D25t, D32t, D40t, D50t, D63t. ZUBR Dt with thermal protection. ZUBR D25t. ZUBR D32t. ZUBR D40t. ZUBR D50t. ZUBR D63t. 2. 3. 4. Purpose. Before the installation ...


File Info : application/pdf, 2 Pages, 1.42MB

PDF preview unavailable. Download the PDF instead.

manual zubr d25-63t vt57 201221
overvoltage protection
for professionals
ZUBR Dt
with thermal protection D25t, D32t, D40t, D50t, D63t
Indicator of the voltage supply to the load Button of the upper limit and increasing of the parameter Functional menu Button of the lower limit and decreasing of the parameter
Technical passport
Installation and operation manual
Low Voltage Directive 2014/35/EU EMC Directive 2014/30/EU

Purpose
Before the installation and operation of the device, please read by the end of this document. This will help to avoid possible danger, mistakes and misunderstandings.
The quality of circuit voltage must meet the state standards and equal to 230 V with minor deviations. At this voltage oriented manufacturers of home appliances during designing and manufacturing. But real supply voltage does not always correspond to this standards. May occur surges from 160 to 380 V, caused by a number of factors including the following:
-- break and getting zero wire on one of the phases of overhead power lines (most common in the private sector, where dominated overhead power lines);
-- a skew phases, caused by overload of one of the phases of some powerful customer;
-- outdated equipment substations that doesn't meet the consumers power that increased.
The list of protected electrical and electronic equipment, is next: Current domestic consumers such as refrigerators, televisions, video and audio, computers and other electrical equipment that could be sensitive to deviations of supply voltage.
Technical data



Parameters

1 Voltage limit

2 Power Volt
3 Device weight 4 Overall dimensions 5 Connection 6 IP to GOST 14254

Value
upper 220­280 V lower 120­210 V not less than 100 V not more than 420 V 0,21 kg ±10 % 66 × 85 × 53 mm
not more than 16 mm² IP20

Warning! It is forbidden to use voltage relay to protect equipment, which runs from the sources of modified sine, uninterruptible power supply output voltage sinusoid are not Long operation (more than 5 minutes) from the following sources voltage may damage ZUBR and lead to not warranty repair.

Supply package

Voltage relay ZUBR Dt with thermal protection Guarantee certificate and card Technical passport, manual Shipping box

1 piece 1 piece 1 piece
1 piece

Connection scheme

Supply voltage (100 ­ 420 V, 50 Hz) served on terminals 1 and 2, while phase (L) is determined by the indicator and activated on terminal 2 and neutral (N) -- terminal 1.

The connecting voltage wires connected to terminal 3 and neutral terminal block (not included).

Voltage relay

DO NOT connect the voltage with surge zero in terminal 1!

1

2

3

N

L

neutral phase

~100­420 V

Scheme 1.

terminal block

The simplified internal circuit and connection scheme



Parameters

7 Rated load current

8 Rated power

9 Break-time at increasing

10 Break-time at lower: > 120 V < 120 V

11

The number of operating cycles under load of not less cycles

12

The number of operating cycles without load of not less cycles

13 Relay type

ZUBR D25t ZUBR D32t

25  (max 30  in 10 minutes)

32  (max 40  in 10 minutes)

5 500 V

7 000 V

0,01­0,03 sec

ZUBR D40t ZUBR D50t ZUBR D63t

40  (max 50  in 10 minutes)

50  (max 60  in 10 minutes)

63  (max 80  in 10 minutes)

8 800 V

11 000 V

13 900 V

not more than 0,04 sec

not more than 1,2 sec 0,01­0,03 sec
100 000 cycles
1 000 000 cycles electromagnetic

not more than 1,2 sec not more than 0,04 sec
10 000 cycles
500 000 cycles polarized

2

3

load

Installation
The appliance is intended for installation inside residences. The risk of moisture or humidity in the installation site should be minimal. When installing in the bathroom, toilet, kitchen, pool appliance must be located in a shell with protection degree not below IP55 per GOST 14254 (partial protection from dust and waterproof in any direction). The ambient temperature during installation should be within ­5...+45 °.The appliance is installed in a special box, which allows to conduct the easy installation and operation. Cabinet should be equipped with standard mounting rail 35 mm width (DIN rail). The appliance takes in width of three standard module on 18 mm. The height of the appliance should be in the range 0,5...1,7 m from the floor. The appliance is installed and activated after installation and inspection of the voltage.For protection against short circuit and excess capacity in circuit load necessarily need to set in front of the appliance, the automatic circuit-breaker (CB). The automatic switch off is established in the open-phase fault wire, as shown at the scheme 2. It shall be calculated upon the rated load current. To protect person from electric shock leak is set SSD (safety shutdown device).
To connect your device:
-- fix the appliance on the mounting rail (DIN);
-- take a wire;
-- make the connection according to the passport.
Terminals of the device designed for wire cross section up to 16 mm2. To reduce mechanical load on the terminals it is desirable to use soft wire. Clean the end wires of 10 ±0,5 mm. If end is longer, it can cause a short circuit, and if short -- cause unreliable connection. Use the cable lugs. Undo the screws of the terminals and insert tipped end of the wire in terminal. Tighten terminal with derived average 2,4 ·m. Low tight may lead to low contact and overheating terminals and wires and over tight -- damage terminals and wires. Wires protracted in terminals with a screwdriver with a shank width not more than 6 mm.
~100­420 V
terminal block

Voltage
relay
CB

1 SSD

12 3

2

load Scheme 2. Connection of the circuit breaker and SSD (safety shutdown device)
4

Screw with shank width more than 6 mm may apply mechanical damage to terminals. This could result in loss of warranty.
Cutting wires of wiring to which connects voltage relay should meet the value of electric current, which consumes voltage.
It is also necessary to take into account that the load power of 3 000 VA at 220 V will be 4 400 VA at 270 V. Therefore, please, do not allow the relay power handling to exceed its certified value at the maximum voltage deviation to the upper limit. If the relay power handling exceeds its certified value use the electric contactor (magnetic starter, power relay) which is designed for this power capacity.

Exploitation

Enabling

When you turn on the appliance, it

immediately begins to indicate the

main voltage. If the voltage is within

acceptable limits, turns on loading and

green indicator.

The value of voltage that has exceeded the limit will

flash alternating with «U__ __», if the lower limit is

exceeded, and with «U

», if the upper limit is

exceeded.

The upper / lower limit
(factory setting 242 V / 198 V)
To view the upper limit, press the «+», button, to view the lower limit, press the «­» button. Then use the «+» and «­» buttons to change the limit as necessary. In 5 sec after the last pushing buttons relay return to indication of main voltage.

When setting the voltage limits use the protected equipment technical documentation.

Function menu (table 1)
Use the middle button to navigate through the menu.
Use the «+» and «­» buttons to change the parameters. After pressing the button for the first time the parameter will flash, after pressing it for the second time the parameter will change.
In 5 sec after the button was pressed the indicator will return to displaying the system voltage.

5

Table 1. Navigating through the Function menu

Menu section

Enter by pressing the middle button

Screen

Factory Change with setting «+» and «­»

Notes

View the latest emergency voltage

click 1 time

The log is capable of storing the last 50 emergency or overheat alarms. Log entries are displayed in order from the last to the oldest («n 0» is the last entry, «n 1» is the penultimate one, and «n99» is the oldest). To move through the log use the «+» or «­» buttons. When viewing the emergency voltage, the relay will briefly display the emergency alarm number in 1 second.
To reset the log, while viewing it, hold down the middle button for 6 seconds until «rSt.» message appears. After releasing the button, the log will be cleared and the screen will display:«---».

Load delay (delay time to on)
Models of time off when the output voltage limits (professional)

click 2 times
click 3 times

Correction of screen reading

click 4 times

Firmware version

hold the button for 6 sec

Delay time of load turning on
Viewing and controlling the delay are described in the function menu table.
The countdown always will be accompanied by flashing dot in the rightmost discharge indicator is set at 3 sec and more than 100 sec, and when the time remaining is less than 100 sec the display will show a countdown in seconds to the turning on of the load. If the set delay time is more than 3 seconds, in a short-term voltage jump the screen will display the maximum voltage, then the current voltage and the countdown.
For protection of refrigeration equipment, where there is a compressor, it is recommended to set a delay of turning on load 120­180 sec. It will allow to increase the service life of the compressor.
Resetting to the factory settings
To reset the factory settings, hold the three buttons at the same time for more than 12 s. until «dEF» message appears on the screen. After release, reset to factory settings and reboot will take place.

3­600 sec, step 3 sec
(see table 2)

It is used for compressor equipment protection.
Professional model is not off load at safe in magnitude and duration of voltage deviations. The curve taken «ITIC (SVEMA) Curve» (see fig. 1).

±20 V

If necessary adjust the voltage indication.

to view

Attention! The manufacturer reserves the right to modify the firmware to enhance the device technical characteristics.

Protection from inner overheating

In case if the temperature inside the exceed 80 °C, will be emergency lockout of loading. On the screen 1 time/s (overheat) will be displayed. At this time, pressing the middle button will display the temperature of the thermal protection

sensor. The device will be unlocked in case if the temperature inside will decrease to 60 °C.

If the protection trips more than 5 times within 24 hours, the voltage relay is blocked until the temperature inside the case drops to 60 °C («oht» stops blinking) and one of the buttons is pressed.

At breakout or short circuit of temperature sensor, device continues to operate normally, but every four seconds the message «Ert» , indicating the problem with sensor. In this case, control over inner overheating will not be done.

Table 2. Models shutdown exit time voltage beyond

Model

Limit

Limit of power, V

Offline time, sec

The usual default

Upper

220­280

see Technical data table

Lower

120­210 less 120

1 see Technical data table

Professional Upper

more 264 220­264

see Technical data table 0,5

176­210

10

Lower

164­176 less 164

0,5
see Technical data table, item 10, at < 120 V

6

7

POSSIBLE PROBLEMS, CAUSES AND WAYS TO OVERCOME THEM
At turning on neither indicator nor screen do not shine.
Possible cause: There is no power supply voltage. It is necessary to: Ensure supply voltage presence.
After turning on the screen normal voltage level, but load is not turning on.
It is necessary to: Check the detention. In other cases, please, address to a service centre.

Safety instructions
Carefully read and become aware of yourself these instructions.
Connection of the device must be done by a qualified electrician.
Before the installation (dismantling) and connection (disconnection) of the device, turn off voltage supply and also act according to the «Rules of an arrangement of electric installations».
Turning on and off or and configure the device should be with dry hands.
Do not connect the device to the network disassembled. Avoid hitting of water or moisture to the device. Do not expose the device to extreme temperatures (higher than 40 º or below -5°C) and high humidity. Never clean the device with the use of chemicals such as benzene, solvents. Do not store the device and do not use it in areas with the dust. Do not attempt to disassemble and repair the device. Do not exceed the landmarks value adaptor and power. To protect against overvoltage caused by lightning discharges, use a lightning protector. Protect the children from games with the working device, it is dangerous.
Do not fire and do not throw away the device with the household waste.
Device used must be taken in accordance with current legislation. Transportation of goods carried in the package, ensuring the safety of the product. The device is transported by any kind of transport (rail, sea, motor, air transportation). Date of manufacture is on the back side of device.
If you have any questions call the Service centre the telephone number listed below.