ABB TruONE™ ATS: The World's First True Automatic Transfer Switch
A critical breakthrough for critical power, engineered for seamless integration and ultimate reliability.
Introduction to TruONETM ATS
Introducing the TruONETM ATS from ABB, a revolutionary purpose-built automatic transfer switch that integrates switch and controller into one seamless unit. Performance tested beyond standard requirements, TruONETM ensures the steady delivery of critical power at all times. Its self-contained design minimizes wires and connections, speeding installation and enhancing reliability. Predictive maintenance and modular components reduce downtime and service costs, while advanced connectivity prepares it for the future. Uniquely, TruONETM allows emergency manual operation under load for immediate power restoration during equipment malfunctions.
ABB received the Global New Product Innovation Award for its TruONETM ATS.
Key Advantages of TruONETM ATS
The TruONETM ATS offers a comprehensive set of advantages:
01 Detachable HMI
Features three levels of control to meet diverse customer requirements. The Human-Machine Interface (HMI) can be detached for flexible mounting.
Visual Description: An image shows the detachable HMI unit with its screen and controls. Another visual illustrates the all-in-one concept where the controller is integrated into the switch unit, simplifying wiring and installation.
02 All-in-one Concept
This integrated design ensures easy and fast installation.
Easy to Install
Reduces installation time by up to 80%. Unlike traditional ATS solutions requiring multiple components and numerous wires, TruONETM integrates the controller and detachable HMI. It can be installed with a single wire using standard enclosures, significantly cutting down setup and testing time.
Safety and Protection
Reduces the risk of operator injury. TruONETM enables emergency manual operation, even under load, without opening the panel door when the HMI is mounted to the ATS frame. Detaching the HMI for door mounting offers panel designer flexibility. Crucially, dangerous line voltages are not routed to the door, minimizing operator injury risk.
Optimum Interface
Simplifies connectivity. TruONETM features cloud-based connectivity via the ABB Ability™ Energy and Asset Manager, ensuring a common user interface and software environment with other ABB devices. Market-leading modular connectivity supports seven communication protocols for current and future integration.
Enhanced Performance and Efficiency
TruONETM further enhances project speed, operational continuity, energy efficiency, and logistics:
Speed Up Your Project
Automatic commissioning capabilities and pre-made configuration files uploaded from a PC minimize human error and reduce programming time by 80%.
Continuous Operation
Features predictive maintenance, self-diagnostics, and customer-replaceable modules to simplify service and reduce downtime. It provides fast in-phase open transition, ensuring seamless generator use even during business hours.
Energy Efficiency
Full compatibility with ABB Ability™ Energy and Asset Manager enables data processing for performance optimization, remote monitoring of energy consumption, and easier implementation of energy management strategies.
Optimized Logistics
A wide voltage range (200-480 VAC with +/-20% tolerance) reduces the need for stocking multiple SKUs, saving inventory space.
Space Saving
Plug-in factory and field-mount accessories eliminate the need for extra space inside the panel, allowing the use of standard cabinets even for specialized needs.
Reliable in Extreme Conditions
TruONETM exceeds standard requirements for performance and reliability, ensuring dependable operation in challenging electrical, mechanical, and environmental conditions.
It guarantees safe and reliable operation during dramatic variations in temperature (-25°C to +70°C) and voltage (200-480 VAC with +/-20% tolerance). It is also tolerant of vibrations (acc. IEC 60068-2-6) and shocks (acc. IEC 60068-2-27). TruONETM offers true short-circuit resilience, remaining fully operational after exposure to dangerous phenomena.
Visual Description: A diagram visually represents the rigorous testing performed on the TruONE ATS, highlighting its reliability under extreme conditions. It depicts a thermometer indicating a wide temperature range (-25°C to +70°C), a graphic showing resistance to vibrations (indicated by wavy lines), and an icon representing tolerance to shocks.
Applications and Target Users
TruONETM provides superior critical power security for a wide range of applications and users:
For Your Product, Project, or Facility:
- Hospitals
- Sports arenas
- Retail environments
- High-rise buildings
- Commercial buildings
- Financial environments
- Data centers
- And more
Target Users:
- Genset OEMs
- Panel builders
- Consultants and engineers
- Contractors
- Facilities managers
TruONETM is the unique, reliable, all-in-one ATS solution.
TruONETM Part Number Key
An example part number is: ABB TruONE® automatic transfer switch, open transition, 800 amperes, UL, 3 phase + Neutral (3ph, 4 wire), Level 4 controls, 200–480 VAC voltage area, open style, bottom entry.
Category | Description | Example Codes |
---|---|---|
ABB Brand | ABB | ABB |
TruONE® ATS | Automatic Transfer Switch | OX |
ATS Type | Open transition (I-II) | A |
Delayed transition (I-O-II) | B | |
Phase Poles | 1-pole | 1 |
2-pole | 2 | |
3-pole | 3 | |
Controller | Level 2 controls (DIP) | 2 |
Level 3 controls (LCD) | 3 | |
Level 4 controls (Touch) | 4 | |
ATS Size | 30, 60, 100, 125, 160, 200, 260, 400, 600, 800, 1000, 1200 (UL) | 800 |
200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 (IEC) | ||
Standard | UL | U |
IEC | E | |
Neutral | Switched Neutral | S |
Overlapping Neutral | O | |
None | X | |
Voltage Code | 200–480 VAC | Q |
Enclosure Rating | Open style, no enclosure | (blank) |
Enclosed style, IP54 | 54 | |
Cabling Direction (Open Style) | Bottom entry (sources on bottom, load on top) | B |
Top entry (sources on the top, load on the bottom) | T | |
Cabling Direction (Enclosed Style) | Bottom entry (all cable entries from bottom) | B |
Note: For available configurations, consult the ordering information.
ATS Frame Size Visuals
The document illustrates different ATS frame sizes and configurations:
- Open style ATS: Shown for UL 30-200 A, IEC 200-250 A; UL 260 A, IEC 315-400 A; UL 400-600 A, IEC 500-800 A; UL 800-1200 A, IEC 1000-1600 A.
- Enclosed style ATS: Shown for IEC 200-1250 A.
Targeted Product Performance
Key performance specifications for TruONE ATS:
Parameter | 30-400 A (UL) / 200-400 A (IEC) | 260-800 A (UL) / 800-1600 A (IEC) | 630-800 A (UL) / 1000-1250 A (IEC) | 260-600 A (UL) / 800-1200 A (IEC) |
---|---|---|---|---|
ATS Frame Size | (Covered by Ampere ranges) | (Covered by Ampere ranges) | (Covered by Ampere ranges) | (Covered by Ampere ranges) |
Rated operational current (IEC 60947-6-1, GB 14048-11: AC-33B) | 30-400 A | 260-800 A | 630-800 A | 260-600 A |
(GB 14048-11: AC-33iA) | 200-400 A | 800-1600 A | 1000-1250 A | 800-1200 A |
(UL1008: Emergency systems–total system load) | 30-200 A | 260-600 A | (N/A for this range) | 260-600 A |
Short-circuit characteristics Iq (rated conditional short-circuit current) | 100 kA | 100 kA | 100 kA | 100 kA |
Icw (rated short-time withstand current)/Short-time current ratings, 100ms | 18-30 kA | 200 kA | 200 kA | 200 kA |
Icw (rated short-time withstand current)/Short-time current ratings, 500ms | 42 kA | (N/A for this range) | (N/A for this range) | (N/A for this range) |
Withstand and Close-on ratings (any breaker) 480V | 200 kA | (N/A for this range) | (N/A for this range) | (N/A for this range) |
Withstand and Close-on ratings, with current limiting fuses | 30 kA | 50 kA | 50 kA | 50 kA |
Note: See the TruONE technical catalog for confirmed ratings |
TruONETM Feature Comparison
Detailed feature comparison across different control levels:
Level 2 Controls (DIP)
Feature | Specification |
---|---|
Ampere sizes available | IEC: 200-1600 A; UL: 30-1200 A |
Rated voltage | 200-480Vac |
Rated frequency | 50 / 60 Hz |
Phase system | Single and Three |
Number of poles | 2, 3 and 4 |
Neutral configuration | Switched: Yes; Overlapping: No |
Product type | Open transition (I-II): Yes; Delayed transition (I-O-II): Yes |
Voltage and frequency settings | Pickup Voltage Source 1/2: Fixed 2% above dropout; Drop out Voltage Source 1/2: +/-5, 10, 15, 20%; Pickup Frequency Source 1/2: Fixed 1% above dropout; Drop out Frequency Source 1/2: +/-5, 10 % |
Time delay settings | Override momentary Source 1 Outage: 0-30 sec; Transfer from Source 1 to Source 2: 2 sec (0-3600 via Ekip Connect); Override momentary Source 2 Outage: 1.5 sec (0-60 via Ekip Connect); Transfer from Source 2 to Source 1: 0-30 sec; Generator stop delay: 30 secs or 4 mins; Center-OFF delay: 0 or 4 sec; Pre-transfer delay S1 to S2: No; Post-transfer delay S1 to S2: No; Pre-transfer delay S2 to S1: No; Post-transfer delay S2 to S1: No; Load shed delay: No |
Source failure detections | No voltage: Yes; Undervoltage: Yes; Overvoltage: Yes; Phase missing: Yes; Voltage unbalance: Yes; Invalid frequency: Yes; Incorrect phase sequence: Yes |
Controls | DIP + keys |
LED indications for ATS, S1 and S2 status | Yes |
Standard digital inputs/outputs | Open transition: 0 / 1; Delayed transition: 1 / 1 |
Programmable digital inputs/outputs | No |
Auto config (voltage, frequency, phase system) | Yes |
Source priority | Source 1, No priority |
Manual re-transfer | Yes |
In-phase monitor (synchro check) | Yes |
Genset exercising: on-load, off-load | Yes |
In-built power meter module | No |
Load shedding | Yes |
Real time clock | Yes |
Event log | Yes |
Predictive maintenance | No |
Harmonics measuring | No |
Field-mount accessories | Auxiliary contacts for position indication: Yes; Digital input/output modules: No; 12-24 Vdc aux supply module for controller: No; Communication modules: No |
Connectivity | Modbus RTU (RS-485): No; Modbus/TCP: No; Profibus DP: No; ProfiNet: No; DeviceNet: No; Ethernet IP: No |
Monitoring via ABB Ability™: Energy and Asset Manager | No |
For applications | Mains - Mains: Yes; Mains - Generator: Yes (Contact ABB for <40kVA gensets) |
Level 3 Controls (LCD)
Feature | Specification |
---|---|
Ampere sizes available | IEC: 200-1600 A; UL: 30-1200 A |
Rated voltage | 200-480Vac |
Rated frequency | 50 / 60 Hz |
Phase system | Single and Three |
Number of poles | 2, 3 and 4 |
Neutral configuration | Switched: Yes; Overlapping: Yes |
Product type | Open transition (I-II): Yes; Delayed transition (I-O-II): Yes |
Voltage and frequency settings | Pickup Voltage Source 1/2: 71-99%, 101-119%; Drop out Voltage Source 1/2: 70-98%, 102-120%; Pickup Frequency Source 1/2: 80.5-99.5%, 100.5-119.5%; Drop out Frequency Source 1/2: 80-99%, 101-120% |
Time delay settings | Override momentary Source 1 Outage: 0-60 sec; Transfer from Source 1 to Source 2: 0-3600 sec; Override momentary Source 2 Outage: 0-60 sec; Transfer from Source 2 to Source 1: 0-120 sec; Generator stop delay: 0-60 sec; Center-OFF delay: 0-300 sec; Pre-transfer delay S1 to S2: 0-60 sec; Post-transfer delay S1 to S2: 0-60 sec; Pre-transfer delay S2 to S1: 0-60 sec; Post-transfer delay S2 to S1: 0-60 sec; Load shed delay: 0-60 sec |
Source failure detections | No voltage: Yes; Undervoltage: Yes; Overvoltage: Yes; Phase missing: Yes; Voltage unbalance: Yes; Invalid frequency: Yes; Incorrect phase sequence: Yes |
Controls | LCD + keys |
LED indications for ATS, S1 and S2 status | Yes |
Standard digital inputs/outputs | Open transition: 1 / 1; Delayed transition: 2 / 1 |
Programmable digital inputs/outputs | Yes |
Auto config (voltage, frequency, phase system) | Yes |
Source priority | Source 1/2, No priority |
Manual re-transfer | Yes |
In-phase monitor (synchro check) | Yes |
Genset exercising: on-load, off-load | Yes |
In-built power meter module | Yes |
Load shedding | Yes |
Real time clock | Yes |
Event log | Yes |
Predictive maintenance | Yes |
Harmonics measuring | No |
Field-mount accessories | Auxiliary contacts for position indication: Yes; Digital input/output modules: Yes; 12-24 Vdc aux supply module for controller: Yes; Communication modules: Yes |
Connectivity | Modbus RTU (RS-485): Yes; Modbus/TCP: Yes; Profibus DP: Yes; ProfiNet: Yes; DeviceNet: Yes; Ethernet IP: Yes |
Monitoring via ABB Ability™: Energy and Asset Manager | Yes |
For applications | Mains - Mains: Yes; Mains - Generator: Yes |
Level 4 Controls (Touch)
Feature | Specification |
---|---|
Ampere sizes available | IEC: 200-1600 A; UL: 30-1200 A |
Rated voltage | 200-480Vac |
Rated frequency | 50 / 60 Hz |
Phase system | Three |
Number of poles | 3 and 4 |
Neutral configuration | Switched: Yes; Overlapping: Yes |
Product type | Open transition (I-II): Yes; Delayed transition (I-O-II): Yes |
Voltage and frequency settings | Pickup Voltage Source 1/2: 71-99%, 101-119%; Drop out Voltage Source 1/2: 70-98%, 102-120%; Pickup Frequency Source 1/2: 80.5-99.5%, 100.5-119.5%; Drop out Frequency Source 1/2: 80-99%, 101-120% |
Time delay settings | Override momentary Source 1 Outage: 0-60 sec; Transfer from Source 1 to Source 2: 0-3600 sec; Override momentary Source 2 Outage: 0-60 sec; Transfer from Source 2 to Source 1: 0-120 sec; Generator stop delay: 0-60 sec; Center-OFF delay: 0-300 sec; Pre-transfer delay S1 to S2: 0-60 sec; Post-transfer delay S1 to S2: 0-60 sec; Pre-transfer delay S2 to S1: 0-60 sec; Post-transfer delay S2 to S1: 0-60 sec; Load shed delay: 0-60 sec |
Source failure detections | No voltage: Yes; Undervoltage: Yes; Overvoltage: Yes; Phase missing: Yes; Voltage unbalance: Yes; Invalid frequency: Yes; Incorrect phase sequence: Yes |
Controls | Touch + keys |
LED indications for ATS, S1 and S2 status | Yes |
Standard digital inputs/outputs | Open transition: 2 / 1; Delayed transition: 3 / 1 |
Programmable digital inputs/outputs | Yes |
Auto config (voltage, frequency, phase system) | Yes |
Source priority | Source 1/2, No priority |
Manual re-transfer | Yes |
In-phase monitor (synchro check) | Yes |
Genset exercising: on-load, off-load | Yes |
In-built power meter module | Yes |
Load shedding | Yes |
Real time clock | Yes |
Event log | Yes |
Predictive maintenance | Yes |
Harmonics measuring | Yes (Voltage, current) |
Field-mount accessories | Auxiliary contacts for position indication: Yes; Digital input/output modules: Yes; 12-24 Vdc aux supply module for controller: Yes; Communication modules: Yes |
Connectivity | Modbus RTU (RS-485): Yes; Modbus/TCP: Yes; Profibus DP: Yes; ProfiNet: Yes; DeviceNet: Yes; Ethernet IP: Yes |
Monitoring via ABB Ability™: Energy and Asset Manager | Yes |
For applications | Mains - Mains: Yes; Mains - Generator: Yes |
Additional Information
ABB reserves the right to make technical changes or modify the contents of this document without prior notice. Agreed particulars shall prevail for purchase orders. ABB Inc. does not accept responsibility for potential errors or lack of information in this document. All rights are reserved in this document and its contents. Reproduction, disclosure to third parties, or utilization of its contents, in whole or in part, is forbidden without prior written consent of ABB Inc.
Contact Information:
ABB Inc. Electrification Products
8155 T&B Boulevard
Memphis, TN 38125
Customer Service: 800-816-7809 (7:00 a.m. - 5:30 p.m., CST, Monday-Friday)
Email: elec_custserv@tnb.com
Technical Support: 888-385-1221, Option 1 (7:00 a.m. - 5:00 p.m., CST, Monday-Friday)
Email: lvps.support@us.abb.com
Copyright © 2021 ABB. All rights reserved. Specifications subject to change without notice.
Document Number: 1SCC303007B0201