GeneralAire Model 5500 Steam Cylinder Replacement Instructions

Steam Cylinder Replacement: Model 55-GFI #7746 (USA) and Model GF-55 (Canada)

WARNING: The humidifier and the cylinder contain live electrical components and very hot surfaces. All service and maintenance operations must be carried out by qualified personnel who are aware of the necessary precautions. Before performing any operations on the cylinder, make sure that the humidifier is disconnected from the power supply. Remove the cylinder from the humidifier only after having drained it completely.

Conductivity

Conductivity measurements indicate the amount of minerals in the water. The GeneralAire® Model 5500 includes a cylinder designed to be used with conductivity levels between 125 and 1250 µS/cm.

Removing and Cleaning Components

CAUTION: The cylinder may reach high temperatures. Let it cool down before touching it or wear protective gloves.

1. To Remove the Cylinder

NOTE: The cylinder must be replaced annually by a duly qualified technician. The steam hose and drain hose must be inspected annually. At the first sign of degradation or leaking, immediately replace the hose - do not wait for an annual inspection.

2. Cleaning the Fill Or Mixing Valve and Drain Pump

e.) Special notes for Drain Pump:

Reassembling and Restarting

The following operations should be performed with a COLD cylinder.

1. Replace components

2. Install the cylinder:

NOTE: Ensure that the components, hoses and cylinder are replaced with correct O-rings and gaskets. Open water supply and check for leaks. Ensure that the steam hose clamp is snug, but not over-tightened.

3. Pre-clean the new cylinder:

WARNING: DO NOT confirm any value higher than 04. If 05 or higher is displayed, press “reset” until the display goes back to the normal operating mode and restart from step a).

4. Resetting the cylinder hour counter:

5. Final check:

Safety and Disposal

WARNING: RISK OF BURNING

Diagram illustrating the risk of burning with an arrow pointing to the cylinder.

Press [click sound indicator] to proceed.

The product must be installed with ground connection, using the special yellow-green terminal on the terminal block. Do not use the neutral for the ground.

Disposal of Product

The product must be disposed of separately in accordance with the local waste disposal legislation in force.

Models: 5500 Steam Cylinder Replacement, 5500, Steam Cylinder Replacement, Cylinder Replacement

File Info : application/pdf, 4 Pages, 513.27KB

PDF preview unavailable. Download the PDF instead.

GF168-Cylinder-Replacement-Instructions

References

Adobe PDF Library 17.0 Adobe InDesign 18.1 (Windows)

Related Documents

Preview GeneralAire GFX4 Digital Humidistat Installation and Operating Instructions
Comprehensive guide for installing and operating the GeneralAire GFX4 Digital Humidistat with Furnace Blower Motor Control. Includes specifications, wiring diagrams, troubleshooting, and warranty information.
Preview GeneralAire MAC and GF Series Air Cleaners Spec Sheet
Detailed specifications for GeneralAire's MAC and GF Series residential whole-house air cleaners, including model numbers, dimensions, weight, MERV ratings, and airflow performance.
Preview GeneralAire GF5500 Steam Humidifier Installation Guide
A step-by-step guide for installing the GeneralAire GF5500 Steam Humidifier, covering daily water calculations, conductivity testing, and configuration for amps/voltage, along with information on Remote Mount Blowers.