User Manual for Dyness models including: BX51100, 5.12kWh Lithium Batteries, BX51100 5.12kWh Lithium Batteries, Lithium Batteries, Batteries

zhangweizhong

User Manual

BX51100 Unit User Manual. BX51100 lithium iron phosphate battery energy storage ... This user manual details the basic structure, parameters, basic procedures and methods...

BX51100 User Manual - Solar Advice

28 ott 2021 — product manual, relevant contract or relevant laws and regulations. ... (2) When the battery works with GOODWE、Solis、LUX、Sofar、DEYE、VICTRON、.

Oct 28, 2021 — ○Please do not put the battery into water or fire, in case of explosion or any other situation that might endanger your life.


File Info : application/pdf, 26 Pages, 1.20MB

Dyness-BX51100-User-Manual
BX51100
User Manual

BX51100 User Manual
Contents
Statement of Law.......................................................................................................... 2 Safety Precautions.........................................................................................................3 Preface........................................................................................................................... 4 1 Introduction............................................................................................................... 4
1.1 Brief Introduction........................................................................................................... 4 1.2 Product Properties..........................................................................................................4 1.3 Product identity definition.............................................................................................5
2 Product Specification.................................................................................................5
2.1 Size and Weight.............................................................................................................. 5 2.2 Performance Parameter................................................................................................. 5 2.3 Interface Definition........................................................................................................ 5
2.3.1 DIP switch definition and description..................................................................................... 6
2.4 Battery Management System(BMS).............................................................................. 9
2.4.1 Voltage Protection..................................................................................................................9 2.4.2 Current Protection................................................................................................................. 9 2.4.3 Temperature Protection...................................................................................................... 10 2.4.4 Other Protection.................................................................................................................. 10
3 Installation and Configuration................................................................................11
3.1 Preparation for installation..........................................................................................11
3.1.1 Environmental requirements............................................................................................... 11 3.1.2 Tools and data...................................................................................................................... 11 3.1.3 Technical preparation.......................................................................................................... 12 3.1.4 Unpacking inspection........................................................................................................... 12 3.1.5 Engineering coordination.....................................................................................................14
3.2 Equipment installation................................................................................................. 14
3.2.1 Installation preparation........................................................................................................ 15 3.2.2 Mechanical installation......................................................................................................... 15 3.2.3 Electrical installation............................................................................................................ 17 3.2.4 Battery parameter settings on the inverter.........................................................................20 3.2.5 Register on the website after installation............................................................................20
4 Use, maintenance and troubleshooting................................................................. 21
4.1 Battery system usage and operation instructions...................................................... 21 4.2 Alarm description and processing............................................................................... 21 4.3 Analysis and treatment of common faults.................................................................. 22
I

Statement of Law

BX51100 Unit User Manual

Copyright of this document belongs to Daqin New Energy Tech (Taizhou) Co., Ltd.

No part of this documentation maybe excerpted, reproduced, translated,annotated or duplicated in any form or by any means without the prior written permission of Daqin New Energy Tech (Taizhou) Co., Ltd. All Rights Reserved.

This product complies with the design requirements of environmental protection and personal safety. The storage, use and disposal of the products shall be carried out in accordance with the product manual, relevant contract or relevant laws and regulations.

Customer can check the related information on the website of Daqin New Energy Tech (Taizhou) Co., Ltd when the product or technology is updated.
Web URLhttp://www.dyness-tech.com.cn Please note that the product can be modified without prior notice.

Revision History

Revision NO. Revision Date

1.0

2021.01.10

Revision Reason
First Published

2

Safety Precautions

BX51100 Unit User Manual

Warning
Please do not put the battery into water or fire, in case of explosion or any other situation that might endanger your life. Please connect wires properly while installation, do not reverse connect. To avoid short circuit, please do not connect positive and negative poles with conductor on the same device. Please avoid any form of damage to battery, especially stab, hit, trample or strike. Please shut off the power completely when removing the device or reconnecting wires during the daily use or it could cause the danger of electric shock. Please use dry powder extinguisher to put out the flame when encountering a fire hazard, liquid extinguisher could result in the risk of explosion. For your safety, please do not arbitrarily dismantle any component in any circumstances. The maintenance must be implemented by authorized technical personnel or our company's technical support. Device breakdown due to unauthorized operation will not be covered under warranty.

Caution
Our products have been strictly inspected before shipment. Please contact us if you find any
abnormal phenomena such as device outer case bulging. The product shall be grounded properly before use in order to ensure your safety. To assure the proper use please make sure parameters among the relevant device are compatible and matched. Please do not mixed-use batteries from different manufacturers, different types and models, as well as old and new together. Ambient and storage method could impact the product life span, please comply with the operation environment instruction to ensure device works in proper condition. For long-term storage, the battery should be recharged once every 6 months, and the amount of electric charge shall exceed 80% of the rated capacity. Please charge the battery in 18 hours after it fully discharged or over-discharging protection mode is activated. Formula of theoretical standby time: T=C/I (T is standby time, C is battery capacity, I is total current of all loads).

3

Preface
Manual declaration

BX51100 Unit User Manual

BX51100 lithium iron phosphate battery energy storage system can be combined in series or parallel to provide energy storage function for photovoltaic power generation users. Our product can store extra electricity into battery from photovoltaic power generation system in daytime and supply stable power to user's equipment as power backup at nighttime or any time when needed. It can improve the efficiency of photovoltaic power generation and increase the electric power efficiency by peak load shifting.
This user manual details the basic structure, parameters, basic procedures and methods of installation and operation and maintenance of the equipment.

4

BX51100 Unit User Manual
1 Introduction
1.1 Brief Introduction
BX51100 lithium iron phosphate battery system is a standard battery system unit, customers can choose a certain number of BX51100 according to their needs, by connecting parallel to form a larger capacity battery pack, to meet the user's long-term power supply needs. The product is especially suitable for energy storage applications with high operating temperatures, limited installation space, long power backup time and long service life.
1.2 Product Properties
BX51100 energy storage product's positive electrode materials are lithium iron phosphate, battery cells are managed effectively by BMS with better performance, the system's features as below:
Comply with European ROHS, Certified SGS, employ non-toxic, non-pollution environment-friendly battery. Anode materials are lithium iron phosphate (LiFePO4), safer with longer life span. Carries battery management system with better performance, possesses protection function like over-discharge, over-charge, over-current, abnormal temperature. Self-management on charging and discharging, Single core balancing function. Intelligent design configures integrated inspection module. Flexible configurations allow parallel of multi battery for longer standby time. Self-ventilation with lower system noise. Less battery self-discharge, then recharging period can be up to 10 months during the storage. No memory effect so that battery can be charged and discharged shallowly. With wide range of temperature for working environment, -20 ~ +55, circulation span and discharging performance are well under high temperature. Less volume, lighter weight.
4

1.3 Product identity definition

BX51100 Unit User Manual

Battery voltage is higher than safe voltage, direct contact with electric shock hazard.
inflammable.
Read the user manual before using.
The scrapped battery cannot be put into the garbage can and must be professionally recycled. After the battery life is terminated, the battery can continue to be used after it recycled by the professional recycling organization and do not discard it at will.
Do not place near open flame or incinerate.
If catch fire, do not put out with water.
If catch fire, do not put out with dry powder fire extinguisher.
Do not cut or spear with sharp objects.

5

2 Product Specification

BX51100 Unit User Manual

2.1 Size and Weight

Table 2-1 BX51100 Device size

Product

Nominal Voltage

BX51100

DC51.2V

Nominal Capacity
100Ah

Dimension 558×545×150mm

Weight 50kg

2.2 Performance Parameter
Table 2-2 BX51100 performance parameter Item

Parameter value

Nominal Voltage(V)

51.2

Work Voltage Range(V)

44.8~57.6

Nominal Capacity(Ah)

100

Nominal Energy(kWh)

5.12

Recommended Charge/Discharge Current (A)

50

Max. Power Charge/Discharge Current (A)

80

Peak Power Charge/Discharge Current (A)

100 (15S)

Charge Voltage (Vdc)

57

2.3 Interface Definition
This section elaborates the interface functions of the front interface of the device.
1

2

3 4 5 67 8 9 10

Figure2-1 The sketch of interface.

11 12

5

Table 2-3 Interface Definition

BX51100 Unit User Manual

Item Name

Definition

1

Power switch

OFF/ON, must be in the "ON" state when in use

2

Positive socket Battery output positive or parallel positive line

3

ADD

DIP switch

SW (battery

When the "OFF/ON" switch button is in the ON state, press

4

wake/sleep

and hold this button for 3 seconds to put the battery into the

switch)

power-on or off state.

5

SOC

The number of green lights shows the remaining power. Table 2-3 for details.

Red light flashing when an alarm occurs, red light always on

6

ALM

during protection status. After the condition of trigger

protection is relieved, it can be automatically closed.

7

RUN

Green light flashing during standby and charging mode. Green light always on when discharging.

8

COM

Communication cascade port, support RS232

9

CAN/485

Communication cascade port, support CAN/ RS485 communication (factory default CAN communication)

10

DRY CONTACT

/

11

Negative socket Battery output negative or parallel negative line

12

Grounding

Shell ground connection

2.3.1 DIP switch definition and description

Table 2-4 Interface Definition DIP switch position (master communication protocol and baud rate selection)

#1

#2

#3

#4

Define different protocols Distinguish between master and slave

Baud rate selection OFFCAN: 500K,485: 9600 ONCAN: 250K,485: 115200

DIP switch description:
When the batteries are connected in parallel, the host communicates with the slaves through the CAN interface. The host summarizes the information of the entire battery system and communicates with the inverter through CAN or 485. The connection mode is divided into the following two cases:

6

BX51100 Unit User Manual 1. If the master is the latest BX51100 battery with DIP switch: (1) The communication cable from the master CAN IN to the inverter comm port should be the correct one. (2) When the battery works with GOODWESolisLUXSofarDEYEVICTRON IMEONInfinisolarSungrowSMARENACDELIOSSAJ(CAN Comm) ,before starting the battery,you need put the master DIP switch "# 3" to the "ON" position (to the top), then turn on the batteries.
Master Setting 1
(3) If the battery communicates with the Axpert-king,Axpert-VMIII,Growatt SPH/SPA(CAN comm)GMDESaj(485 comm), turn the master DIP switch "#2" to "ON" position.
Master Setting 2
(4) If the battery communicates with the Growatt SPF HVM-P/ES/WPV by RS485 communication, turn the master DIP switch "#2" and "#3" to "ON".
Master Setting 3
(5) If the battery communicates with the Schneider Conext Series, turn the master DIP switch "#1" and "#3" to "ON".
Master Setting 4
(6) When you setup the master DIP as setting 1~4,all the slaves keep the DIP 0000,no need change. (7) If the energy storage system has only one BX51100, it is the master itself, and still follow the above steps. Note: For more information of matching inverter brands, please subject to the latest document <The list of compatibility between Dyness ESS and Inverters >.
Front

Plug

Socket of communication port

CAN/485

Figure 2-2 CAN/485 interface definition

7

Table 2-5 Pin Definition
Foot position PIN1 PIN2 PIN3 PIN4 PIN5 PIN6 PIN7 PIN8 PIN9 PIN10 PIN11 PIN12 PIN13 PIN14 PIN15 PIN16

Color Orange/white Orange Green/white Blue Blue/white Green Brown/white Brown Orange/white Orange Green/white Blue Blue/white Green Brown/white Brown

BX51100 Unit User Manual
Definition 485B 485A XGND CANH CANL Reserve XIN Reserve Reserve Reserve XGND CANH CANL Reserve XOUT Reserve

Foot position PIN1 PIN2 PIN3 PIN4 PIN5 PIN6

Definition Reserve GND TXD RXD GND Reserve

Figure 2-3 COM interface definition
Tips: Please pay attention of the communication com definition of inverter, in order to avoid voltage in the port to affect communication.

8

Table 2-6 LED status indicators

BX51100 Unit User Manual

Battery Status Shutdown
Standby

SOC
/ 80%SOC100% 60%SOC80% 40%SOC60% 20%SOC40%
0%SOC20%
SOC=0
SOC=100%

LED1 off     
off 

LED2 off     off
off 

LED3 off    off off
off 

LED4 off   off off off
off 

LED5

ALM

RUN

off

off

off



off

Flashing

off

off

Flashing

off

off

Flashing

off

off

Flashing

off Flashing Flashing

off

Flashing /

Flashing



off

Flashing

80%SOC100%









Flashing

off

Flashing

60%SOC80%



Charging

40%SOC60%







Flashing

off



Flashing

off

off

off

Flashing

off

Flashing

20%SOC40%



Flashing

off

off

off

off

Flashing

0%SOC20% Flashing

off

off

off

off

off

Flashing

80%SOC100%











off



60%SOC80%









off

off



40%SOC60%







off

off

off



Discharging 20%SOC40%





off

off

off

off



0%SOC20%



off

off

off

off Flashing



SOC=0

off

off

off

off

off

Flashing /

Flashing/

A special ALM light flashing state: when the communication between batteries is lost or abnormal,all the lights from SOC to RUN of the master battery will flash

together.

 means green light always on

 means red light always on

Flashing: means green light flashing or red light flashing

2.4 Battery Management System(BMS)

2.4.1 Voltage Protection

Low Voltage Protection in Discharging 
When any battery cell voltage or total voltage is lower than the rated protection value during discharging, the over-discharging protection is activated, and the battery buzzer makes an alarm sound. Then battery system stops supplying power to the outside. When the voltage of each cell back to rated return range, the protection is over.

Over Voltage Protection in Charging Battery will stops charging when total voltage or any battery cell voltage reaches the rated protection value during charging stage. When total voltage or all cell back to rated range, the protection is over.
2.4.2 Current Protection
Over Current Protection in Charging

9

BX51100 Unit User Manual When the charge current  90A, current limit protection mode is activated, current will be limited to 3Aprotection is removed after rated time delaying 10S. Circulate like this until the current is lower than 90A. Over Current Protection in Discharging When the discharge current is higher than 100A, the battery buzzer alarms and the system stops discharging after 15s. After protection, the discharging will restore in 60s delay or immediately when there is charging current.
Caution:
The buzzer sound alarm setting can be manually turned off on the background software, and the factory default is on.
2.4.3 Temperature Protection
Low/Over temperature protection in charging When battery's temperature is beyond range of -5  ~+55  during charging, temperature protection is activated, device stops charging. The protection is over when temperature back to rated working range.
Low/Over temperature protection in discharging When battery's temperature is beyond range of -20  ~+55  during discharging, temperature protection is activated, device stops supplying power to the outside. The protection is over when temperature back to rated working range.
2.4.4 Other Protection
Short Circuit Protection When the battery is activated from the shutdown state, if a short circuit occurs, the system starts short-circuit protection for 60 seconds. Self-Shutdown When device connects no external loads and power supply and no external communication for over 72 hours, device will dormant standby automatically.
Caution
Battery's maximum discharging current should be more than load's maximum working current.
10

BX51100 Unit User Manual
3 Installation and Configuration
3.1 Preparation for installation
Safety Requirement
This system can only be installed by personnel who have been trained in the power supply system and have sufficient knowledge of the power system. The safety regulations and local safety regulations listed below should always be followed during the installation.
 All circuits connected to this power system with an external voltage of less than 51.2V must meet the SELV requirements defined in the IEC60950 standard.
 If operating within the power system cabinet, make sure the power system is not charged. Battery devices should also be switched off.
 Distribution cable wiring should be reasonable and has the protective measures to avoid touching these cables while operating power equipment.
 when installing the battery system, must wear the protective items below:

The isolation gloves

Safety goggles

Safety shoes

Figure3-1

3.1.1 Environmental requirements
Working temperature: -20 ~ +55 Charging temperature range is 0oC~+55, Discharging temperature range is -20 ~+55 Storage temperature: -10~ +35 Relative humidity: 5% ~ 85%RH Elevation: no more than 4000m Operating environment: Indoor installation, sites avoid the sun and no wind, no conductive dust and corrosive gas. And the following conditions are met:
 Installation location should be away from the sea to avoid brine and high humidity environment.
 The ground for product arrangement shall be flat and level.  No flammable explosive materials near the installation site.
 The optimal ambient temperature is 15~ 30 
 Keep away from dust and messy zones
3.1.2 Tools and data
Tools and meters that may be used are shown in table 3-1. Table 3-1 Tool instrument

ScrewdriverSlottedPhillips Torque wrench Diagonal pliers
Pointed nose pliers Pliers to hold the wire
Stripping pliers Electric drill

Name

Multimeter Clamp current meter
Insulation tape Temperature meter Anti-static bracelet
Cable tie Tape measure

11

3.1.3 Technical preparation

BX51100 Unit User Manual

Electrical interface check Devices that can be connected directly to the battery can be user equipment, power supplies, or other power supplies.  Confirm whether the user's PV power generation equipment, power supply or other power supply equipment has a DC output interface, and measure whether the DC power output voltage meets the voltage range requirements in Table 2-2.  Confirm that the maximum discharge current capability of the DC power interface of the user's photovoltaic power generation equipment, power supply or other power supply equipment should be higher than the maximum charging current of the products used in Table 2-2.
If the maximum discharge capacity of the DC power interface of the user's photovoltaic power generation equipment is less than the maximum charging current of the products used in Table 2-2, the DC power interface of the user's photovoltaic power generation equipment shall have a current limiting function to ensure the normal operation of the user's equipment.  Verify that the maximum operating current of the battery-powered user equipment (inverter DC input) should be less than the maximum discharge current of the products used in Table 2-2.

The security check  Firefighting equipment should be provided near the product, such as portable dry
powder fire extinguisher.  Automatic fire fighting system shall be provided for the case where necessary.  No flammable, explosive and other dangerous materials are placed beside the battery.

3.1.4 Unpacking inspection
 When the equipment arrives at the installation site, loading and unloading should
be carried out according to the rules and regulations, to prevent from being exposed to
sun and rain.  Before unpacking, the total number of packages shall be indicated according to the
shipping list attached to each package, and the case shall be checked for good condition.  In the process of unpacking, handle with care and protect the surface coating of the
object.  Open the package, the installation personnel should read the technical documents, verify
the list, according to the configuration table and packing list, ensure objects are complete
and intact, if the internal packing is damaged, should be examined and recorded in detail.

12

Packing list is as follows:

Item

Specification

Quantity

Battery-BX51100

51.2V/100Ah

1

Parallel cablepositive

Red /25mm2/L250mm

1

Parallel cablenegative

Black /25mm2/L250mm

1

Communication parallel cable

Black /L500mm/Double
RJ45 plug

1

Communication cable-to inverter

Black /L2000mm /Double
RJ45 plug

1

Ground wire

L500mm,4mm²

1

User Manual

User manual

1

Screw

screws M6

8

Expansion screw

Expansion screw

8

cardboard

Positioning cardboard

1

BX51100 Unit User Manual
Figure
13

Battery bracket Battery bracket

1

BX51100 Unit User Manual

Fixing bracket Fixing bracket

1

3.1.5 Engineering coordination
Attention should be paid to the following items before construction:  Power line specification.
The power line specification shall meet the requirements of maximum discharge current for each product.  Mounting space and bearing capacity. Make sure that the battery has enough room to install, and that the brackets have
enough load capacity.  Wiring.
Make sure the power line and ground wire are reasonable. Not easy to short-circuit, water and corrosion.
3.2 Equipment installation

Table 3-2 Installation steps

Step1 Step 2

Installation preparation
Mechanical installation

Step3

Electrical installation

Step4

Battery system self-test

Step5

Connecting inverter

Confirm that the ON/OFF switch on the front panel of BX51100 unit is in the "OFF" state to ensure no live operation.
1. Battery placement position determination
2. Battery module installation
1. Ground cable installation
2. Battery module parallel cable installation
3. Parallel communication cable connection 1. Turn the ON/OFF switch to the "ON" state 2. Press SW button 3S to wake up battery 3. Check the system output voltage and led status 4. Shut down the system 1. Connect total positive & total negative cable of the battery system to the inverter 2. Battery module total positive cable installation 3. Battery module total negative cable installation 4. Connect the communication cable from the master CAN IN to the inverter 5.Turn on the Power switch and wake up system by SW button 6.Close the DC breaker between inverter and battery 7.Turn on the inverter and check the communication between inverter and battery system

14

3.2.1 Installation preparation

BX51100 Unit User Manual

1. Prepare equipment and tools for installation. 2. Check the BX51100 unit and confirm that the ON/OFF switch is in the "OFF" state to
ensure the device is shut off.
3.2.2 Mechanical installation (1) Brackets Installation:

1. BX51100 brackets The BX51100 bracket is shown before installation as shown in figure3-2.

Figure3-2

2. Place the BX51100 and brackets as shown in the figure3-3, and insert the BX51100 into the brackets. Each bracket is connected to the module by four screws, two screws on one side. Twisting force keeps 9.8N·m. As shown in figure3-3.

Figure3-3

3. Install another pair of brackets on the first one, fixed by screws between them. Twisting force keeps 9.8N·m. Two screws are required for each bracket as shown in figure3-4.

Figure3-4
15

4. Insert the second BX51100 into the brackets.

BX51100 Unit User Manual

5. Stack the required number of battery and bracket combinations as described above, and fix the screws. Shown as Figure3-6.

Figure3-5

(2) Wall hanging Installation method:
1. Use the positioning cardboard (provided in accessory package) and mark the screw hole positions on the wall, as shown on the right.
2. The cardboard must be perpendicular to the ground while drawing the holes.
3. The bottom of the cardboard is about 300mm from the ground.
4. According to the position of the mark, 8 holes in diameter 10mm and depth of more than 70mm are hit on the wall with an electric drill, which are used for fitting expansion bolt M6.

Figure3-6
Figure3-7
16

5. Fixing the expansion bolt M6 into the bottom of the hole on the wall, and fix the Support bracket and Battery bottom bracket on the wall with M6 bolts. Twisting force keeps 9.8N·m.

BX51100 Unit User Manual

6. Carry or hoist the battery box to the installed Battery bottom bracket. Fixing the Support bracket and the upper part of the battery box with M6 bolts, twisting force keeps 9.8N·m.Then fixing the Battery bottom bracket and the bottom part of the battery box with M6 bolts. Twisting force keeps 9.8N·m.

Figure3-8

Figure3-9

3.2.3 Electrical installation
Before connecting the power cables, use multimeter to measure cable continuity, short circuit, confirm positive and negative, and accurately mark the cable labels. Measuring methods
 Power cable check: select the buzzer mode of multimeter and detect the both ends of the same color cable. If the buzzer calls, it means the cable is in good condition.
 Short circuit judgment: choose multimeter resistor file, probe the same end of positive
and negative pole, if the resistor shows infinity, means that the cable is available.
 After visual testing of power line connection, the positive and negative poles of the
battery shall be connected respectively to the positive and negative poles of the opposite terminal. It is better to add a circuit breaker between the inverter and the battery system. The selection of the circuit breaker requires:
Voltage: U>60V

Inverter power

Current: I =

45V

The circuit breaker is installed between the battery module and the inverter, as shown in Figure

3-10:

17

BX51100 Unit User Manual 18

Circuit breaker
Power cablepositive
Parallel cablepositive

BX51100 Unit User Manual
Inverter Communication cable-to inverter Power cablenegative
Parallel cablenegative
Communication parallel cable

Master Setting 1

Master Setting 2

Master Setting 3

Master Setting 4

Slave Setting 1

Figure3-10 Note: 1. For more ADD SettingsReference 2.3.1 "DIP switch definition and description" 2. After the whole system connection, set the master DIP mode according to the inverter model firstly, then start the battery. 3. The BAT-INV comms cable is from inverter comm port to master CAN IN port, BAT-BAT cable is from master CAN OUT to slave1 CAN IN, slave1 CAN OUT to slave2 CAN IN... 4. Each pair of power cable, it's limited continuous current is 200A, so if the inverter Max. work current more than 200A, please add power cable according to the proportion.

19

3.2.4 Battery parameter settings on the inverter
Max Charging(Bulk) Voltage: 57V Absorption Voltage: 56.5V Float Voltage: 56V Shut Down(cut off) Voltage: 50V Shut Down(cut off) SOC: 20% Restart Voltage: 52V Max Charge Current: 50A*battery QTY Max Discharge Current: 50A*battery QTY
3.2.5 Register on the website after installation

BX51100 Unit User Manual

After the battery system installation is completed and the running is normal, you need to log

in to the DYNESS official website to register the product installation and use information to

make the product warranty effective. Please follow the instructions on the website to register.

http://www.dyness-tech.com.cn

Service

Sign Up

20

BX51100 Unit User Manual
4 Use, maintenance and troubleshooting
4.1 Battery system usage and operation instructions
After completing the electrical installation, follow these steps to start the battery system. 1. Refer to the description of the DIP switch of 2.3.1 to prepare the battery module before starting up, then press the ON/OFF button to the ON position, press and hold the SW button for 3 seconds. 2. After the indicator self-test, the RUN indicator will light and the SOC indicator will be on (100% SOC status in the Figure4-1).

DIP ON SW

SOC ALM RUN COM

CAN/485 IN OUT

DRY CONTACT

Figure4-1
Caution:
1. After pressing the power button, if the battery status indicator on the front panel continues to be red, please refer to the "4.2 Alarm description and processing ". If the failure cannot be eliminated, please contact the dealer timely.
2. Use a voltmeter to measure whether the voltage of the circuit breaker battery access terminal is higher than44.8V, and check whether the voltage polarity is consistent with the inverter input polarity. If the circuit breaker battery input terminal has a voltage output and is greater than 44.8V, then the battery begun to work normally.
3. After confirming that the battery output voltage and polarity are correct, turn on the inverter, close the circuit breaker.
4. Check if the indicator of the inverter and battery connection (communication indicator and battery access status indicator) is normal. If it is normal, successfully complete the connection between the battery and the inverter. If the indicator light is abnormal, please refer to the inverter manual for the cause or contact the dealer.
4.2 Alarm description and processing
When protection mode is activated or system failure occurred, the alarm signal will be given through the working status indicator on the front panel of the BX51100. The network management can query the specific alarm categories.
21

BX51100 Unit User Manual If the fault such as single cell over voltage, charging over-current, under-voltage protection, high-temp protection and other abnormalities which affects the output, please deal with it according to Table 4-1.
Table 4-1 Main alarm and Protection

Statue Charge state

Alarm category Over-current High temp

Alarm indication RED
Buzzer start
RED

Processing Stop charging and find out the cause of the trouble
Stop charging

Over-current

Discharge state

High temp
Total voltage undervoltage Cell voltage undervoltage

RED Buzzer start
RED
RED Buzzer start
RED Buzzer start

Stop discharging and find out the cause of the trouble Stop discharging and find out the cause of the trouble
Start charging
Start charging

4.3 Analysis and treatment of common faults

Analysis and treatment of common faults in the Table 4-2:

Table 4-2 Analysis and treatment of common faults

No. Fault phenomenon

Reason analysis

Solution

The indicator does

1 not respond after the Total voltage lower than 37.3V Check the total voltage

power on

Battery data status is abnormal. Read the battery

2 No DC output

Battery gets into over-discharged information on the

protection

monitor.

3

The DC power supply time is too short

Battery capacity become smaller

Storage battery replacement or add more modules

4

The battery can't be fully charged to 100%

Charging voltage is too low

Adjust charging voltage at 57V or 57.6V

The power cable

Turn off the battery, check

5 sparks once power on Power connection short-circuit the cause of the short

and ALM light RED

circuit

The DIP setting of the host is

wrong/ the battery type of the

inverter is wrong/

Communication cable used

6

Communication fault

incorrectly/The communication cable is incorrectly connected at the battery communication port

Check these possible causes one by one

or the inverter communication

port/The battery firmware

version is too low to support the

inverter

If you need any technical help or have any question, please contact the dealer in time.

22

DAQIN NEW ENERGY TECH (TAIZHOU) Co.,LTD Address: Building 13, Jiangyan Industrial Park, Sanshui Street, Jiangyan District, Taizhou City, Jiangsu Province225500
Email: sales@dyness-tech.com Website: www.dyness-tech.com.cn



References

WPS 文字 3-Heights™ PDF Optimization Shell 6.3.1.5 (http://www -tools.com)