Installation Instructions
Model BTC-1 Backup Tone Card

INTRODUCTION
The Model BTC-1 Backup Tone Card from Siemens Industry, Inc. provides two tones for the MXLV System that can be selected by dipswitches. This card can be installed on top of the ACM-1 to provide backup of the two primary tones should the tone generator of the ACM-1 fail. The BTC-1 can also be installed on the OCC-1 Output Control Card module to provide a default tone when the low power riser fails and when the OCC-1 loses contact with the MMB.
Select the two backup tones on switch S1 by matching SW1-SW4 and SW5-SW8 to the CSG-M (AccuLINK) configuration tone selections. Table 1 on the next page shows the switch settings for each available tone.
For additional information on the Voice System, refer to the MXLV Manual, P/N 315-092036.
INSTALLATION
Remove all system power before installation, first battery and then AC. (To power up, first connect the AC and then the battery.)
1. Remove the card from its protective bag.

2. Refer to the function section of the CSG-M configuration printout for the tones to be configured.
3. Set the desired tones on switch S1 using dipswitches SW1-SW4 for the first tone selection and dipswitches SW5-SW8 for the second tone selection.
a. Refer to Figure 2 or 3 on page 3 for the location of S1.
b. Refer to Table 1 for the switch settings and their associated tones.
c. Set the tones (See Note at the top of the next page).
Do not install the BTC-1 on the ACM-1 or OCC-1 until the system is ready for the installation of PC cards. Until then, keep the BTC-1 in its protective bag.
Mounting
The BTC-1 mounts on either the ACM-1 (See Figure 2) or the OCC-1 (See Figure 3) with two snap-in type standoffs and a comblike connector.
1. Install the standoffs and comb connector in the component side of the ACM-1 or the OCC-1, whichever is appropriate. (See Note at top of the next page.)

Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-090919-8

Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada

firealarmresources.com

Figure 1 BTC-1 Backup Tone Card Module

Note: Mount on an ACM-1 to provide a backup for the two primary tones.
Mount on an OCC-1 to provide a default tone in degrade mode when communication to the MXL fails and there is a local alarm detected. This is useful only if the OCC-1 is providing input to the amplifier.

TABLE 1 Setting the Tones on Switch 1

SETTING

4321

8765

0000

0000

000X

000X

00X0

00X0

00XX

00XX

0X00

0X00

0X0X

0X0X

0XX0

0XX0

0XXX

0XXX

X000

X000

X00X

X00X

X0X0

X0X0

X0XX

X0XX

XX00

XX00

XX0X

XX0X

XXX0

XXX0

XXXX

XXXX

TONE
Illegal Chime 2000 Hz Slow Whoop Yelp Wail California code 900 Hz pulsed at 30 pulses per minute lllegal Horn Temporal code 3 900 Hz pulsed at 30 pulses per minute Yeow High/Low Illegal 900 Hz tone

X = Switch closed OR ON; 0 = Switch open OR OFF

Note: To open a dipswitch, press down on the side of the dipswitch marked OPEN. To close a dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.

To open a slide switch, push the slide to the side opposite the side marked ON. To close a slide switch, push the slide to the side marked ON.

2
firealarmresources.com

2. Position the BTC-1 over the connector and standoffs with the components of the board facing out. Be certain that the standoffs and the connector pins line up with their respective holes in the BTC-1 card and connector.
3. Place the BTC-1 on the standoffs and connector by pressing them into place. This takes some effort. Be careful because once the standoffs are installed, they are difficult to remove. (If it is

necessary to remove the BTC-1 from either the ACM-1 or the OCC-1, first disconnect the system.)

ELECTRICAL RATINGS

Active 5VDC Module Current Active 24VDC Module Current Standby 24VDC Module Current

10mA 40mA 45mA

Figure 2 Mounting the BTC-1 on the ACM-1

Figure 3 Mounting the BTC-1 on the OCC-1
3
firealarmresources.com

Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-090919-8