Thank you for choosing a NIVELCO product!

1. APPLICATION
The UNICONT PKK­312­ series comprises 4...20 mA current controlled limit switches. The relay output of the units switch at the current limit values (taught to the unit), depending on the limits, switching difference or window comparison modes. Error status indication can be programmed so that the relay gets energized or de-energized when detecting a failure. Failure may be discontinuity in the cable / lower value fault current or short circuit / upper value error current. The unit is suitable for powering all NIVELCO manufactured 2-wire (4...20 mA) transmitters. Some models of this series meet the requirements of intrinsically safe operation. The UNICONT PKK­312­8 Ex can monitor the DC powered, 2-wire NIVOSWITCH Ex type vibrating fork's output current changes between freely vibrating and immersed states without any further programming.

Relay

2. TECHNICAL DATA 2.1 GENERAL
Type Nominal input current range Accuracy of switching level / Threshold level Discontinuity threshold / Lower value fault current Short circuit threshold / Upper value fault current Input impedance Input overload capability Switching delay
­ Output ­ Rating ­ Insulation strength ­ Electrical / Mechanical life expectancy
Electrical connection
Mechanical connection Ingress protection Weight

PKK­312­
1...22 mA ±0.1 mA 3.7 mA 22 mA
10  Max. 100 mA (continuous) 0.1 s; 1 s; 2 s; 5 s selectable
1× SPDT 250 V AC, 8 A, AC1
4000 V 50 Hz 105 / 2 x 106 switching Max. 2.5 mm2 (AWG14) twisted, or max 4 mm2 (AWG12) solid wire
EN 60715-35 rail IP20
~210 g (~0.5 lb)

2.2 SPECIAL DATA
Type Power supply range Power consumption Safety maximum voltage Switching levels Ex marking
Intrinsic safety data
Output load capability Electrical protection Reference document number Ambient temperature

Ex version

PKK­312­5Ex PKK­312­6Ex PKK­312­7Ex PKK­312­8Ex

230 V AC ±10% 110 V AC ±10%

50...60 Hz

50...60 Hz

24 V AC ±10%, 50...60 Hz, 24 V DC ±15%

< 2.5 VA

< 2.5 VA or < 2.5 W

Um = 253 V AC

2 values in the range of 1...22 mA

10.5 mA; 12.5 mA

II (1) G [Ex ia Ga] IIB

II (1) G [Ex ia Ga] IIC

II (1) D[Ex ia Da] IIIC

II (1) D[Ex ia Da] IIIC

PKK­312­1
230 V AC ±10% 50...60 Hz

Standard version

PKK­312­2

PKK­312­3

PKK­312­4

110 V AC ±10% 24 V AC ±10% 24 V AC ±10%, 50...60 Hz,

50...60 Hz

50...60 Hz

24 V DC ±15%

< 2.7 VA

< 2.5 W

­

2 values in the range of 1...22 mA

­

U0 = 28.4 V; I0 = 140 mA; P0 = 1 W;

U0 = 28.4 V; I0 = 80 mA; P0 = 0.6 W

­

L0 = 6 mH; C0 = 50 nF

L0 = 4 mH; C0 = 50 nF

IT = 22 mA when UOUT  12 V

IT = 22 mA when UOUT  15 V

­

U0 = 30 V IMAX = 70 mA UOUT min = 16 V

Class II

Class III

Class II

pkk3121m060bh_06

­

-25...+55 °C (-13...+131 °F)

U0 = 24 V IMAX = 80 mA UOUT min = 23 V
Class III

2.3 ACCESSORIES ­ User's Manual ­ Warranty Card ­ EU Declaration of Conformity
2.4 DIMENSIONS

3. INSTALLATION UNICONT PKK­312­ must be mounted on an EN 60715-35 rail.
ATTENTION! Before installing the device, make sure that the input current values can be provided by the loop of the application. If not, teach the current values to the device before installing it. (See chapter 5 "Commissioning, Setting, Programming")

4. WIRING 4.1 EX MODELS
PKK­312­8Ex with NIVOSWITCH Ex vibrating
fork

PKK­312­7Ex with 2-wire Ex transmitter (e.g. EchoTREK
SEA­380­6 Ex)

PKK­312­5Ex ... PKK­312­7Ex for monitoring of Ex passive
switch and cable

2.5 ORDER CODE

PKK­ 3 1 2 ­

EX*

POWER SUPPLY / EX

230 V AC

110 V AC

24 V AC

24 V AC / DC

230 V AC

EX

110 V AC

EX

24 V AC / DC EX

24 V AC/ DC EX

CODE 1 2 3 4 5 6 7 8**

* Order codes of an Ex versions end in 'Ex' ** For DC powered, 2-wire NIVOSWITCH Ex vibrating fork of NIVELCO

4.2 STANDARD MODELS
PKK­312­1 ... PKK­312­4 with 4-wire active transmitter (e.g. EchoTREK STA­460)

PKK­312­1 ... PKK­312­4 with 4 wire active transmitter (e.g. MICROSONAR UTS­211)

PKK­312­1 ... PKK­312­4 for monitoring of passive switch

pkk312en21h06  2/1

5. COMMISSIONING, SETTING, PROGRAMMING 3 seconds after powering up, the unit begins to work with the signals as per the table of WORKING STATUS.

Working status

LED

Status

Interpretation

GREEN

Relay energized R = 1

(SELECT)

RED SIMULTANOUS RED BLINKING
OF BOTH LED

Relay de-energized R = 0
Memory failure, Relay state sustained

FAIL (STEP)

GREEN RED

No cable fault/No fault current. No cable monitoring
Cable fault, or. fault current

The relay states relating to the operating modes and the input current are shown in the first diagram. Operation with delayed switching is demonstrated in the second diagram below.

State of the relay depending on the input current

Relay operation with delayed switching
CAUTION! If the input current is between the trigger points in hysteresis comparison mode when the unit is switched on, the relay will always be de-energized (R = 1 or R = 0) regardless of the operating mode.

Depending on the actual task, the unit may need programming, which involves setting the operating mode (except PKK­312­8Ex type) and the re-learning of the switching points. The PKK­312­8Ex device without any additional programming is also suitable for the attenuated and unattenuated monitoring of the 2-wire DC-powered NIVOSWITCH Ex vibrating fork and for the monitoring of the current consumption associated with its unattenuated state and, based on this, to influence the state of the relay output. For this type the trigger points current values of 10.5 and 12.5 mA and switching differential operating mode cannot be changed.
Settings:

Relay operating mode Cable discontinuity monitoring Cable short circuit monitoring Damping Revert to default

(Default: R = 1) (Default: NONE) (Default: NONE) (Default: 0.1 s)

A PKK­312­1 ... PKK­312­7Ex Settings:

Teaching current value Relay operating mode Selecting comparison type Cable discontinuity monitoring Cable short circuit monitoring Damping Revert to default

(Default: 10.5 mA and 12.5 mA) (Default: R = 1) (Default: Switching difference) (Default: NONE) (Default: NONE) (Default: 0.1 s)

PROGRAMMING Programming involves setting the operating mode and learning of the input current values.
Programming / reading the operating mode To initiate programming mode, press and hold the A button for about 5 seconds till the LED 'PROGRAM' lights up. To access the adjusting columns (as per the table below), press the A button briefly while in programming mode, and the steps will be indicated by the relevant LED 'STEP'. The rows of the columns can be selected by pressing the B button, and the 'SELECT' LED will indicate the choice. After performing the necessary adjustments, exit programming mode by pressing and holding the A button for about 5 seconds until the LED 'PROGRAM' goes off.

pkk312en21h06  2/2

PROGRAMMING / READING THE OPERATING MODE

Enter programming mode: press key A (for about 5 s) till the LED PROGRAM lights up

Adjustment columns with corresponding LED STEP states, accessed by short pressing of key A

GREEN

GREEN BLINKING

RED

RED BLINKING

OFF

Relay operation
mode

Comparison Cable short circuit */ Cable discontinuity */

operation monitoring lower

monitoring upper

mode

current

current

Switching delay

Adjustment row with relevant state
of the LED SELECT, selected by short pressing
of key B

R = 1

Limit value 1.

ON, relay should be activated

ON, relay should be activated

0.1 s

GREEN

R = 0

Limit value 2.

ON, relay should be released

ON, relay should be released

1 s

GREEN BLINKING

--

Hysteresis

NO

NO

2 s

RED

--

Window

--

--

5 s

RED BLINKING

Quit programming mode: press key A (for about 5 s) till the LED PROGRAM goes off.

* Cable monitoring can only be applied with Ex certified 2-wire units

AUTO-QUIT PROGRAMMING MODE The unit will operate during programming by the previous parameters. The new, modified parameters will only take effect after quitting programming mode. If the transmitter is left in programming mode, it will automatically quit programming mode after 30 seconds, and the modified values will not take effect.

RELAY TEST The proper operation of the relay can be tested by pressing the B button for about 5 seconds. The state of the relay and the color of the LED will change (e. g., from green to red). Releasing the key makes the relay and the LED revert to their previous state.

REVERT TO DEFAULT The device reverts to the factory default programming values if buttons A and B are pressed together before/during power-up.

TEACHING CURRENT VALUE OF TRIGGER POINT Teaching input currents involves saving the Iin current values for switching points 1 and 2 between the terminals (figure on the right) at the moment of the teaching. The circuits on the application site can produce necessary current values. If the circuit of the actual application produces the input current, the actual current values do not have to be known.

Arrangements for teaching input currents

To teach the current values, press the buttons A and B simultaneously for about 5 seconds until the device enters teaching mode, indicated by the blinking of LED 'PROGRAM'. Release one of the buttons (A or B), and the momentary current value will be assigned to switching point 1 or 2. Release the other button, and the teaching process is completed, indicated by the going off of LED 'PROGRAM'.

You can teach the other limit value without exiting programming mode if you do not release the other button and press the one that was released for 5 seconds, then release the button you kept pressed while teaching the first value.

Entering teaching mode Teaching current value for point 1
Quitting teaching mode
Entering teaching mode Teaching current value for point 2
Quitting teaching mode

Status of key A

Teaching

Status of key B

STEP LED

KEEP PRESSED > 5 s

OFF

KEEP PRESSED

RELEASE

RELEASE

-

KEEP PRESSED > 5 s

RELEASE

KEEP PRESSED

-

RELEASE

OFF
According to WORKING STATUS
OFF
GREEN if SUCCESSFUL RED blinking if
FAILED According to WORKING
STATUS

PROGRAM LED
blinking
OFF
blinking
OFF

SELECT LED
OFF
GREEN if SUCCESSFUL RED blinking if
FAILED According to WORKING
STATUS
OFF
OFF
According to WORKING STATUS

6. MAINTENANCE AND REPAIR
The device does not require regular maintenance. The warranty card contains the terms and conditions. Before returning the device for repairs, it must be cleaned thoroughly. The parts in contact with the medium may contain harmful substances; therefore, they must be decontaminated. Our official form (Returned Equipment Handling Form) must be filled and enclosed in the parcel. Download it from our website www.nivelco.com. The device must be sent back with a declaration of decontamination. A statement must be provided in the declaration that the decontamination process was successfully completed and that the device is clean from any hazardous substances.
7. STORAGE CONDITIONS
Ambient temperature: -30...+60 °C (-22...+140 °F) Relative humidity: max. 98%.
pkk312en21h06 October 2021 NIVELCO reserves the right to change anything in this manual without notice!