Altronix EFLOW6N8DV | Power Supply Charger, 8 PTC Class 2 Ou

eFlow6NV-Installation-Instructions

Altronix EFLOW6N8V Power Supply Charger, 8 Fused Outputs, 12/24VDC @ 6A | 123 Security Products


File Info : application/pdf, 16 Pages, 1.40MB

PDF preview unavailable. Download the PDF instead.

eFlow6NV-Installation-Instructions
eFlow6NV Series
Power Supply/Chargers

Models Include:

eFlow6NV/ eFlow6NXV
- 6A @ 12VDC or 24VDC
eFlow6N8V/ eFlow6NX8V
- 6A @ 12VDC or 24VDC - Eight (8) Fused Outputs
eFlow6N16V/ eFlow6NX16V
- 6A @ 12VDC or 24VDC - Sixteen (16) Fused Outputs

eFlow6N8DV/ eFlow6NX8DV
- 6A @ 12VDC or 24VDC - Eight (8) PTC Protected
eFlow6N16DV/ eFlow6NX16DV
- 6A @ 12VDC or 24VDC - Sixteen (16) PTC Protected

Installation Guide

Rev. 6NVRP052213

More than just power.TM

Installing Company: _______________ Service Rep. Name: __________________________________

Address: _____________________________________________ Phone #: __________________

12VDC Output Range (V) 24VDC Output Range (V) 12VDC Output Range (V) 24VDC Output Range (V) Maximum Supply Current for Main and Aux. Outputs (A) Input Rating: 220VAC, 50/60Hz Input Fuse Rating Battery Fuse Rating Ripple Voltage (mV) Under low battery condition Power Distribution Modiule Number of Outputs Fused Outputs Ratings Auto-Resettable PTC Outputs Ratings Accommodates up to 7AH Batteries Accommodates up to 12AH Batteries

Overview:
Altronix eFlow6NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input to a 12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).

eFlow6NV Series Power Supply Configuration Reference Chart:

Nominal DC Outputs

[DC]

[AUX]

Altronix Model Number

eFlow6NV eFlow6NXV

10.0- 20.19- 10.03- 20.1913.2 26.4 13.2 26.4

6

2.1A

5A/ 250V

10A/ 32V

910

N/A

­ ­P­ 1 ­ ­ ­P

eFlow6N8V eFlow6NX8V

10.0- 20.19- 10.03- 20.1913.2 26.4 13.2 26.4

6

2.1A

5A/ 250V

10A/ 32V

910

PD8

2.5A ­ P ­

8 2.5A ­

­

P

eFlow6N8DV eFlow6NX8DV

9.78- 20.0- 10.03- 20.1913.2 26.4 13.2 26.4

6

2.1A

5A/ 250V

10A/ 32V

910

PD8CB

­ 2A P ­ 8 ­ 2A ­ P

eFlow6N16V eFlow6NX16V

10.0- 20.19- 10.03- 20.1913.2 26.4 13.2 26.4

6

2.1A

5A/ 250V

10A/ 32V

910

PD16W 2 - PD8

2.5A ­ 16
2.5A ­

P­ ­P

eFlow6N16DV eFlow6NX16DV

9.78- 20.0- 10.03- 20.1913.2 26.4 13.2 26.4

6

2.1A

5A/ 10A/ 250V 32V

910

PD16WCB 2 - PD8CB

16

­ ­

2A 2A

P ­

­ P

European Conformity

Stand-by Specifications:

Battery

Burg. Applications Fire Applications

4 hr. Stand-by/ 24 hr. Stand-by/

15 min. Alarm

5 min. Alarm

7AH 12AH 40AH (for eFlow6NXV refer to Fig. 8, pg. 10) 65AH (for eFlow6NXV refer to Fig. 8, pg. 10)

0.4A/6A 1A/6A 6A/6A 6A/6A

N/A 0.3A/6A 1.2A/6A 1.5A/6A

Access Control Applications Stand-by
10 Mins./6A 25 Mins./6A Over 4 Hours/6A Over 4 Hours/6A

- 2 -

eFlow6NV Series Installation Guide

Specifications:

Input: · 220VAC (working range 198VAC - 256VAC),
50/60Hz.
Output: · For output voltage and supply current refer to
eFlow6NV Series Power Supply Configuration Reference Chart, pg. 2. · Auxiliary output rated @ 1A (unswitched). · Overvoltage protection.
Fuse Ratings: · Refer to eFlow6NV Series Power Supply
Configuration Reference Chart, pg. 2.
Battery Backup: · Built-in charger for sealed lead acid or
gel type batteries. · Maximum charge current 1.54A. · Automatic switch over to stand-by battery
when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
Fire Alarm Disconnect: · Supervised Fire Alarm disconnect (latching or non-
latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.

Supervision: · AC fail supervision (form "C" contacts). · Battery fail and presence supervision
(form "C" contacts). · Low power shutdown. Shuts down DC output
terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Visual Indicators: · Green AC Power LED indicates 220VAC present. · AC input and DC output LED indicators.
Additional Features: · Short circuit and overload protection. · Unit is complete with power supply, enclosure,
battery leads and cam lock.
Enclosure Dimensions (approximate H x W x D): eFlow6NV, eFlow6N8V, eFlow6N8DV, eFlow6N16V, eFlow6N16DV:
13.5" x 13" x 3.25" (342.9mm x 330.2mm x 82.6mm) eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, eFlow6NX16V, eFlow6NX16DV:
15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm)

Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located indoors within the protected premises. 1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in
the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure's upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground. 2. Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Fig. 1i, pg. 5). 3. Connect unswitched AC power (220VAC 50/60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground lug. Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, Battery Wires). Minimum 0.25" spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel. For Fire Alarm applications the outputs are "Special Applications" only, see list (refer to Appendix A, pg. 13). 4. Measure output voltage before connecting devices. This helps avoiding potential damage. 5. Connect devices to be powered: a. For eFlow6NV/eFlow6NXV connect devices to terminals marked [­ DC +] (Fig. 1h, pg. 5). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked
[1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4a & 4b, pg. 6) carefully observing correct polarity. For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect device to terminals marked [+ AUX ­] (Fig. 1f, pg. 5).

eFlow6NV Series Installation Guide

- 3 -

6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to terminals marked [­ BAT +] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory relay outputs.
8. To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position (Fig. 1c, pg. 5). To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position (Fig. 1c, pg. 5). Note: Must be set to ON position for Burglar Alarm Applications.
9. To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position (Fig. 1c, pg. 5). To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position (Fig. 1c, pg. 5).
10. Trigger terminals are end of a line resistor supervised (10k Ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5).
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5).
12. For Access Control Applications: mount tamper switch (Altronix Model TS112 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2" from the right side (Fig. 5, pg. 7 or Fig. 7, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the appropriate reporting device.

Wiring:
Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper

voltage level eFlow6NV: 12VDC or 24VDC nominal rated @ 6A max.

Battery Test:

Under normal load conditions check that the battery is fully charged, check specified

voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at battery terminal and at the board

terminals marked [­ BAT +] to ensure that there is no break in the battery connection wires.

Note: Maximum charging current under discharges is 1.54A.

Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

Power Supply/Charger

LED Diagnostics:

Red (DC)

Green (AC/AC1) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

- 4 -

eFlow6NV Series Installation Guide

Power Supply/Charger

Terminal Identification:

Terminal Legend Function/Description

L, N

Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg. 5).

­ DC +

12VDC or 24VDC nominal @ 6A continuous output (power-limited output) (Fig. 1h, pg. 5).

Trigger EOL Supervised

Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).

NO, GND RESET + AUX ­
AC Fail NC, C, NO

FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5).
Auxiliary power-limited output rated @ 1A (unswitched) (Fig. 1f, pg. 5).
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 5).

Bat Fail NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).

­ BAT +

Stand-by battery connections. Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 5).

Power Distribution Module Terminal Legend PD8/PD8CB 1P to 8P 1N to 8N

Terminal Legend PD16W/PD16WCB 1P to 16P 1N to 16N

Function/Description Positive DC power outputs. Negative DC power outputs.

Fig. 1 - eFlow6NV Board Configuration

1i

OFF --- 24V ON --- 12V
ON

--- DC +

1h

10A

--- BAT +

5A 250V

5A 250V

10A 32V

1g

AC FAIL BAT FAIL AC1

AC DELAY SHUTDOWN
O N

LG N

NC C NO NC C NO

AC DC 1 min. enable TRIGGER EOL 2 hr. disable SUPERVISED

NO GND RESET

+ AUX ­

1a

1b

1c 1d 1e 1f

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

Trouble/Time Limited Warning of Stand-by Batteries:

The Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to

indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect

the circuit to the Batt Fail relay contacts to an appropriate input of a Burglar Alarm or Access Control Panel. The

following figure shows the circuitry needed for local annunciation.

eFlow6NV Series Installation Guide

- 5 -

Fig. 2 - Battery trouble indication For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 6).
AC FAIL BAT FAIL

POWER SOURCE

NC C NO NC C NO

RED INDICATING LAMP
­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­
Power Distribution Module(s):

Fig. 3a - PD8 Power Distribution Board Non Power-Limited Outputs
Replace fuses with the same type and rating 3.5A/250V

Fig. 3b - PD8CB - Power Distribution Board Power-Limited Outputs

1 2 3 4
P

56 7 8

FUSED POWER OUTPUTS

D1

R1

LED

N
COMMON POWER OUTPUTS
DC Output to devices 1P-8P Power Outputs, 1N-8N Common Outputs

INPUT
From Power Supply Board
(Factory Installed)

1 2 3 4
P

56 7 8

FUSED POWER OUTPUTS

D1

R1

LED

N
COMMON POWER OUTPUTS
DC Output to devices 1P-8P Power Outputs, 1N-8N Common Outputs

INPUT
From Power Supply Board
(Factory Installed)

Fig. 4a - PD16W Power Distribution Board Non Power-Limited Outputs
DC Output to devices 1P-16P Power Outputs, 1N-16N Common Outputs

12345678

common outputs
protected outputs

9 10 11 12 13 14 15 16 N
P

From Power Supply Board (Factory Installed)

Fig. 4b - PD16WCB - Power Distribution Board Power-Limited Outputs

DC Output to devices 1P-16P Power Outputs, 1N-16N Common Outputs

12345678

common outputs
protected outputs

9 10 11 12 13 14 15 16 N
P

From Power Supply Board (Factory Installed)

Input S P P N N Input S P P N N

For continuous protection against risk of fire replace fuses with same type and rating
3.5A 250V
- 6 -

eFlow6NV Series Installation Guide

Fig. 5 - eFlow6NV Configuration

Edge of Enclosure

Enclosure

Tamper Switch (included)

To Access Control Panel or UL Listed Reporting Device

Ground Lug

RESET

SUPERVISED

BAT FAIL

AC FAIL

+AUX-

TRIGGER EOL NO GND

NC C NO NC C NO

L G N

AC DC

AC1

220VAC power mains

Switch Detail

PD8/PD8CB

PD16W/ PD16WCB

ON 1

Battery & AC Supervision Circuit

Switch On - 12V Switch Off - 24V

DC Output to Devices (refer to Fig. 3a, 3b, 4a, 4b for board configuration, pg. 6)

ON

OFF - 24V ON - 12V

J1

AC Delay
Battery Connection

- BAT +

- DC +

Optional Rechargeable Stand-by Battery

Optional Rechargeable Stand-by Battery

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

7AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.

eFlow6NV Series Installation Guide

- 7 -

NEC Power-Limited Wiring Requirements for eFlow6N Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).

Fig. 6
220VAC Input 50/60Hz
(non powerlimited)

Optional Battery Enclosure
(non power-limited)

Supervisory, Fire Alarm Interface and Aux. output Connections (power-limited)

Power Distribution

DC Outputs*

Fig. 6a
- 8 -

Battery Connections (non power-limited)

Incorrect Wire Handling

External Jacketed
Shield

Correct Wire Handling

Wire Insulation
Solid Copper Conductors

* Outputs are non power-limited:

eFlow6NV, eFlow6N8V, eFlow6N16V.

Outputs are Class 2 power-limited:

Pull back external jacketed shield approx. 1/2".

eFlow6N8DV, eFlow6N16DV.

eFlow6NV Series Installation Guide

Fig. 7 - eFlow6NXV Configuration

Edge of Enclosure

Enclosure

Tamper Switch (included)

To Access Control Panel or UL Listed Reporting Device

Battery Connection

- DC +

Ground Lug

ON 1
ON

OFF - 24V ON - 12V
Switch Detail
Switch On - 12V Switch Off - 24V

L G N
220VAC power mains

Battery & AC Supervision Circuit

AC1

AC DC

NC C NO NC C NO

AC FAIL

BAT FAIL

TRIGGER EOL NO GND

SUPERVISED

RESET

+AUX-

- BAT +

PD8/PD8CB
DC Output to Devices* (refer to Fig. 3a, 3b, 4a, 4b for board configuration, pg. 6)

PD8/PD8CB
DC Output to Devices* (refer to Fig. 3a, 3b, 4a, 4b for board configuration, pg. 6)

P N

P N

* Outputs are non power-limited: eFlow6NXV, eFlow6NX8V, eFlow6NX16V. Outputs are power-limited: eFlow6NX8DV, eFlow6NX16DV.

Optional Rechargeable Stand-by Battery

Optional Rechargeable Stand-by Battery

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

12AH Rechargeable batteries are the largest batteries that can fit in this enclosure.

A UL listed external battery enclosure must be used if using 40AH or 65AH batteries.

eFlow6NV Series Installation Guide

- 9 -

NEC Power-Limited Wiring Requirements for eFlow6NXV Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 8a).

Fig. 8

Supervisory, Fire Alarm Interface and Aux. output Connections (power-limited)

Input 220VAC 50/60Hz (non powerlimited)
DC Output*

Power Distribution

Optional Battery Enclosure (non powerlimited)

Fig. 8a
- 10 -

Battery Connections (non power-limited)

Incorrect Wire Handling

External Jacketed
Shield

Correct Wire Handling

Wire Insulation
Solid Copper Conductors

* Outputs are non power-limited:

eFlow6NXV, eFlow6NX8V, eFlow6NX16V.

Outputs are Class 2 power-limited:

Pull back

eFlow6NX8DV, eFlow6NX16DV.

external jacketed

shield approx. 1/2".

eFlow6NV Series Installation Guide

Enclosure Dimensions (BC300):
eFlow6NV, eFlow6N8V, eFlow6N8DV, eFlow6N16V, eFlow6N16DV 13.5" x 13" x 3.25" (342.9mm x 330.2mm x 82.6mm)

1.40" (35.6mm)

4.85" (123.2mm)

4.85" (123.2mm)

1.40" (35.6mm)
1.20" (30.5mm)

3.25" (82.6mm)

1.20" (30.5mm)
1.40" (35.6mm)

0.75" (19.1mm)

12.5" (317.5mm) 11.0" (279.4mm)

0.75" (19.1mm)
0.9375" (23.8mm)

1.20" (30.5mm)
1.40" (35.6mm)

5.10" (129.5mm)

5.10" (129.5mm)

13.0" (330.2mm)

6.5625" (166.7mm)

5.10" (129.5mm)

3.25" (82.6mm)

0.9375" (23.8mm)

3.25" (82.6mm)

3.25" (82.6mm)

1.0" (25.4mm)
1.0" (25.4mm)

10.5" (266.7mm)

1.0" (25.4mm)

eFlow6NV Series Installation Guide

- 11 -

Enclosure Dimensions (BC400):
eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, eFlow6NX16V, eFlow6NX16DV 15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm)

1.5" (38.1mm)

4.615" (117.2mm)

4.615" (117.2mm)

1.5" (38.1mm)

1.75" (44.5mm)

1.25" (31.8mm)
1.5" (38.1mm)

4.5" (114.3mm)

1.1" (27.9mm)

12.23" (310.6mm)

1.1" (27.9mm)

4.5" (114.3mm)
1.375" (34.9mm)
1.125" (28.6mm)

1.25" (31.8mm)
1.5" (38.1mm)

0.91" (23.1mm)

0.91" (23.1mm)

15.5" (393.7mm)

2.0" (50.8mm)
2.0" (50.8mm)

5.0" (127.0mm)

0.79" (20.1mm)

5.0" (127.0mm)

1.25" (31.8mm)

1.1" (27.9mm)

1.25" (31.8mm)

1.5" (38.1mm)

4.615" (117.2mm)

4.615" (117.2mm)

1.75" (44.5mm)
1.5" (38.1mm)

- 12 -

eFlow6NV Series Installation Guide

Appendix A - Compatible Devices
­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­
A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with eFlow6NV output.

System Sensor Smoke Detector/Base

Detector Type

Max

Alarm

Stand-by Current

Current (mA) (mA)

B112LP

Base

0.12

B114LP

Base

*

B404B

Base

*

DH100ACDC

Photoelectric

0.15

DH100ACDCLP

Photoelectric

0.15

DH100ACDCLPW

Photoelectric

0.15

DH400ACDCI

Ionization Duct

25

DH400ACDCP

Photoelectric Duct

25

1112/24/D

Ionization

0.05

1424

Ionization

0.10

1451 (w/B402B Base)

Ionization

0.10

2112/24ATR

Photoelectric

0.50

2112/24AITR

Photoelectric

0.50

2112/24/D

Photoelectric

0.05

2112/24T/D

Photoelectric w/135o Thermal

0.05

2112/24TSRB

Photoelectric w/135o Thermal Supervisory Relay

15

2312/24TB

Photoelectric

0.12

2412 (12 volt)

Photoelectric

0.12

2424

Photoelectric

0.10

2451

Photoelectric

0.10

2451TH (with/B402B Base)

Photoelectric

0.10

2W-MOD

Loop Test/Maintenance Mod.

30

4W-B (12/24 volt)

Photoelectric I3

0.05

4WT-B (12/24 volt)

Photoelectric I3 w/Therm

0.05

4WTA-B (12/24 volt)

I3 Photo w/Therm/Sounder

0.05

4WTR-B (12/24 volt)

I3 Photo w/Therm/Relay

0.05

4WITAR-B (12/24 volt)

I3 Photo w/Isolated Therm/Sounder/Relay

0.05

2W-MOD2

I3 Loop Test/Maintenance Mod.

0.05

RRS-MOD

I3 Reversing Relay/Sync Module

0.05

6424

Projected Beam

10

Beam 1224(S)

Projected Beam

17

36 * * 0.70 0.70 0.70 95 95 50 41 39 60/70 60/70 50 50 45 50 77 41 39 39 50 23 23 35 35 50 * * 28.4 38.5

* Contact manufacturer for current draws. ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­
A.2 Relays Table A-2 below lists relays compatible with eFlow6NV output.

Manufacturer

Model Current (mA)

Manufacturer

Model Current (mA)

PR-1**

15

PR-2*

30

System Sensor

PR-3* EOLR-1

30 30

R-10T**

23

R-14T**

23

System Sensor

R-20T** R-24T** R-10E** R-14E** R-20E** R-24E**

* Compatible only with eFlow6NV, eFlow6NXV, eFlow6N8V, eFlow6NX8V, eFlow6N16V, eFlow6NX16V. ** Compatible only when unit is set for 24VDC.
eFlow6NV Series Installation Guide

40 40 23 23 40 40
- 13 -

eFlow Power Supply/Chargers can be Controlled and Monitored while Reporting
Power/Diagnostics from Anywhere over the Network...

LINQ2 - Network Communication Module LINQ2 provides remote IP access to real-time data from eFlow power supply/chargers to help keep systems up and running at optimal levels. It facilitates fast and easy installation and set-up, minimizes system downtime, and eliminates unnecessary service calls, which helps reduce Total Cost of Ownership (TCO) - as well as creating a new source of Recurring Monthly Revenue (RMR).
LINQ2
Features:
- UL Listed in the U.S. and Canada. - Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN. - Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service,
input trigger state change, output state change and unit temperature. - Access control and user managment: Restrict read/write, Restrict users to specific resources - Two (2) integral network controlled Form "C" Relays. - Three (3) programmable input triggers: Control relays and power supplies via external hardware sources. - Email and Windows Dashboard notifications - Event log tracks history. - Secure Socket Layer (SSL). - Programmable via USB or web browser - includes operating software and 6 ft. USB cable.
LINQ2 Mounts Inside any eFlow Enclosure

- 14 -

TRIGGER EOL disable 2 hr. SUPERVISED enable 1 min.
O N

L G

N

AC1
NC C NO NC C NO
AC DC AC DELAY
SHUTDOWN

BAT FAIL AC FAIL

eFlow Power Supply/Charger

LINQ2 Module Network Connection: Installation, Programming and Monitoring
eFlow6NV Series Installation Guide

Notes:

Altronix is not responsible for any typographical errors. ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056

website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty

IIeFlow6NV Series

G23U

MEMBER

eFlow6NV Series Installation Guide

- 15 -

Power Supply/Chargers Operating Guide

Models Include:
Model
eFlow6NV, eFlow6N8V, eFlow6N8DV, eFlow6N16V, eFlow6N16DV eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, eFlow6NX16V, eFlow6NX16DV

Input 220VAC, 50/60Hz

Output

Auxiliary Power-Limited Ripple

12VDC 24VDC Output (unswitched) Voltage

2.1A

6A

6A

1A

910mV

Overview:
The eFlow6NV series power supply/chargers convert a 220VAC, 50/60Hz input to a 12VDC or 24VDC output.

Battery 7AH 12AH 40AH 65AH

Stand-by Specifications:

Burg. Applications 4 hr. Stand-by/ 15 min. Alarm 0.4A/6A
1A/6A
6A/6A
6A/6A

Fire Applications 24 hr. Stand-by/
5 min. Alarm N/A
0.3A/6A
1.2A/6A
1.5A/6A

Access Control Applications Stand-by
10 Mins./6A 25 Mins./6A Over 4 Hours/6A Over 4 Hours/6A

Battery Backup: · Built-in charger for sealed lead acid or gel type batteries. · Maximum charge current 1.54A. · Automatic switch over to stand-by battery when AC fails.
Transfer to stand-by battery power is instantaneous with no interruption.

Red (DC) ON ON OFF OFF

Green (AC/AC1) ON OFF ON OFF

LED Diagnostics:
Power Supply Status Normal operating condition. Loss of AC. Stand-by battery is supplying power. No DC output. Loss of AC. Discharged or no stand-by battery. No DC output.

CUT ALONG DOTTED LINE

Installing Company: _______________ Service Rep. Name: __________________________________ Address: _____________________________________________ Phone #: __________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow6NV Series, Rev. 6NVRP052213 for complete instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 6NVRP052213

