

Diagram Description: A single-phase circuit breaker (L1, N or L2) is connected to the HTC module. Output terminals (9, 11) from the HTC are wired to a "Contactor" coil. A connection for "To heat tracing" is also shown.

WARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

SSR Output Wiring

HTC Output Connections to SSR - Single-Phase

Terminals 5 & 6 switch voltage to the SSR. The internal SSR driver switches the internal supply voltage (12 Vdc) to the SSR.

Diagram Description: A single-phase circuit breaker (L1, N or L2) is connected to the HTC module. Terminals 5 & 6 are wired to an "SSR". The SSR output is connected to "To heat tracing" (L1, N or L2).

HTC3 Output Connections to SSR - Three-Phase

Diagram Description: A three-phase circuit breaker (L3, L1, L2, N) is connected to the HTC3 module. Terminals 5 & 6 are wired to an "SSR". The SSR output is connected to "To heat tracing" (L1, L2, L3).

WARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

Alarm Relay Functionality

WARNING: Shock Hazard. Disconnect from live voltage prior to accessing terminals.

Note: Exposure to some chemicals may degrade the sealing properties of the alarm relay. Periodically inspect the alarm relay for degradation and replace if necessary.

The alarm relay is multi-purpose and energized in a normal state, configured as Fail Safe. It provides a Form C dry contact rated at 277 V max (3 A).

  • NO (Normally Open) contact: Opens when de-energized. Closes during normal conditions when energized. Opens upon an alarm condition or power failure.
  • NC (Normally Closed) contact: Closes when de-energized. Opens during normal conditions when energized. Closes upon an alarm condition or power failure.

Relay Contact Rating: 250 V / 3A 50/60 Hz (CE); 277 V / 3A 50/60 Hz (c-CSA-us).

Connections are the same for the HTC3.

Diagram Description: An HTC module's alarm relay terminals (1, 2, 3) are shown, labeled NO, C, NC. It indicates "Failsafe Mode: Contacts shown energized with no alarm condition".

Digital Input Connections

North American and European Installation Techniques

Digital Input: Multi-purpose input for connection to external dry (voltage free) contact or DC voltage.

Rating: 100 Ω max loop resistance or 5-24 Vdc @ 1 mA maximum.

Connections are the same for the HTC3.

North American Installations

Diagram Description: An HTC module's digital input terminals (7 & 8) are shown connected to a "Terminal block". The terminal block is then connected to "+ From user input".

European Installations

Diagram Description: Similar to North American, with terminals 7 & 8 connected to a "Terminal block" and then to "+ From user input". An "Earth grounding bar located at the HTC module" is also shown.

Panel Enclosure and Location

1. Provide Suitable Panel Enclosure

The NGC-40-HTC or NGC-40-HTC3 must be mounted in an enclosure to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements.

Note: The nVent RAYCHEM NGC-40-HTC or NGC-40-HTC3 is designed for operation in ambient temperatures from -40°C to 65°C (-40°F to 149°F). If the ambient temperature is outside this range, a space heater and/or cooling fan will be required in the panel.

2. Determine Locations for Assembly in Panel

The NGC-40-HTC or NGC-40-HTC3 should be located in the rear of the panel. The assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.

* North American panel installation techniques

Diagram Description: A typical electrical panel layout is shown. The "Panel door" has an "Alarm light". The "Panel" interior shows various components and a row of HTC modules mounted.

NGC-40 CAN Bus Connections

Up to 10 Modules

Diagram Description: Illustrates a CAN bus network configuration for up to 10 modules. It shows a "Termination Block", a "Power/Termination Module", and a "Bridge Module" distributing power (24 Vdc) and CAN signals to multiple HTC/HTC3 or I/O modules connected in a daisy-chain via RJ-45 ports (IN/OUT). Primary and redundant power supplies (100-240 Vac In) are depicted, with a limit of 20 modules per power supply.

Up to 20 Modules

Diagram Description: Expands on the 10-module configuration, showing how to connect up to 20 modules. The structure remains similar, with power distribution and daisy-chaining of modules. It includes a section for modules 11 through 20, also connected to power supplies and the CAN bus.

Up to 40 Modules

Diagram Description: Depicts a larger CAN bus network for up to 40 modules, organized into segments. It shows multiple "Power/Termination Modules" and "Bridge Modules" supporting the daisy-chain connection of HTC/HTC3 or I/O modules across three tiers of 10-20 modules each. Power supplies are shown with capacity for 20 modules per supply.

* Power supply shall have a means for disconnect from the voltage.

Servicing

The NGC-40-HTC/HTC3 contains no user-serviceable parts. Contact your nVent representative for service and an RMA number if required.

Warnings

  • WARNING: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2 hazardous and nonhazardous locations.
  • AVERTISSEMENT - Risque D'explosion - La substitution de composants peut rendre ce matériel inacceptable pour les emplacements de Classe I, Division 2.
  • WARNING: Explosion Hazard - Do not replace NGC-40-PTM unless power has been switched off or the area is known to be nonhazardous.
  • AVERTISSEMENT - Risque D'explosion - Couper le courant ou s'assurer que l'emplacement est désigné non dangereux avant de replacer le NGC-40-PTM.
  • WARNING: Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is known to be nonhazardous.
  • AVERTISSEMENT - Risque D'explosion - Avant de déconnecter l'équipement, couper le courant ou s'assurer que l'emplacement est désigné non dangereux.

Contact Information

North America

Tel +1.800.545.6258

Fax +1.800.527.5703

thermal.info@nVent.com

Europe, Middle East, Africa

Tel +32.16.213.511

Fax +32.16.213.604

thermal.info@nVent.com

Asia Pacific

Tel +86.21.2412.1688

Fax +86.21.5426.3167

cn.thermal.info@nVent.com

Latin America

Tel +1.713.868.4800

Fax +1.713.868.2333

thermal.info@nVent.com


File Info : application/pdf, 10 Pages, 1.52MB

PDF preview unavailable. Download the PDF instead.

Raychem-IM-H58087-NGC40HTC-EN

References

Adobe PDF Library 16.0 Adobe InDesign 16.4 (Windows)

Related Documents

Preview nVent RAYCHEM NGC-30 Series Control and Monitoring Modules Installation Guide
Installation guide and technical specifications for the nVent RAYCHEM NGC-30 series of control and monitoring modules, designed for heat tracing applications. Covers NGC-30-CRM, NGC-30-CRMS, NGC-30-CTM, and NGC-30-CVM modules.
Preview nVent RAYCHEM NGC-30: Advanced Heat-Tracing Control System Datasheet
Comprehensive datasheet for the nVent RAYCHEM NGC-30, a multi-circuit electronic control, monitoring, and power distribution system for industrial heat-tracing applications. Details features, specifications, components, and configurations for process temperature maintenance and freeze protection.
Preview nVent RAYCHEM NGC-30 Installation Manual
This manual provides detailed installation, operation, and safety instructions for the nVent RAYCHEM NGC-30 system, including CRM, CRMS, CTM, and CVM modules. It covers electrical connections, hazardous area classifications, and maintenance.
Preview nVent RAYCHEM RMM2-E Trace-Heating Remote Monitoring Module Installation Guide
Comprehensive installation manual for the nVent RAYCHEM RMM2-E Remote Monitoring Module, detailing its features, specifications, and setup procedures for trace heating applications. Includes guidance on sensor connection, RS-485 communication, and safety precautions.
Preview nVent RAYCHEM Zone 2 Control & Monitoring Panels
nVent RAYCHEM Zone 2 Control and Monitoring panels are ATEX and IECEx approved electric heat-tracing panels designed for hazardous area applications. They offer flexible configurations, advanced features, and reliable performance for process temperature maintenance and freeze protection.
Preview nVent RAYCHEM Control and Monitoring Systems: Comprehensive Guide
Explore nVent RAYCHEM's advanced control and monitoring solutions for heat-tracing applications, including sensors, thermostats, controllers, and software for optimal performance and reliability.
Preview nVent RAYCHEM Elexant 4020i Single-Point Heat-Tracing Control Module Technical Specifications
Comprehensive technical specifications and product overview for the nVent RAYCHEM Elexant 4020i, a versatile single-point heat-tracing control module featuring a touch screen interface, advanced monitoring, safety features (SIL 2), and multiple communication options for industrial applications.
Preview nVent RAYCHEM E-40 End Seal Kit Installation Guide
Comprehensive installation instructions and technical specifications for the nVent RAYCHEM E-40 End Seal Kit. This guide covers usage conditions, safety warnings, installation steps, and certifications for use with nVent RAYCHEM XTV, KTV, HTV, and VPL heating cables.