Bogen Ceiling Speaker Enclosure & Tile Bridge Models RE84 and TB8
Installation and Use Manual
UL LISTED (UUMW) Flush-Mounted Loudspeaker Installation
For Use In Return Air Ceiling Plenum Spaces
Enclosures (UL Listed) | RE84 |
Intended for use with: | TB8 (Tile Support Bridge) |
RE84 Features
- Listed by Underwriters Laboratories, Inc. Category UUMW.
- Material and construction permits use where ceiling plenum is part of the air handling system.
- Compound knockout(s) provided for listed type metallic type fittings for 1/2" and 3/4" plenum rated cable and plenum whip flex conduit.
- Four horseshoe tab slots provided on each enclosure to mate with four horseshoe tabs on TB8 bridge eliminates the need for screws.
- Two seismic tie-off tabs and four tie-off tab slots with enclosure.
Diagram Description: The RE84 enclosure is shown with features including horseshoe tab slots, tie-off tab slots, clearance holes, screw holes, and knockouts.
TB8 Features
- Distributes the weight of a speaker, grille, and protective enclosure onto the ceiling grid.
- Four locator tabs to prevent sliding on ceiling tile.
- Four horseshoe tabs to mate with four horseshoe tab slots on enclosure.
Diagram Description: The TB8 tile bridge is depicted with locator tabs, horseshoe tabs, and threaded holes for mounting.
Installation Notes
A Listed assembly requires that the enclosed loudspeaker is not exposed within the air handling plenum. Wiring, and/or conduit enclosure entry fittings, and installation must comply with local codes. Many local codes require a separate enclosure assembly with customer-supplied "tie-off" wire to secure the assembly to the top of the building structure.
NOTE: All cable splices and connections to Speaker/Transformer pigtails must be made inside of Listed enclosure.
TB8 Installation
- Place ceiling tile with the finished side facing up over a large trash can (provides support and saves clean up time).
- Cut hole in the center of the ceiling tile using the raw speaker as a template.
- Position the tile bridge on the unfinished side of the ceiling tile and bend (4) locator tabs into tile opening to prevent sliding.
- Install Ceiling Speaker assembly using (4) 8-32 screws and the threaded holes of the tile bridge as shown. (Screws are provided with Ceiling Speaker assembly).
Diagram Description: Illustrates the TB8 tile bridge positioned on a ceiling tile, with arrows indicating the bending of locator tabs and the attachment of the speaker assembly.
TB8 with RE84 Installation
- Place ceiling tile with the finished side facing up over a large trash can (provides support and saves clean up time).
- Cut hole in the center of the ceiling tile using the raw speaker as a template.
- Bend (4) horseshoe tabs up on tile bridge.
- Position the tile bridge on the unfinished side of the ceiling tile and bend (4) locator tabs into tile opening to prevent sliding.
- Slip seismic mounting tie-off tabs (2) through RE84 tie-off tab slots until they click into place and secure customer-supplied "tie-off" wire to tab.
- Punch out knockout in the RE84 and install Listed metallic enclosure entry fitting to knockout to accommodate plenum cable or plenum whip and feed cable or whip through the knockout.
- Install RE84 to tile bridge by orienting horseshoe tab slots (4) over horseshoe tabs (4) of bridge.
- With pliers, twist horseshoe tabs (4) of tile bridge 1/2 turn, securing enclosure to bridge.
- Screw the Ceiling Speaker assembly to the RE84 using (4) 8-32 screws provided with the Ceiling Speaker assembly, sandwiching the TB8 and ceiling tile in between. The screws must go through the TB8 clearance holes as shown. (Screws anchor into the RE84).
Diagram Description: Shows the step-by-step assembly of the RE84 enclosure and TB8 tile bridge onto a ceiling tile, including details on tab orientation and screw placement.
Diagram Description: A detailed view of the assembled RE84 and TB8 components on a ceiling tile, highlighting the connection points and clearances.
Limited Warranty
The RE84 and TB8 are warranted to be free from defects in material or workmanship for two (2) years from the date of sale to the original purchaser. Any part of the product covered by this warranty that, with normal installation and use, becomes defective will be repaired or replaced by Bogen, at our option, provided the product is shipped insured and prepaid to: Bogen Factory Service Department, 50 Spring Street, Ramsey, NJ 07446, USA. The product will be returned to you freight prepaid.
This warranty does not extend to any of our products that have been subjected to abuse, misuse, improper storage, neglect, accident, improper installation or have been modified or repaired or altered in any manner whatsoever, or where the serial number or date code has been removed or defaced.
THE FOREGOING LIMITED WARRANTY IS BOGEN'S SOLE AND EXCLUSIVE WARRANTY AND THE PURCHASER'S SOLE AND EXCLUSIVE REMEDY. BOGEN MAKES NO OTHER WARRANTIES OF ANY KIND, EITHER EXPRESS OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED TO THE MAXIMUM EXTENT ALLOWABLE BY LAW. Bogen's liability arising out of the manufacture, sale or supplying of products or their use or disposition, whether based upon warranty, contract, tort or otherwise, shall be limited to the price of the product. In no event shall Bogen be liable for special, incidental or consequential damages (including, but not limited to, loss of profits, loss of data or loss of use damages) arising out of the manufacture, sale or supplying of products, even if Bogen has been advised of the possibility of such damages or losses. Some States do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from State to State.
Products that are out of warranty will also be repaired by the Bogen Factory Service Department - same address as above or call 201-934-8500. The parts and labor involved in these repairs are warranted for 90 days when repaired by the Bogen Factory Service Department. All shipping charges in addition to parts and labor charges will be at the owner's expense. All returns require a Return Authorization number.