Instruction Manual for neptronic models including: CMU-06 Compact Make up Air Unit, CMU-06, Compact Make up Air Unit, Make up Air Unit, Air Unit

plafond

Compact Make-up Air Unit

May 30, 2023 — * If the IMC10 Room Control Switch is not used, place a jumper between pins 1 & 2. Page 9. Compact Make-up Air Unit. Specification and Installation Instructions.24 pages


File Info : application/pdf, 24 Pages, 1.20MB

PDF preview unavailable. Download the PDF instead.

Compact Make-Up Air Unit-230414
Compact Make-up Air Unit
Specification and Installation Instructions

Description
The Neptronic Compact Make-up Air Unit (CMU) is designed to pull in fresh, tempered air from outside a building in order to replace existing air and continuously provide comfortable ventilation throughout the building.
Equipped with intelligent control strategies and the patented Neptronic EAS (Electronic Air Flow Sensors), the CMU maximizes efficiency and optimizes indoor air quality.

The advanced control strategies and optional BACnet MS/TP and Modbus RTU communication modules make it the ideal product for integration with the automation system of intelligent buildings, by enhancing user comfort and reliability.

CMU Series

Features
· Air flow range of 50 to 750CFM (85 to 1274m3/h) · Sizes from 6" to 12" (152 to 305mm) · Wide power range (1kW to 20kW) · Voltage from 120V/1ph to 600V/3ph · T between 22°F (11°C) and 86°F (45°C) · Multiple I/O support for advanced control strategies · Patented Neptronic EAS (Electronic Air Flow Sensors) · Ease of operation and maintenance, and enhanced
comfort with Neptronic TDF digital room sensors  Display supply temperature  Configure CFM and temperature setpoints  Monitor alarms
· ECM and AC fan strategies · Intelligent control strategies
 Indoor air quality applications with integrated temperature, humidity, CO2 and occupancy sensor
 Dehumidification logic  Interlock with extraction fans  Outside air sensors prime heater coils for fast
response and comfort  Static pressure PID algorithms, control of fresh air
and return air · Integrate with BMS and intelligent buildings via BACnet
MS/TP or Modbus RTU · Safety interlocks and thermal cutouts · Schedule support
Specifications

Network Communication
· BACnet MS/TP or Modbus communication (selectable via DIP switch)
· Select MAC address via DIP switch or via network · BMS integration via BACnet MS/TP or Modbus · Multiple BACnet/Modbus points to propel you towards
the Internet of Things (IoT) · Remote monitoring (status, alarms, diagnostics, and
trending) · Real-time feedback of output capacity · Provides real-time temperature measures and power
consumption data
BACnet MS/TP®
· MS/TP @ 9600, 19200, 38400, 57600 or 76800 bps · Automatically assigns device instance · Automatic Baud Rate Detection
Modbus
· Modbus @ 9600, 19200, 38400, 57600 or 76800 bps · RTU Slave, 8 bits (configurable parity and stop bits) · Connects to any Modbus master

Technical data Maximum outlet air temperature Maximum operating outlet temperature Inlet bushing Control signal Fan Air flow direction Voltage, Current, Power, and Minimum air flow

CMU Series 200°F (93°C) 95°F (35°C) 2 knockouts of 1 '' (35mm) or 1 ¾" (44.5mm) Modulating or Vernier control (select models) AC or ECM fan Horizontal with reversible installation See name plate

Certification

4011008

Complies to standards UL 60335-1 & UL 60335-2-40, CSA C22.2 No. 60335-1 & CSA C22.2 No. 60335-2-40

Compact Make-Up Air Unit-230414

Page | 1

Compact Make-up Air Unit
Specification and Installation Instructions

Models

Model
CMU

Collar Size
06

Voltage Code
A

Heating Capacity
010

Fan Type
A

Power Switch
D

CMU = Compact Make-Up Air Unit

06 = 6" 08 = 8" 10 = 10" 12 = 12"

Warnings

A = 120VAC/1ph B = 208VAC/1ph C = 220, 240VAC/1ph D = 347VAC/1ph E = 480VAC/1ph F = 600VAC/1ph G = 208VAC/3ph H = 400VAC/3ph* I = 480VAC/3ph J = 600VAC/3ph
* = This option does not have ETL Certification

010 = 1kW
015 = 1.5kW
020 = 2kW 030 = 3kW
040 = 4kW
045 = 4.5kW
050 = 5kW 060 = 6kW 070 = 7kW 080 = 8kW 090 = 9kW 100 = 10kW 120 = 12kW 140 = 14kW 160 = 16kW 180 = 18kW 200 = 20kW

A = AC Axial Fan C = ECM Axial Fan D = ECM Centrifugal Fan

D = Disconnect Switch = None

Caution, Risk of malfunction, In case of alteration (drilling holes or other) to the electrical compartment, ensure proper protection of all electrical components installed. Chips may cause short circuit or affect operation of electrical components.
Caution, Risk of damage and malfunction, Ensure minimum air flow, insufficient air flow will lead to opening of mechanical air flow switch (PDN or PDA) or electronic air flow sensors (EAS) and automatic thermal cutout. This may damage heating elements and controls.

!

Caution, Risk of malfunction, Do not proceed with modification or alteration to internal electric connections or components of the make-up air unit. Any non-authorized modification will void the warranty.

Important, This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children must be supervised to ensure that they do not play with the appliance.

Handling

! Warning, Risk of failure or malfunction. Do not operate the CMU if heating elements have been damaged during transport or handling.
· Protective packaging must be kept until installation. · Product must be handled with care.

www.neptronic.com

Page | 2

Dimensions
A
E

Compact Make-up Air Unit
Specification and Installation Instructions
B

C D

Models with Axial Fan

Models
CMU06 (Small) CMU06 (Large) CMU08 (Small) CMU08 (Large)
CMU10 CMU12

Dimensions (inch) [mm]

A 23 [584] 28.9 [734] 24 [610] 30 [762] 27.7 [704] 28.8 [732]

B 7.6 [193]
9.6 [244] 11.6 [295] 13.8 [351]

C 13.3 [338]
15.3 [389] 17.3 [439] 19.3 [490]

Collar Size (inch) [mm]
D
6 [152]
8 [203] 10 [254] 12 [305]

Door Length (inch) [mm]
E 14.7 [373] 20.7 [526] 14.7 [373] 20.7 [526] 16.7 [424] 16.7 [424]

Maximum Air Flow
(CFM) [m3/h]
125 [212]
320 [544]
650 [1104] 750 [1274]

Maximum Power (kW)
3
8 12 20

Models with Centrifugal Fan

Models
CMU06 CMU08 CMU10 CMU12

Dimensions (inch) [mm]

A 34.2 [869] 31.5 [800] 37.9 [963] 41 [1041]

B 9.9 [252] 11.9 [302] 13.9 [353] 15.9 [404]

C 15.3 [389] 17.3 [439] 19.3 [490] 21.3 [541]

Collar Size (inch) [mm]
D 6 [152] 8 [203] 10 [254] 12 [305]

Door Length (inch) [mm]
E 25.9 [658] 22.2 [564] 26.8 [681] 28.9 [734]

Maximum Air Flow
(CFM) [m3/h]
250 [425]
350 [595]
500 [850]
700 [1189]

Maximum Power (kW)
3 8 12 20

www.neptronic.com

Page | 3

Compact Make-up Air Unit
Specification and Installation Instructions

Mechanical Installation
! Caution, Risk of electric shock and burns. Personnel must use appropriate personal protective equipment to protect themselves from risk of electric shock and burns due to contact with heating elements and bare live parts. Always proceed with caution when handling and servicing the CMU by following the appropriate lock-out procedures to ensure safety.

!

Caution, Risk of damage and malfunction. Do not block air flow to heating elements and ventialtion slots, as insufficient air flow may damage heating elements and controls.

Thermal Cutout

Reversible Airflow

OUT

IN

Thermal Cutout

IN

OUT

· The compact make-up air unit is designed to be installed for horizontal air flow only. Vertical installation is not recommended.
· The CMU is equipped with thermal cutouts both on top and bottom of the unit, which allow it to simply be rotated 180º to change the air flow direction without modifying the fan or wiring. The air flow direction from the fan itself is fixed and cannot be reversed. Before mounting the make-up air, determine the direction of air flow required and rotate the unit accordingly.
· The CMU is designed to preheat fresh air and not ambient air.
· For proper air flow, a minimum straight duct distance of 2x the collar size/duct diameter must be maintained upstream and downstream the CMU, between the unit and any obstacle, such as dampers, louvers and elbows.
· Use round insulated ducts for the inlet connection and uninsulated ducts for the outlet, while ensuring to minimize the use of elbows.
· When taking air directly from outside, install the inlet duct at an incline, in order to prevent condensation or melted snow from flowing into the unit.
· It is recommended to have a secondary damper before the inlet of the make-up air unit, in order to prevent a strong draft of wind from opening the damper in the unit. The secondary damper can be a gravity damper or a damper with an actuator.
· A louver with a bird protection grille must be installed on the air inlet.

Minimum 2x Collar Size

CMU

Minimum 2x Collar Size

www.neptronic.com

Page | 4

Compact Make-up Air Unit
Specification and Installation Instructions
Clearance
· Leave a minimum clearance of 24'' (610mm) or equivalent to the length of the front access panel/door (see dimension E on page 3) + 1.5" (38mm) at the front of the unit, in order to provide sufficient space for accessing the electrical compartment and air filter, to ensure proper servicing.
· Other surfaces require zero clearance.

Minimum 24" (610mm)
Insulation
· Insulation may be added around the main surfaces of the CMU for energy conservation and noise reduction. The collars and ductwork preceding and following the CMU may be insulated.
· Insulation must be rated for temperatures of minimum 250°F (121°C) and must not have an R-value greater than 8 (typical R-value for 2'' [51mm] thick fiberglass insulation).
! Warning, Do not apply insulation on the control box, front access panel, heat sinks and filter of the CMU.
Surfaces that can be insulated
Surfaces that cannot be insulated

www.neptronic.com

Page | 5

Compact Make-up Air Unit
Specification and Installation Instructions
Wall Mounting
· Prior to installation, ensure that the strength of the chosen wall and supports conform to the requirements of local codes and regulations. The use of metal strut channels is recommended when wall mounting the unit (by others).
· Mount the unit at a minimum height of 6.5ft (2m) above the floor level. · Mount the CMU using at least 2 screws of minimum #10 (M5) size (by others) using the keyholes located in the back of the
unit and ensure that the installation is secure.

Use 2 screws (by others)

Ceiling Installation
· The CMU can be hung by the ceiling using an appropriate support platform (by others). Consult local codes and regulations for minimum structural requirements for such platforms.
· The CMU must be attached to the platform by use of 4 self-drilling screws of #10 (M5) size fixed at the designated locations indicated by the dimples on the bottom of the unit, as per the image below.
· The screws must not be inserted into the CMU at a depth of more than ¾" (20mm). · Ensure not to install the bottom of the unit's front access panel directly onto the platform, as this will prevent it from
opening.

7.75" (197mm)

1.75" (45mm)

1.75" (45mm)

1.75" (45mm)

1.75" (45mm)

Bottom View: Location of Mounting Holes

www.neptronic.com

Page | 6

Compact Make-up Air Unit
Specification and Installation Instructions

Electrical Installation
· DANGER: Risk of electric shock. Disconnect all electrical supplies before working on any circuit. · CAUTION: Risk of malfunction. Use only copper wires suitable for 221°F (105°C). · CAUTION: Electric installation must be done by qualified electrician and must conform to local electrical code. · CAUTION: If a disconnect switch has not been supplied with control panel of the unit, an external disconnect
switch must be installed on the supply. · CAUTION: Gauge of electric supply wires must be of appropriate section, function of line current, as per local
electrical code.

Power Supply Wiring
See the name plate for information for voltage and current.
· Connect all wires to appropriate terminals as per the electrical diagram affixed inside the control panel door. · Correct connection and proper tightening must be verified before start-up, and after a short period of operation (typically after 2
weeks).

To quickly calculate the amperage, use the following formulas:
· Single phase: Amperage = Watts / Voltage. ex.: 10 kW at 240V/1 is equal to: 10,000 / 240 = 41.7A
· Three phases: Amperage = Watts / (1.732 x Voltage). ex.: 20 kW at 600V/3 is equal to: 20,000 / (1.732 x 600) = 19.2A

Electrical Diagram Legend
Thermal cut-out automatic reset
Thermal cut-out Manual reset
Contactor coil
Back-up safety contactor coil Normally closed contact

or

Normally open contact

or

Disconnect switch

Heating element

Transformer

Fuse

Single phase power supply terminals 3 phases power supply terminals Ground terminal
Common
Light

www.neptronic.com

Page | 7

Compact Make-up Air Unit
Specification and Installation Instructions

Main PCB Overview
MAC1

MAC2

TB1 TB2 TB3

TB2 TB1

TB8 TB7

TB3

Connect to Damper 1

Actuator

2

1
IMC10 2
3

COM

1

OUTPUT 2

POWER 3

Connect to

1

STC8-11 Duct Sensor 2

TB4

TB5*

P1

TB6

Fan Speed

JP5 LD1 Status

P2 Temperature Setpoint

MAC3

Connect to Damper Actuator

JP2 JP3
1
TB4
2

1 COM

1

IMC10 2 OUTPUT 2 TB5*

P1

JP3 Connect to
CMU Add-on
PCB

3

POWER 3

Fan Speed

JP3

Connect to

1 TB6

STC8-11 Duct Sensor 2

P2

JP7 LD1 Status

Temperature Setpoint

Connect to CMU Add-on
PCB

MAC4

Connect to Damper 1

Actuator

2

1

COM

1

IMC10 2

OUTPUT 2

3

POWER

3

Connect to

1

STC8-11 Duct Sensor 2

JP1

TB1 JP 4 JP 5
JP 7
TB6

TB2 TB3

TB4 TB5

TB7

JP 9

TB8*

P1

Fan Speed

TB9 JP11 LD1 Status

P2
Temperature Setpoint

Connect to CMU Add-on
PCB

Connect to

1

Damper Actuator 2

1
IMC10 2
3

COM

1

OUTPUT 2

POWER 3

Connect to

1

STC8-11 Duct Sensor 2

TB1

TB6

TB7 TB2

JP4 TB3

TB4*

P1

JP3

Fan Speed

TB5

P2

JP8 LD1 Status

Temperature Setpoint

Connect to CMU Add-on
PCB

* If the IMC10 Room Control Switch is not used, place a jumper between pins 1 & 2.

www.neptronic.com

Page | 8

Compact Make-up Air Unit
Specification and Installation Instructions

Temperature and Air Flow Adjustment
After installing and wiring the system, use the potentiometers on the PCB to adjust the desired temperature setpoint (P2) and the fan speed control (P1) to adjust the air volume. The fan speed must be adjusted based on the application to compensate for the specific static pressure of the installation.
For models with the optional add-on board with thermostat connection, the setpoint for air flow and temperature from the thermostat will override the physical setting of the potentiometers on the PCB.

Potentiometer P1 = Fan Speed Control

75%

75%

75%

75%

75%

50%

40%

60%

30%

70%

75%

80%

20%

80%

75%

90%

15%

90%

0%

100%

0%

100%

AC Fan Speed Settings

ECM Fan Speed Settings

Potentiometer P2 = Temperature Setpoint

17.5°C

(63.5°F)

14°C (57.2°F)

21°C (69.8°F)

*10.5°C (50.9°F)

24.5°C (76.1°F)

*7°C (44.6°F)

28°C (82.4°F)

*3.5°C (38.3°F)

31.5°C (88.7°F)

*0°C (32°F)

35°C (95°F)

*A minimum temperature of 12°C (53.6°F) will be maintained, even if the setpoint on the potentiometer is set to a lower value.

Operational Conditions

Air Flow
· Air flow must not be lower than the minimum air flow indicated on name plate. · Air flow going through the unit must be free of combustible particles, flammable vapour or gas. · Open Coil: Air flow going through the unit must be free of dust.

Temperature Control
· For optimal and accurate measurement, it is recommended to use a duct sensor, especially in worst case scenarios in which the CMU is operating at its lowest speed with a high static pressure, for example, at a 75% speed with a static pressure of 0.2" WC (50 Pa) for AC axial fans.

Zero Clearance Construction
· Neptronic compact make-up air units are designed and approved for zero clearance to combustible material. Insulation material may be installed directly onto the CMU surfaces or onto air duct. However, the control panel must be accessible for maintenance.
Warning, Risk of fire and/or malfunction, Do not install insulation directly on heating elements.

www.neptronic.com

Page | 9

Fan Performance
Axial Fan Performance

Compact Make-up Air Unit
Specification and Installation Instructions

Centrifugal Fan Performance

www.neptronic.com

Page | 10

Compact Make-up Air Unit
Specification and Installation Instructions

Add-on PCB Overview (Option)

Binary Outputs | TB1-2 BO1: Binary Output 1 COM: Common BO2: Binary Output 2 COM: Common
TDF Digital Room Sensor | TB3 COM: Common 24Vac: Power Supply DATA: Data
Network Port | TB4 A+: BACnet/Modbus A+ B-: BACnet/Modbus B-

AI1 AI2 COM AI3 AI4 AO1 COM AO2

End of Line | JP2

Non e*

120 ohms

* default setting

MAC Address | DS1 The 8 DIP switches represent a binary logic to calculate the MAC address.
Default = all OFF
BACnet all OFF = 0 Modbus all OFF = 1

BO1 1 COM 2 BO2 1 COM 2 COM 1 24Vac 2 DATA 3
A+ 1 B- 2

TB1
TB2
J1
TB3 JP2 TB5
TB4

DS1
ON 1 2 3 4 5 6 7 8

DS2 ON 1 2 3 4

TB6

TB7

1 23 1 2 1 23

Baud Rate | DS2

1 OFF OFF OFF OFF ON ON ON

2 OFF OFF ON ON O FF O FF ON

3 OFF ON OFF ON OFF ON OFF

Result Auto Detect* 960 0 19,200 38,400 57,600 76,800 115,200

* default setting

Network | DS2

4 OFF ON

Mode BA Cn et * Modbus

* default setting

Analog Inputs | TB5
AI 1: Analog I nput 1 (0-10Vdc) AI 2: Analog I nput 2 (0-10Vdc) COM: Common

Temperature Sensor | TB6
AI3: Analog Input 3 (10KOhms or dry contact) AI4: Analog Input 4 (10KOhms or dry contact)

Analog O utputs | TB7
AO1: Analog Output 1 COM: Common AO2: Analog Output 2

MAC Address DIP Switch (DS1)
MAC address for BACnet and Modbus communication, are selectable by DIP switch DS1 using binary logic.

BACnet

· Highest MAC address is 254. · Default is all switches OFF = MAC address 0 · If you do not change device instance in program mode, it will be automatically modified according to the MAC address.

MAC Address 0 1 2 3 4 ... 126 ... 254

DS.1 = 1 OFF ON OFF ON OFF ... OFF ... OFF

DS.2 = 2 OFF OFF ON ON OFF ... ON ... ON

DS.3 = 4 OFF OFF OFF OFF ON ... ON ... ON

DS.4 = 8 OFF OFF OFF OFF OFF ... ON ... ON

DS.5 = 16 OFF OFF OFF OFF OFF ... ON ... ON

DS.6 = 32 OFF OFF OFF OFF OFF ... ON ... ON

DS.7 = 64 OFF OFF OFF OFF OFF ... ON ... ON

DS.8 = 128 OFF OFF OFF OFF OFF ... OFF ... ON

Default Device Instance 153000 153001 153002 153003 153004 ... 153126 ... 153254

Modbus

· Highest MAC address is 247. · Default is all switches OFF = MAC address 1 · MAC address is binary value +1 · There is no device instance for Modbus.

MAC Address 0+1 = 1 1+1 = 2 2+1 = 3 3+1 = 4 4+1 = 5 ... 126+1 = 127 ... 246+1 = 247

DS.1 = 1 OFF ON OFF ON OFF ... OFF ... OFF

DS.2 = 2 OFF OFF ON ON OFF ... ON ... ON

DS.3 = 4 OFF OFF OFF OFF ON ... ON ... ON

DS.4 = 8 OFF OFF OFF OFF OFF ... ON ... OFF

DS.5 = 16 OFF OFF OFF OFF OFF ... ON ... ON

DS.6 = 32 OFF OFF OFF OFF OFF ... ON ... ON

DS.7 = 64 OFF OFF OFF OFF OFF ... ON ... ON

DS.8 = 128 OFF OFF OFF OFF OFF ... OFF ... ON

www.neptronic.com

Page | 11

Compact Make-up Air Unit
Specification and Installation Instructions

Wiring to TDF Digital Room Sensor
TDF
TB1
1 2 3 4 5 6 7

Op tion al: connect to enable service port
To other BA Cn et /Mo db us
device

BO1 1 COM 2 BO2 1 COM 2 COM 1 24Vac 2 DATA 3
A+ 1 B- 2

TB1
TB2
J1
TB3 JP 2 TB5
TB4

TB6

DS1
ON 1 2 3 4 5 6 7 8
TB7

DS2 ON 1 2 3 4

1 23 1 2 1 23

AI1 AI2 COM AI3 AI4 AO1 COM AO2

TDF PCB Drawing
3 wire cable (TB1 #1, 2 & 3) Connect TB1 #6 (A+) & #7 (B-) to CMU to enable the BACnet service port.
Avoid touching the CO2 sensor as this may cause incorrect readings.

CO2 sensor (models with CO2)

1

COM

2

PWR

3

DATA

4

5

6

A+

7

B-

JP1 RUN PGM

Mode Selection (JP1)

JP1 RUN PGM
JP1 RUN PGM

RUN: Digital Room Sensor is in Operation Mode. Digital Room Sensor must be set in this mode for normal system operation. If not locked, setpoint and control mode can be changed by the end user.
PGM: Digital Room Sensor is set in Programming Mode. Refer to the following sections for more details.

www.neptronic.com

Page | 12

Compact Make-up Air Unit
Specification and Installation Instructions

Access to Menus (Add-on PCB and TDF Required)

The programming menu can be accessed using the TDF digital room sensor by connecting it to the optional add-on PCB. Ensure that the TDF Mode Selection jumper (JP1) is set to PGM. Use the following action buttons to access the menus and save changes using the TDF.
Action Buttons on TDF

Action Button

Task

Press to access the programming menus and save any changes.

Press to return to the previous step without saving.

LED Error Sequence
The output on the LED will show when the alarm is active. Following is the LED error sequence:

Error Duct Sensor Fault Airflow Sensor Fault Automatic/Manual Cutout Tripped Normal Operation Any other Scenarios*

LED Output Blinks 5 times and stays ON for 5 seconds. Blinks 10 times and stays ON for 10 seconds. Blinks 15 times and stays ON for 15 seconds. Blinks once every 2 seconds. LED stays on continuously till the alarm is reset.

* Other scenarios can include but not limited to: 1. Error in Feedback for ECM Fans 2. Incorrect configuration of the IO's on the COM board 3. Communication error between Add-on and Host Board

For the above scenarios, please contact tech support at the factory for assistance.

www.neptronic.com

Page | 13

Compact Make-up Air Unit
Specification and Installation Instructions

Inputs ­ Menu Overview (1 of 4) | AI1 to AI4

Main Menu

Sub Menu

Configuration

*** To save any changes, press on TDF *** *** To return to the previous step without saving, press

on TDF ***

= scroll menu items
Main Menu
INPt (Inputs)
OutP (Outputs)

Inputs
AI1 AI2 AI3 AI4

= scroll menu items

Ctrl (Control)

Alar (Alarm)

AI1 MODE

= select / set value AI1 MSV.3

OF F

SAT (supply air temperature)

SARH (supply air relative humidity)

OAT (outside air temperature) OARH (outside air relative humidity) StPr (static pressure) FSSp (fan speed setpoint) DpFb (damper feedback)

AI2 MODE

= select / set value AI2 MSV.4

OF F

SAT (supply air temperature)

SARH (supply air relative humidity)

OAT (outside air temperature)

OARH (outside air relative humidity)

StPr (static pressure)

FSSp (fan speed setpoint)

DpFb (damper feedback)

AI3 MODE

= select / set value AI3 MSV.5

OF F

SAT (supply air temperature)

OAT (outside air temperature)

DpFb (damper feedback)

OCC (occupancy) STA (stage)

AI4 MODE

= select / set value AI4
MSV.6

OF F

SAT (supply air temperature)

OAT (outside air temperature)

DpFb (damper feedback)

OCC (occupancy) STA (stage)

Go to "AI2"
PRESSUR RANGE PASCAL 250 500 1250
AI1 SIGNAL RANGE VOLT 2-10 (Vdc Sensor) 0-10 (Vdc Sensor)

MSV.11 MSV.12

Go to "AI2" Go to "AI2"

Go to "AI3"
PRESSUR RANGE PASCAL 250 500 1250
AI2 SIGNAL RANGE VOLT 2-10 (Vdc Sensor) 0-10 (Vdc Sensor)

MSV.11 MSV.13

Go to "AI3" Go to "AI3"

Go to "AI4"

AI3 STAGE WEIGHT PERCENT 50% (10-100%)

AV.15

Go to "AI4"

Go to "OutP"

AI4 STAGE WEIGHT PERCENT 50% (10-100%)

AV.16

Go to "OutP"

www.neptronic.com

Page | 14

Compact Make-up Air Unit
Specification and Installation Instructions

Outputs ­ Menu Overview (2 of 4) | AO1, AO2, BO1 and BO2

Main Menu

Sub Menu

= scroll menu items
Main Menu

*** To save any changes, press on TDF *** *** To return to the previous step without saving, press

Configuration
on TDF ***

INPt (Inputs) OutP (Outputs) Ctrl (Control) Alar (Alarm)

OUTputs
AO1 AO2 BO1 BO2

= scroll menu items

= select / set value

AO1

AO1 MODE

MSV.7

OF F

FAN (exhaust fan)

DMPR (damper)

= select / set value AO2

AO2 MODE

MSV.8

OF F

FAN (exhaust fan)

DMPR (damper)

Go to "AO2"
FAN DELAY SECONDS 2 sec (1-255 sec)

AV.17

DAMPER DELAY SECONDS AV.20 2 sec (0-255 sec)

Go to "BO1"
FAN DELAY SECONDS 2 sec (1-255 sec)

AV.17

FAN MIN VOLT 0V (0-10V)

AV.18

FAN MAX VOLT AV.19 10V (0-10V)

Go to "AO2"

AO1 SIGNAL RANGE VOLT MSV.14
2-10 (Vdc Sensor) 0-10 (Vdc Sensor)

Go to "AO2"

FAN MIN VOLT 0V (0-10V)

AV.18

FAN MAX VOLT 10V (0-10V)

AV.19 Go to "BO1"

= select / set value

BO1

BO1 MODE

MSV.9

OF F

FAN (exhaust fan)

DMPR (damper)

= select / set value BO2

BO2 MODE

MSV.10

OF F

FAN (exhaust fan)

DMPR (damper)

DAMPER DELAY SECONDS AV.20 2 sec (0-255 sec)

Go to "BO2"
FAN DELAY SECONDS 2 sec (1-255 sec)

AV.17

AO2 SIGNAL RANGE VOLT MSV.15 2-10 (Vdc Sensor) 0-10 (Vdc Sensor)
Go to "BO2"

Go to "BO1"

DAMPER DELAY SECONDS AV.20 2 sec (0-255 sec)

Go to "BO2"

Go to "Ctrl"
FAN DELAY SECONDS AV.17 2 sec (1-255 sec)

Go to "Ctrl

DAMPER DELAY SECONDS AV.20 2 sec (0-255 sec)

Go to "Ctrl"

www.neptronic.com

Page | 15

Compact Make-up Air Unit
Specification and Installation Instructions

Control ­ Menu Overview (3 of 4) | Ctrl

Main Menu

Sub Menu

= scroll menu items
Main Menu

Configuration
*** To save any changes, press on TDF *** *** To return to the previous step without saving, press

on TDF ***

INPt (Inputs) OutP (Outputs) Ctrl (Control)

= select / set value

CNTRL TEMP MODE

MSV.16

SAT (supply air temperature) RAT (room air temperature)

CO2 EXTRACT DIS (disable) ENA (enable)

BV.15

DRY MODE BV.14 DIS (disable) ENA (enable)

STATIC PRESSUR LOOP BV.16 DIS (disable) ENA (enable)

OCC MIN TIME MINUTES AV.21 30 min (0-240 min)

Go to "Alar"

Alar (Alarm)

www.neptronic.com

Page | 16

Compact Make-up Air Unit
Specification and Installation Instructions

Alarm ­ Menu Overview (4 of 4) | Alar

Main Menu

Sub Menu

= scroll menu items
Main Menu

Configuration
*** To save any changes, press on TDF *** *** To return to the previous step without saving, press

on TDF ***

INPt (Inputs) OutP (Outputs) Ctrl (Control)

= scroll menu items
Alarm Host Comm

= select / set value
Therm Cutout Alarm BV.19
0 1

Comm Timeout Alarm 0 1

BV.20

Ssr Cutout Alarm 0 1

BV.21

Board Cutout Alarm BV.22 0 1

Ssor1 Alarm
0 1

BV.23

Ssor2 Alarm
0 1

BV.24

Board Temp Alarm 0 1

BV.25

Ssr Temp Alarm
0 1

BV.26

Alar (Alarm)

Fan Temp Alarm
0 1

BV.27

Air Flow Alarm 0 1

BV.28

Invalid Config Alarm BV.29
0 1

No Heat Detect Alarm BV.30
0 1

Invalid Input Signal Alarm BV.31
0 1

Go to "INPt"

= select / set value
Damper Blocked Alarm BV.32
0 1

Damper Blocked Status BV.33 0 1

Sat Not Detect Alarm BV.34 0 1

Rat Not Detect Alarm BV.35 0 1

Com Timeout Alarm 0 1

BV.36

AI1 Error Alarm
0 1

BV.37

AI2 Error Alarm 0 1

BV.38

No Heat Detect Alarm BV.39
0 1

Invalid Setpnt Alarm BV.40 0 1

Go to "INPt"

www.neptronic.com

Page | 17

Compact Make-up Air Unit
Specification and Installation Instructions

Operation Menus
This menu is accessible through normal operation mode using the TDF digital room sensor.

1. The Mode Selector jumper (JP1) of the digital room sensor must be set to the "RUN" position (Operation Mode).

2. Press the and

buttons simultaneously for 5 seconds. The "Enter Password" screen appears.

3. Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the and

buttons to

toggle between the digits.

a. Password 637 = Network Settings Menu

b. Password 757 = Configuration Menu

4. If you enter the wrong password, the digital room sensor displays "Eror" and returns to Operation Mode. The digital room

sensor will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press

any key for 5 minutes. The changed values will be saved automatically.

Menu 637 ­ Network Settings

= scroll menu items
Network bAC (BACnet) mOd (Modbus) End (exit menu)
Exit menu and return to normal operation

= select / set value
KBAUD RATE Auto 9.6 (9600) 19.2 (19200) 38.4 (38400) 57.6 (57600) 76.8 (76800) DipS (DIP switch)
= select / set value
KBAUD RATE Auto 9.6 (9600) 19.2 (19200) 38.4 (38400) 57.6 (57600) 76.8 (76800) DipS (DIP switch)

MAC Address 0 (0-254)

MAX Master 127 (1-127)

DEVICE INSTANC IS NEXT Go

0153000 0 (device instance)

Returns to run mode

COMPORT CONFIG
NP2s (no parity, 2 stop bits) EP1s (even parity, 1 stop bit) OP1s (odd parity, 1 stop bit)

ADDRESS 1 (1-246)

COMM TIMEOUT 900 sec (15-1800 sec)

Returns to run mode

*** To save any changes, press on TDF *** *** To return to the previous step without saving, press

on TDF ***

www.neptronic.com

Page | 18

Compact Make-up Air Unit
Specification and Installation Instructions

Menu 757 ­ Configuration

= select / set value

TEMP SETPNT SOURCE
OnBo (on board) TSTA (thermostat) NET (network)

MSV.17

= scroll menu items
Config StPt (setpoint) PID (PID control) SCHd (schedule) Optn (options) OfSt (offset) End (exit menu)
Exit menu and return to normal operation

TEMP SETPNT LOCK ON OF F

BV.10

TEMP MIN SETPNT

AV.22

15°C/59°F (0°C-35°C/32°F-212°F)

TEMP AUTO PID ON OF F

BV.39

TEMP MAX SETPNT

AV.23

25°C/77°F (0°C-35°C/32°F-212°F)

UNOCC AIRFLOW STPNT PERCENT

100% (0-100%)

AV.14

OCCUP PRESSUR SETPNT PASCAL

150Pa (0-1250Pa)

AV.27

CO2 dEADBND ppm AV.30 200PPM (0-200PPM)

Go to PID

SAT CONTROL BAND

AV.45

3°C/37°F (2-10°C/36-50°F)

DRYMODE SETPNT 50% (10-90%)

AV.24

UNOCCUP PRESSUR SETPNT PASCAL

150Pa (0-1250Pa)

AV.28

OCCUP AIRFLOW STPNT PERCENT

100% (0-100%)

AV.13

TEMP INTEGRA TIME 10 sec (0-255 sec)

AV.40

DRYMODE DEADBND 5% (1-10%)

AV.25

NO HEAT DB

AV.47

3.5°C/38.3°F (2-8°C/36-46°F)

CO2 SETPNT PPM 800PPM (0-1000PPM)

AV.28

ST PRSS PROP BAND 10Pa (0-250Pa)

AV.42

ST PRSS DERIVAT TIME 0 sec (0-255 sec)

AV.44

Go to SCHd

TEMP PROP BAND

AV.39

2.0°C/36°F (0.5°C-20°C/33°F-68°F)

TEMP DERIVAT TIME 0 sec (0-255 sec)

AV.41

DB DELAY TIME 60 sec (30-240 sec)

AV.48

ST PRSS INTEGRA TIME 10 sec (0-255 sec)

AV.43

= scroll menu items
Schedul HrS (time) dAtE (Date) Opt (options) SCHd (schedule) End (exit menu)
Exit menu and go to Optn

= select / set value

ENABLE OCCUP INPUTS
No Yes

BV.13

= select / set value

SAT OFFSET

AV.31

Actual °C/°F (±5°C/9°F)

Format 12h 24h
Year 2000 (2000-2136)
Enable Schedule No Yes
Day of Week mo (Monday) tu (Tuesday) wE (Wednesday) th (Thursday) Fr (Friday) Sa (Saturday) Su (Sunday)
OCCUP INPUTS INACTV MODE BV.17 Unoc (unoccupied) OF F

OAT OFFSET

AV.33

Actual °C/°F (±5°C/9°F)

Hours 00 (00-23)

Minutes 00 (00-59)

Go to dAtE

Month 01 (01-12)

Day 01 (01-31)

Go to Opt

Schedul Default Value
Occ (occupancy) nOcc (non occupancy) Off

Schedul PRIO For Writing 16 (1-16)

E1 00:00
E1 - E6 (event) 00 - 23 hours 00, 15, 30, 45 minutes OFF, Occ (occupancy), nOcc (non occupancy), -- (null)

Go to Optn

Reset Schedule No Yes

TOP LINE VALUE

MSV.18

None Time CO2 (carbon dioxide) SARH (supply air relative humidity) RARH (room air relative humidity)

DISP TEMP VALUE

MSV.19

DFLT (default) ALT (alternate) SAT (supply air temperature) TSTA (Thermostat)

Go to OfSt

SARH OFFSET

AV.32

Actual %RH (±5 %RH)

OARH OFFSET

AV.34

Actual %RH (±5 %RH)

Returns to run mode

Go to SCHd

*** To save any changes, press on TDF *** *** To return to the previous step without saving, press

on TDF ***

www.neptronic.com

Page | 19

Compact Make-up Air Unit
Specification and Installation Instructions

Maintenance
Neptronic make-up air units do not require specific maintenance; however, we recommend a yearly inspection, typically before the winter season or after a long term shut down.
Visual Inspection
Risk of electric shock. Disconnect all supplies before any visual inspection.

o Verify condition of heating elements. o Heating element must be clean and free of dust or lint. o Open Coil: Carefully verify that there is no dust accumulation. Any dust of lint accumulation can lead to fire hazard. o Verify any indication of overheating conditions (discoloration) as well as any trace of oxidation (rust).

Electrical Inspection

Risk of electric shock. Disconnect all supplies before any electrical inspection.
o Verify that electrical connections are correct and properly tightened. o Verify the condition of fuses. o Verify resistance of each circuit against ground. o Verify correct operation of contactor(s). o If necessary, electrical components must be replaced only with identical origin components.

Filter Maintenance

Risk of electric shock. Disconnect all supplies before removing and inspecting the filter.
o CMU is equipped with a filter that must be washed at regular intervals. o Check the filter after two months of operation. o To take out the filter, remove the access cover by disconnecting the two screws. o If the filter is extremely dirty, increase the frequency of inspections. o Ensure that the filter is dry before replacing it.

!

Warning, the CMU must always have a filter installed at this location even if an auxiliary filter is used.

Filter

General Warranty
This product is subject to the terms and conditions described at http://www.neptronic.com/Sales-Conditions.aspx.
Technical Support
For any questions or specific requests, please consult our web site: www.neptronic.com Or call: 1 800 361-2308 or (514) 333-1433.

www.neptronic.com

Page | 20

Notes

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com
Toll free in North America: 1-800-361-2308 Tel.: (514) 333-1433 Fax: (514) 333-3163
Customer service fax: (514) 333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time)



References

Microsoft Word for Microsoft 365