Package Unit Modulating Economizer Installation Instructions

For Downflow Economizer Models # 562533 / 563209

For 2-5T Convertible Package Units (AC, HP OR GAS ELECTRIC)

Product Certification and Safety

This product is certified to meet California Title 24, Part 6 Low Leak and FDD requirements.

Warning: Recognize this symbol ⚠️ as an indication of Important Safety Information!

  • Read all instructions prior to installation.
  • Disconnect electrical power to the unit before servicing.
  • Failure to do so can cause electrical shock resulting in personal injury or death.
  • Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer or service agency.

DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

Before You Begin

Reference Unit Technical Service Literature for application requirements.

Inspect economizer for shipping damage and correct parts with list below:

  • 1 - Economizer Assembly w/ Filter installed
  • Upper Adaptor Panels (See Table 1 on Page 2)
  • 1 - Side Adaptor Panel
  • 1 - Outdoor Air Hood (Attached to Economizer)
  • 1 - Hardware Package
  • 1 - Mixed Air Sensor (MAS)
  • 1 - Mixed Air Sensor Wiring Harness
  • 2 - 8" Wire Tie
  • 3 - #10 x 16 x ½" Self-Tapping Screws
  • 13 - #10 x 16 x 1½" Type A Screws

Note: For rooftop or other installations that require the economizer to be lifted or hoisted, always lift economizer with the supplied packaging in place to prevent damage from lifting and rigging equipment.

Optional Accessory Kits:

  • CO2 Sensor Kit, Wall Mount (920317)
  • CO2 Sensor Kit, Duct Mount (920318)
  • Differential Enthalpy Kit (922431)
  • HP isolation relay kit (older heat pump models) (922598)
  • Power Exhaust Kit (547842, 555578)
Figure 1: Economizer assembly with adaptor panels and hood.

Diagram showing the economizer assembly with upper and side adaptor panels, and an outdoor air hood.

Figure 2: Unit Dimensions and Shipping Information.
Unit#ABCDEFGHIJKHeightLengthWidthWeight
56253347.5937.5618.7328.8610.7912.548.1818.9018.0027.5028.253557 ½20 ½109
56320951.0341.0618.7532.2914.2917.3418.0031.0831.833557 ½20 ½112

Installation Steps

Figure 3: Exploded view of the downflow economizer unit.

Diagram showing the components of the downflow economizer unit: Economizer Assembly, Upper Adaptor Panels (1, 2, 3), Side Adaptor Panel, Economizer Top Pan, Economizer Face Panel, and Fresh Air Hood.

UNIT HEIGHT (WITH BASE RAILS)*UPPER PANEL CLOSE-OFFUSED w/ UNIT#
35"PANEL 1 - 22" x 3"562533
39"PANEL 1 - 22" x 3"563209
43"PANEL 2 - 22" x 7"
47"PANEL 3 - 22" x 11"

Step 1: Shutdown unit and disconnect from electrical power.

Step 2: Remove the return access panel. (Save screws.)

Step 3: Using CAUTION not to puncture coil tubing, align holes and place the tab on the side panel on the return side of divider wall and secure with self-tapping screw provided.

Step 3a: (Optional) Install differential enthalpy control and DCV (CO2) sensor according to that kit's instructions. (See products technical service literature.)

Step 4: Install economizer in unit, attaching only left and right side mounting screws. Ensure economizer rails sit flush on return air opening lip. Use CAUTION not to tear insulation on unit side wall or floor. (Use screws that were removed in Step 2.) (See wiring diagram attached.)

Step 5: Screw side panel in place.

Step 6: Remove economizer top pan and face panels. Locate unit economizer plug (S1) in return air compartment (top right corner). Remove jumper wire and zip tie it to economizer wiring harness. Connect economizer plug (P1) to unit plug (S1). Inspect all wiring and linkage connections for security and proper operation. Secure all loose wires with a 6" wire tie. Ensure that wires are protected from all sharp edges, inadvertent grounding, and will not become entangled with filter or moveable vanes.

Step 6a (Optional) If installed, make sure differential enthalpy control and DCV (CO2) sensor wiring connections are made in accordance with that kit's instructions.

Step 7: Remove unit blower access panel and install mixed air sensor in appropriate location (as shown in Figure 4) with two #10 Type A screws provided and then make electrical connection. Replace blower access panel.

Figure 4a: Mixed Air Sensor Installation (Gas/Electric).

Diagram showing the placement of the Mixed Air Sensor (MAS) for Gas/Electric unit configurations.

Figure 4b: Mixed Air Sensor Installation (Electric/Electric or Heat Pump).

Diagram showing the placement of the Mixed Air Sensor (MAS) for Electric/Electric or Heat Pump unit configurations.

Step 8: Return power to unit, Setup and configure economizer. (See Appendix A on page 5)

Step 9: Install appropriate upper close-off panel and replace face panel and top panel and secure with screws (See Table 1). Ensure all mounting screws, panels, and doors are installed.

Notes to Installer

  • When this economizer is used in conjunction with heat pumps, unit WHITE wire from economizer plug pin #7 MUST be relocated from defrost control board "T1" to low voltage terminal board "A1".
  • When this economizer is used with any 2-5 ton package unit (Gas/Electric, A/C, or Heat Pump) WITHOUT A COMMERCIAL THERMOSTAT, the GREEN wire from economizer plug pin #1 MUST be relocated from low voltage terminal board "G" to low voltage terminal board "R" to force dampers to remain in minimum position 100 percent of the time, while in heating mode, to meet the minimum fresh air requirements. When used in conjunction with a commercial thermostat, see Note 2 on wiring diagram.
  • Some older 2-5T package heat pumps may not be equipped with a reversing valve isolation relay, required for use with economizers that have a Jade control system. Nordyne kit #922598 is required for these applications.

Maintenance

Return Air Filter Replacement

Recommended every 30 days. (Filter size: 16 x 16 x 1)

Step 1: Remove economizer face panel and side screws of top pan.

Step 2: Slide filters out (2) and replace with new filters.

Step 3: Replace face panel and secure all screws.

Figure 5: Filter Replacement Procedure.

Diagrams illustrating the removal of the economizer face panel for filter replacement.

Fresh Air Filter Cleaning

Recommended every 3 months.

Step 1: Remove lower section of fresh air hood to access washable filters. (4 screws)

Step 2: Remove filters (2) and clean with water and a mild detergent.

Step 3: Taking note of "Air Flow Direction" marking on filter frame, reinstall the filters and fresh air filter access cover, securing all screws.

Figure 6: Fresh Air Filter Cleaning Procedure.

Diagrams illustrating the removal of the fresh air filter access cover for cleaning.

Appendix A: Controller and Operation Details

User Interface

The user interface consists of an LCD display and a 4-button keypad on the front of the Economizer module. The LCD is a 16 character by 2 line dot matrix display.

Power Up Cycle

All setpoints and advanced settings are restored after any power loss (a power loss is assumed if voltage falls below 18 Vac). Normal operation is restored when power returns above 18 Vac.

Initial Menu Display

On initial startup, Honeywell displays on the first line and Economizer W7220 on the second line. After a brief pause, the revision of the software appears on the first line (second line is blank). It then displays W7220 on the first line and STATUS on the second line.

Figure 7: Honeywell W7220 Controller Interface.

Illustration of the Honeywell W7220 Economizer controller module's LCD display and 4-button keypad, labeling the buttons: MENU UP (EXIT), SELECT (ENTER), SCROLL (UP/DOWN).

Keypad

The four navigation buttons illustrated in Figure 7 are used to scroll through the menus and menu items, select menu items, and to change parameter and configuration settings.

Using the Keypad with Menus

  • Press the ⬆ button to move to the previous menu.
  • Press the ⬇ button to move to the next menu.
  • Press the ➡️ button (Enter) to display the first item in the currently displayed menu.
  • Press the ↖ button (Menu up) to exit a menu's item and return to the list of menus.

Using the Keypad with Settings and Parameters

  • Navigate to the desired menu.
  • Press the ➡️ button (Enter) to display the first item in the currently displayed menu.
  • Use the ⬆ and ⬇ buttons to scroll to the desired parameter.
  • Press the ➡️ button (Enter) to display the value of the currently displayed item.
  • Press the ➡️ button to increase (change) the displayed parameter value.
  • Press the ⬅ button to decrease (change) the displayed parameter value.
  • Press the ➡️ button to accept the displayed value and store it in non-volatile RAM.
  • When the value is accepted, CHANGE STORED is displayed on the LCD.
  • Press the ➡️ button (Enter) to return to the current menu parameter.
  • Press the ↖ button (MenuUp/Exit) to return to the previous menu.

Note: When values are displayed, pressing and holding the ⬆ or ⬇ button causes the display to automatically increment.

Menu Structure

The Menus in display order are:

  • STATUS
  • SETPOINTS
  • SYSTEM SETUP
  • ADVANCED SETUP
  • CHECKOUT
  • ALARMS

IMPORTANT: Your menu parameters may be different depending on your configuration. For example, if you do not have a DCV (CO2) sensor, then none of the DCV parameters appear. If you have a CO2 sensor, DCV MIN and DCV MAX will appear.

Setup and Configuration

Before being placed into service, the JADE™ Economizer module must be setup and configured for the installed system. Use the System Setup menu, the Advanced Setup menu (if necessary), and the Setpoints menu to accomplish this.

Time-out and Screen Saver

When no buttons have been pressed for 10 minutes, the LCD displays a screen saver, which cycles through the Status items. Each Status item displays for 5 seconds.

Status Menu

The Status Menu displays the current values of various parameters and sensors.

ParameterParameter Default ValueParameter Range and IncrementNotes
ECON AVAILNOYES/NOYES = economizing available; the system can use Outdoor Air for free cooling when required.
ECONOMIZINGNOYES/NOYES = Outdoor Air being used for 1st stage cooling.
OCCUPIEDNOYES/NOYES = OCC signal received from space thermostat or unitary controller. YES = 24 Vac on terminal OCC. No = 0 Vac on terminal OCC.
HEAT PUMPCOOLCOOL/HEATDisplays COOL or HEAT when SYSTEM is set to heat pump (non-conventional).
COOL Y1-INOFFON/OFFY1-I signal from space thermostat input for cooling stage 1 or heat pump heating stage 1. ON = 24 Vac on terminal Y1-I. OFF = 0 Vac on terminal Y1-I.
COOL Y1-OUTOFFON/OFFCool Stage 1 Relay Output to stage 1 mechanical cooling (Y1-OUT terminal).
COOL Y2-INOFFON/OFFY2-I signal from space thermostat input for second stage cooling or heat pump heating stage 2. ON = 24 Vac on terminal Y2-I. OFF = 0 Vac on terminal Y2-I.
COOL Y2-OUTOFFON/OFFCool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).
MA TEMP-.- °F-40 to 150°FDisplays value of measured mixed air from MAT sensor. Displays -.- if not connected, short, or out-of-range.
DA TEMP-.- °F-40 to 150°FDisplays when Discharge Air Sylk Bus sensor is connected and displays measured discharge air temperature. Displays -.-°F if sensor sends invalid value, if not connected, short or out-of-range.
OA TEMP-.- °F-40 to 140°FDisplays measured value of outdoor air temperature. Displays -°F if sensor sends invalid value, if not connected, short or out-of-range.
OA HUM-.- %0 to 100%Displays measured value of outdoor humidity from OA Sylkbus sensor. Displays -% if not connected, short, or out-of-range.
RA TEMP-.- °F0 to 140°FIf field installed Dual Enthalpy sensor is connected, displays measured value of return air temperature. Displays -°F if sensor sends invalid value, if not connected, short or out-of-range.
RA HUM-.- %0 to 100%If field installed Dual Enthalpy sensor is connected, displays measured value of return air humidity. Displays -% if sensor sends invalid value, if not connected, short or out-of-range.
IN CO2-.- ppm"0 to 2000 (3500) ppm"If field installed CO2 sensor is connected, displays value of measured CO2. Invalid if not connected, short or out-of-range. May be adjusted in Advanced menu by Zero offset and Span.
DCV STATUSn/an/aIf field installed CO2 sensor is connected, displays ON if above setpoint and OFF if below setpoint.
DAMPER OUT-.- %0 to 100%Displays output position to the damper actuator. When used with Honeywell communicating actuator the damper out is in XX.X%.
ACT POS.n/a0 to 100%Displays actual position of actuator.
ACT COUNTn/a1 to 65,535Displays number of times actuator has cycled. 1 Cycle equals 180° of movement in any direction.
ACTUATORn/aOK/AlarmDisplays Error on ALARM MENU if voltage or torque is below actuator range.
EXH1 OUTOFFON/OFFOutput of EXH1 terminal. Displays ON when damper position reaches programmed percentage setpoint. ON = 24 Vac Output; OFF = No Output.
EXH2 OUTOFFON/OFFOutput of AUX1 O terminal. Displays ON when damper position reaches programmed percentage setpoint. ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O = EXH2.
ERVOFFON/OFFOutput of AUX1 O terminal, ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O = ERV.
MECH COOL ON00, 1, or 2Displays number of mechanical cooling stages that are active.
FAN SPEEDn/aLOW/HIGHDisplays speed of fan on a 2-speed fan unit.
W (HEAT IN)n/aON/OFFDisplays status of heat on a 2-speed fan unit.

Setpoints Menu

This menu allows adjustment of various operating parameters.

ParameterParameter Default ValueParameter Range and IncrementNotes
MAT SET53°F38 to 70°F; increment by 1The economizer will modulate the OA damper to maintain the mixed air temperature at the setpoint.
LOW T LOCK32°F-45 to 80°F; increment by 1Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout. At or below the setpoint the Y1-O and Y2-O will not be energized on the controller.
DRYBLB SET63°F48 to 80°F; increment by 1Setpoint determines where the economizer will assume outdoor air temperature is good for free cooling; e.g.; at 63 °F setpoint unit will economizer at 62 °F and below and not economize at 64 °F and above. There is a 2 °F deadband.
ENTH CURVEES3ES1, ES2, ES3, ES4, or ES5Does not display if a field installed Dual Enthalpy kit is connected. Enthalpy boundary "curves" for economizing using single enthalpy comparison between outdoor air enthalpy and setpoint.
DCV SET1100 ppm500 to 2000 ppm; increment by 100Displays ONLY if field installed CO2 sensor is connected. Setpoint for Demand Control Ventilation of space. Above the setpoint, the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
MIN POS2.8 V2 to 10 VdcDisplays ONLY if a CO2 sensor is NOT connected. With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V.
VENTMAX2.8 V2 to 10 VdcDisplays only if a field installed CO2 sensor is connected. Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sensor. If OA, MA, RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM and displays from 100 to 9990 cfm. With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan) settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.
VENTMIN2.25 V2 to 10 VdcDisplays only if field installed CO2 sensor is connected. Used for Va (ventilation min cfm) setpoint. This is the ventilation requirement for less than maximum occupancy of the space. If OA, MA, RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM and displays from 100 to 9990 cfm. With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) settings are required. Default for VENTMIN L is 2.5V and VENTMIN H is 2.25V.
ERV OAT SP32°F0 to 50°F; increment by 1Only when AUX1 O = ERV.
EXH1 SET50%0 to 100%; increment by 1Setpoint for OA damper position when exhaust fan 1 is powered by the economizer. With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%.
EXH2 SET75%0 to 100%; increment by 1Setpoint for OA damper position when exhaust fan 2 is powered by the economizer. Only used when AUX1 O is set to EHX2. With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%.

Note: ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.

System Setup Menu

This menu configures basic system parameters.

ParameterParameter Default ValueParameter Range and IncrementNotes
INSTALL01/01/2011DD, MM, then YY.Display order = MM/DD/YY. Setting order = DD, MM, then YY.
UNITS DEG°F°F or °CSets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENTCONVCONV HPCONV = conventional. HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump input from thermostat or controller.
AUX2 IN/AIn CONV mode: SD = Enables configuration of shutdown (default); W = Informs controller that system is in heating mode. NOTE: If using 2-speed fan mode, you must program CONV mode for W. Shutdown is not available in the two-speed fan mode. In HP O/B mode: HP(O) = energize heat pump on Cool (default); HP(B) = energize heat pump on Heat.
FAN TYPE1 speed1 speed/ 2 speedSets economizer controller for operation of 1 speed or 2 speed supply fan. The controller does not control the fan but positions the OA and RA dampers to the heating or cooling mode. NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.
FAN CFM5000cfm100 to 15000 cfm; increment by 100This is the capacity of the RTU. The value is found on the label from the RTU manufacturer. The cfm of the fan is only used with DCV CAL ENABLE AUO.
AUX1 OUTNONENONE ERV EXH2 SYS
  • NONE = not configured (output is not used)
  • ERV = Energy Recovery Ventilator
  • EXH2 = second damper position relay closure for second exhaust fan.
  • SYS = use output as an alarm signal
OCCINPUTINPUT or ALWAYSWhen using a setback thermostat with occupancy out (24 Vac), the 24 Vac is input "INPUT" to the OCC terminal. If no occupancy output from the thermostat then change program to "ALWAYS" OR add a jumper from terminal R to OCC terminal.
FACTORY DEFAULTNONO or YESResets all set points to factory defaults when set to YES. LCD will briefly flash YES and change to NO but all parameters will change to factory default values.

Advance Setup Menu

This menu provides advanced configuration options.

ParameterParameter Default ValueParameter Range and IncrementNotes
MA LO SET45°F35 to 55°F; increment by 1°Temp to activate Freeze Protection (close damper or modulate to MIN POS if temp falls below set value).
FREEZE POSCLOCLO MINDamper position when freeze protection is active (closed or MIN POS).
CO2 ZERO0 ppm0 to 500 ppm; increment by 10Displays only if field installed CO2 sensor is connected. CO2 ppm level to match CO2 sensor start level.
CO2 SPAN2000 ppm1000 to 3000 ppm; increment by 50Displays only if field installed CO2 sensor is connected. CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor output would be 500 CO2 zero and 1000 CO2 span. See note on page 6 for C7632 CO2 sensor.
STG3 DLY2.0h0 min, 5 min, 15 min, then 15 min intervals. Up to 4h or OFFDelay after stage 2 for cool has been active. Turns on 2nd stage of mechanical cooling when economizer is 1st stage call and mechanical cooling is 2nd stage call. Allows three stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling.
SD DMPR POSCLOCLO OPNIndicates shutdown signal from space thermostat. When controller receives 24 Vac input on the SD terminal in conventional mode, the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut off.
DCVCAL ENAMANMAN (manual) AUTOTurns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA and MA sensor conditions. Requires all sensors (RA, OA, MA and CO2). This operation is not operable with a 2-speed fan unit.
MAT T CAL0.0 F°+/-2.5F°Allows for the operator to adjust for an out of calibration mixed air temperature sensor.
OAS T CAL0.0F°+/-2.5F°Allows for the operator to adjust for an out of calibration outdoor air temperature sensor.
OAS H CAL0% RH+/-10% RHAllows for the operator to adjust for an out of calibration outdoor air humidity sensor.
RA T CAL0.0F°+/-2.5F°If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out of calibration temperature sensor.
RA H CAL0% RH+/-10% RHIf field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out of calibration humidity sensor.
DA T CAL0.0 F°+/-2.5F°Allows for the operator to adjust for an out of calibration Discharge Air Sylk Bus temperature sensor.
2SP FAN DELAY5 Minutes0 to 20 minutes in 1 minute increments.When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled.

Checkout Menu

This menu is used to test damper operation and configured outputs.

ParameterParameter Default ValueParameter Range and IncrementNotes
DAMPER VMIN-HSn/an/aPositions damper to VMIN position.
DAMPER VMAX-HSn/an/aPositions damper to VMAX position.
DAMPER VMAX-LSn/an/aWith 2-speed fan units the damper will position to VMAX low speed fan.
DAMPER OPENn/an/aPositions damper to the full open position. Exhaust fan contacts enable during the DAMPER OPEN test. Pause in this mode to allow for exhaust contacts to energize due to system delay.
DAMPER CLOSEn/an/aPositions outside air damper to the fully closed position.
CONNECT Y1-On/an/aCloses the Y1-O relay (Y1-O).
CONNECT Y2-On/an/aCloses the Y2-O relay (Y2-O).
CONNECT AUX1-On/an/aEnergizes the AUX1-O output. If AUX1-O setting is: NONE (no action), ERV (24 Vac out for ERV operation), SYS (24 Vac out for system alarm).
CONNECT EXH1n/an/aCloses the power exhaust fan 1 relay (EXH1).

Checkout Procedure:

  1. Inspect all wiring connections at the Economizer module's terminals and verify compliance with the installation wiring diagrams.
  2. For checkout, review the Status of each configured parameter and perform the Checkout tests.
  3. Scroll to the desired test in the Checkout menu using the ⬆ and ⬇ buttons.
  4. Press the ➡️ button to select the item.
  5. "RUN?" appears on the display.
  6. Press the ➡️ button to start the test.
  7. The unit pauses and then displays TEST RUNNING.
  8. Press the ↖ button (Menu up) to end the test. Test stops automatically after 10 minutes without a command or mode change.

WARNING: Electrical Shock Hazard. Disconnect power supply before beginning wiring or making wiring connections.

CAUTION: Equipment damage may result. Allow enough time for compressor startup and shutdown between checkout tests to avoid short-cycling.

Alarm Menu

The Economizer module provides alarm messages that display on the 2-line LCD.

ParameterParameter Default ValueParameter Range and IncrementNotes
MAT SENS ERRn/an/aAlarms display only when they are active. The menu title "ALARMS (_)" includes the number of active alarms in parenthesis ().
CO2 SENS ERRn/an/a
OA T SENS ERRn/an/a
DA ENTHL ERRn/an/a
SYS ALARMn/an/aWhen AUX1 O is set to SYS and there is any alarm (e.g., failed sensors, etc.), the AUX1 O terminal has 24 Vac out.
ACT UNDER Vn/an/aVoltage received by Actuator is above expected range.
ACT OVER Vn/an/aVoltage received by Actuator is below expected range.
ACT STALLEDn/an/aActuator stopped before achieving commanded position.

Note: Upon power up, the module waits 60 minutes before checking for alarms, except for the MA sensor which will alarm immediately.

Clearing Alarms:

  1. Navigate to the desired alarm.
  2. Press the ➡️ button.
  3. "ERASE?" displays.
  4. Press the ➡️ button.
  5. "ALARM ERASED" displays.
  6. Press the ↖ button (MenuUp/Exit) to complete the action and return to the previous menu.

Sequence of Operation

Detailed tables outlining the sequence of operation based on various conditions (Dry Bulb/Enthalpy, DCV/No DCV, 1-Speed/2-Speed Fan).

Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffHigh0-v/Off0-v/OffMIN POSClosed
NoneNoOnOffHigh24-v/On0-v/OffMIN POSClosed
OnOnHigh24-v/On24-v/OnMIN POSClosed
OffOffHigh0-v/Off0-v/OffMIN POSClosed
NoneYesOnOffHigh0-v/Off0-v/OffMIN POS to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffMIN POS to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.

Dry Bulb Operation With DCV (CO2 sensor) - 1 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffHigh0-v/Off0-v/OffVENTMINClosed
OnOffHigh24-v/On0-v/OffVENTMINClosed
Below CO2 setOnOnHigh24-v/On24-v/OnVENTMINClosed
OffOffHigh0-v/Off0-v/OffVENTMINClosed
YesOnOffHigh0-v/Off0-v/OffVENTMIN to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffVENTMIN to Full-OpenClosed to Full-Open
OffOffHigh0-v/Off0-v/OffVENTMIN to VENTMAXClosed
NoOnOffHigh24-v/On0-v/OffVENTMIN to VENTMAXClosed
Above CO2 setOnOnHigh24-v/On24-v/OnVENTMIN to VENTMAXClosed
OffOffHigh0-v/Off0-v/OffVENTMIN to VENTMAXClosed
YesOnOffHigh0-v/Off0-v/OffVENTMIN to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffVENTMIN to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.

Enthalpy Operation No DCV (CO2 sensor) - 1 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffHigh0-v/Off0-v/OffMIN POSClosed
NoneNoOnOffHigh24-v/On0-v/OffMIN POSClosed
OnOnHigh24-v/On24-v/OnMIN POSClosed
OffOffHigh0-v/Off0-v/OffMIN POSClosed
NoneYesOnOffHigh0-v/Off0-v/OffMIN POS to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffMIN POS to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.

Enthalpy Operation With DCV (CO2 sensor) - 1 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffHigh0-v/Off0-v/OffVENTMINClosed
OnOffHigh24-v/On0-v/OffVENTMINClosed
Below setOnOnHigh24-v/On24-v/OnVENTMINClosed
OffOffHigh0-v/Off0-v/OffVENTMINClosed
YesOnOffHigh0-v/Off0-v/OffVENTMIN to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffVENTMIN to Full-OpenClosed to Full-Open
OffOffHigh0-v/Off0-v/OffVENTMIN to VENTMAXClosed
NoOnOffHigh24-v/On0-v/OffVENTMIN L to VENTMAXClosed
Above setOnOnHigh24-v/On24-v/OnVENTMIN H to VENTMAXClosed
OffOffHigh0-v/Off0-v/OffVENTMIN L to VENTMAXClosed
YesOnOffHigh0-v/Off0-v/OffVENTMIN to Full-OpenClosed to Full-Open
OnOnHighDELAY(b) 24-v/On0-v/OffVENTMIN to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied.

Dry Bulb Operation No DCV (CO2 sensor) - 2 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffLow0-v/Off0-v/OffMIN POS LClosed
NoneNoOnOffLow24-v/On0-v/OffMIN POS LClosed
OnOnHigh24-v/On24-v/OnMIN POS HClosed
OffOffLow0-v/Off0-v/OffMIN POS LClosed
NoneYesOnOffLow0-v/Off0-v/OffMIN POS L to Full-OpenClosed to Full-Open
OnOnHighDELAY(b) 24-v/On0-v/OffMIN POS H to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied. With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Dry Bulb Operation With DCV (CO2 sensor) - 2 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffLow0-v/Off0-v/OffVENTMIN LClosed
OnOffLow24-v/On0-v/OffVENTMIN LClosed
Below setOnOnHigh24-v/On24-v/OnVENTMIN HClosed
OffOffLow0-v/Off0-v/OffVENTMIN LClosed
YesOnOffLow0-v/Off0-v/OffVENTMIN L to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffVENTMIN H to Full-OpenClosed to Full-Open
OffOffLow0-v/Off0-v/OffVENTMIN L to VENTMAXClosed
NoOnOffLow24-v/On0-v/OffVENTMIN L to VENTMAXClosed
Above setOnOnHigh24-v/On24-v/OnVENTMIN H to VENTMAXClosed
OffOffLow0-v/Off0-v/OffVENTMIN L to VENTMAXClosed
YesOnOffLow0-v/Off0-v/OffVENTMIN L to Full-OpenClosed to Full-Open
OnOnHighDELAY(b) 24-v/On0-v/OffVENTMIN H to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied. With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Enthalpy Operation No DCV (CO2 sensor) - 2 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffLow0-v/Off0-v/OffMIN POS LClosed
NO CO2 SENSORNoOnOffLow24-v/On0-v/OffMIN POS LClosed
OnOnHigh24-v/On24-v/OnMIN POS HClosed
OffOffLow0-v/Off0-v/OffMIN POS LClosed
YesOnOffLow0-v/Off0-v/OffMIN POS L to Full-OpenClosed to Full-Open
OnOnHighDELAY(b) 24-v/On0-v/OffMIN POS H to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied. With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Dry Bulb Operation With DCV (CO2 sensor) - 2 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffLow0-v/Off0-v/OffVENTMIN LClosed
OnOffLow24-v/On0-v/OffVENTMIN LClosed
Below setOnOnHigh24-v/On24-v/OnVENTMIN HClosed
OffOffLow0-v/Off0-v/OffVENTMIN LClosed
YesOnOffLow0-v/Off0-v/OffVENTMIN L to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffVENTMIN H to Full-OpenClosed to Full-Open
OffOffLow0-v/Off0-v/OffVENTMIN L to VENTMAXClosed
NoOnOffLow24-v/On0-v/OffVENTMIN L to VENTMAXClosed
Above setOnOnHigh24-v/On24-v/OnVENTMIN H to VENTMAXClosed
OffOffLow0-v/Off0-v/OffVENTMIN L to VENTMAXClosed
YesOnOffLow0-v/Off0-v/OffVENTMIN L to Full-OpenClosed to Full-Open
OnOnHighDELAY(b) 24-v/On0-v/OffVENTMIN H to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied. With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Enthalpy Operation With DCV (CO2 sensor) - 2 Speed Fan

DCVOA Good to economize?Y1-IY2-IFAN SPDY1-OY2-OOccupiedUnoccupied
OffNoOffOffLow0-v/Off0-v/OffVENTMIN LClosed
OnOffLow24-v/On0-v/OffVENTMIN LClosed
Below setOnOnHigh24-v/On24-v/OnVENTMIN HClosed
OffOffLow0-v/Off0-v/OffVENTMIN LClosed
YesOnOffLow0-v/Off0-v/OffVENTMIN L to Full-OpenClosed to Full-Open
OnOnHigh24-v/On0-v/OffVENTMIN H to Full-OpenClosed to Full-Open
OffOffLow0-v/Off0-v/OffVENTMIN L to VENTMAXClosed
NoOnOffLow24-v/On0-v/OffVENTMIN L to VENTMAXClosed
Above setOnOnHigh24-v/On24-v/OnVENTMIN H to VENTMAXClosed
OffOffLow0-v/Off0-v/OffVENTMIN L to VENTMAXClosed
YesOnOffLow0-v/Off0-v/OffVENTMIN L to Full-OpenClosed to Full-Open
OnOnHighDELAY(b) 24-v/On0-v/OffVENTMIN H to Full-OpenClosed to Full-Open

Note: With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have not been satisfied. With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.

Enthalpy Curves and Settings

This section details enthalpy settings and provides curves for economizing.

Single Enthalpy and Dual Enthalpy High Limit Curves

Diagram showing Enthalpy vs. Temperature and Humidity for various setpoints (ES1-ES5, HL).

Enthalpy CurveTemp. Dry-Bulb (°F)Temp. Dewpoint (°F)Enthalpy (btu/lb/da)Point P1Point P2
Temp. °FHumidity %RHTemp. °FHumidity %RH
ES180.060.028.080.036.866.380.1
ES275.057.026.075.039.663.380.0
ES370.054.024.070.042.359.781.4
ES465.051.022.065.044.855.784.2
ES560.048.020.060.046.951.388.5
HL86.066.032.486.038.972.480.3

Enthalpy Settings

When the OA temperature, enthalpy and dew point are below the respective setpoints, the Outdoor Air can be used for economizing. The W7220 uses 5 boundaries (setpoints ES1 through ES5) defined by dry bulb temperature, enthalpy, and dew point. Refer to the table above for ENTH CURVE setpoint values.

To use enthalpy, the W7220 must have a C7400S Sylkbus sensor for OA. The W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA sensor. When the OA temperature, OA humidity, and OA dew point are all below the selected boundary, economizing is available.

When conditions are above the selected boundary, economizing is not available.

The high limit boundary is ES1 when no mechanical cooling stages are energized and HL when a compressor stage is energized.

Two-Speed Fan Operation

The W7220 controller can work with systems using a 2-speed supply fan. The W7220 uses input status to determine fan speed and controls the OA damper accordingly.

StateFan Speed
OCCLow
Y1Low
Y2High
WHigh

The W (heating mode) status informs the controller where to position the OA damper for minimum position for the fan speed.

The 2-speed fan delay is available when the system is programmed for 2-speed fan. The default delay is 5 minutes.

When there is a call for Y1 In and a call for Y2 In during free cooling mode, the 2-speed fan delay starts. The OA damper modulates to 100% open, and the supply fan should be set to high speed. After the delay:

  • The Y2 In call is satisfied with the damper 100% open and fan on high speed, and the call turns off.
  • OR, if the call for additional cooling is not satisfied, the first stage of mechanical cooling will be enabled through Y1 Out or Y2 Out.

Wiring Diagrams and Component Information

Figure 8: Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS3103J or MS3105J communicating actuators.

Figure 9: Diagram illustrating a 2-position actuator and its connections, with notes on using ON/OFF actuators and programming AUX1 O.

Wiring Diagram Details (Page 20):

A detailed wiring schematic shows connections between the W7220 controller, sensors (MA TEMP, OAT, DA ENTHL, RA ENTHL), thermostat, and the rooftop unit. It includes component codes, Nordyne/Honeywell part numbers, wire color codes, and notes on specific wiring configurations.

  • Component Code / Description:
    • 622754 / MS3105J3030: Damper Actuator 24v
    • 626621 / W7220A1000: Logic Module
    • 626622 / C7400S1000: Fresh Air Enthalpy Sensor
    • 626623 / C7250A1001: Mixed Air Temperature Sensor
    • P1: Male Interface Unit Plug
    • S1: Male Interface Unit Plug
  • Wire Color Code: BLK, BLU, BRN, GRN, GRY, ORG, PNK, RED, TAN, VIO, WHT, YEL
  • Notes:
    • Unit wiring shown as reference only; check actual unit wiring.
    • For thermostats with OCC connection, move white wire from pin #1 to pin #7 and connect thermostat OCC output to A1 terminal.
    • Economizer pin location S1-2 connects to "W1" (Gas/Electric, AC) or "O" (Heat Pump Cooling).
    • For mechanical cooling (compressor) to energize during economizer cooling mode, a thermostat "Y2" call is required. A 2-stage cooling thermostat is needed.
    • Refer to Page 3 for unit low voltage wiring changes for W7220 JADE control module.
  • Manufacturer/Distributor Information: RRS Rooftop Systems, A Ruskin Company, 1625 Diplomat Drive, Carrollton, Texas 75006. Phone: (972) 247-7447, Fax: (972) 243-0940.
Models: P8SE Air Conditioner Packaged, P8SE, Air Conditioner Packaged, Conditioner Packaged, Packaged

File Info : application/pdf, 20 Pages, 1.20MB

PDF preview unavailable. Download the PDF instead.

212e

References

TCPDF 6.0.003 (http://www.tcpdf.org)

Related Documents

Preview Honeywell DDNECNJ3672NR Jade Economizer Installation Manual
Installation guide and technical specifications for the Honeywell DDNECNJ3672NR Downflow Jade Economizer, compatible with Daikin and Goodman HVAC systems. Learn about economizer operation, installation steps, wiring, and troubleshooting.
Preview Honeywell RXRD-01MCDAM3 Vertical Airflow Economizer Installation Instructions
Comprehensive installation guide for the Honeywell RXRD-01MCDAM3 Vertical Airflow Economizer, detailing setup, operation, and troubleshooting for HVAC systems. Includes parts list, step-by-step instructions, and system configuration details.
Preview Honeywell JADE Economizer Module W7220 Installation and Setup Guide
This document provides comprehensive instructions for the installation, wiring, setup, and troubleshooting of the Honeywell JADE Economizer Module, Model W7220. It covers electrical specifications, input/output details, various wiring configurations with diagrams, menu structure, sequence of operation tables, and alarm handling.
Preview Honeywell JADE™ W7220 Economizer Module Installation Instructions
Comprehensive installation and setup guide for the Honeywell JADE™ W7220 Economizer Module, covering product description, specifications, wiring, interface overview, and troubleshooting.
Preview Honeywell LCBS Connect Solution: HVAC Control System Application Manual
Explore the Honeywell LCBS Connect Solution, an advanced application manual for commercial HVAC control systems. Learn about its features including cloud connectivity, occupancy control, multi-stage heating/cooling, economizer strategies, dehumidification, DCV, and multispeed fan control for optimal building performance and energy efficiency.
Preview Honeywell Multizone Control System W7080A Series
This document provides detailed specifications, operation, and installation information for the Honeywell W7080A Multizone Control System and its associated components. It covers features, cross-references to Ranco components, electrical ratings, system input and output signals, wiring diagrams, and checkout procedures.
Preview Honeywell T7350 Communicating Programmable Commercial Thermostats - Features and Components
Detailed overview of Honeywell's T7350H communicating programmable commercial thermostats, including features, specifications, accessories, and compatible components for HVAC systems.
Preview Honeywell HZ221 TrueZONE Zone Panel Professional Installation Guide
This guide provides professional installation instructions for the Honeywell HZ221 TrueZONE zone panel. It covers product specifications, recommended accessories, detailed installation steps, wiring diagrams for thermostats, dampers, and HVAC equipment, operational LED indicators, and warranty information.