Installation Guide for TRANE models including: 4TWV0024A1000C, 4TWV0036A1000C, 4TWV0024A1000C Heat Pumps and Air Conditioners, Heat Pumps and Air Conditioners, and Air Conditioners, Air Conditioners, Conditioners, 4TWV0048A1000C, 4TWV0060A1000C, 4TTV0024A1000C, 4TTV0036B1000C, 4TTV0048A1000C, 4TTV0060A1000C, 4TTV0061A1000C

Installer's Guide

Search Results: PROD-SLB060-EN - Public


File Info : application/pdf, 28 Pages, 2.98MB

PDF preview unavailable. Download the PDF instead.

18-BC89D1-1M-EN 07202023
Installer's Guide

Variable Speed ComfortLinkTM II Heat Pumps and Air Conditioners

4TWV0024A1000C 4TWV0036A1000C 4TWV0048A1000C 4TWV0060A1000C

4TTV0024A1000C 4TTV0036B1000C 4TTV0048A1000C 4TTV0060A1000C 4TTV0061A1000C

Scan to see help videos on this product

Note: "Graphics in this document are for representation only. Actual model may differ in appearance."

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

July 2023

18-BC89D1-1M-EN

SAFETY SECTION -- OUTDOOR

Important -- This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
WARNING
HAZARDOUS VOLTAGE!
Failure to follow this Warning could result in property damage, severe personal injury, or death. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.
WARNING
REFRIGERANT OIL!
Any attempt to repair a central air conditioning product may result in property damage, severe personal injury, or death. These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a "Rose" color to indicate the type of refrigerant and may contain a "dip" tube to allow for charging of liquid refrigerant into the system. All R-410A systems with variable speed compressors use a PVE oil that readily absorbs moisture from the atmosphere. To limit this "hygroscopic" action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement.
CAUTION
HOT SURFACE!
May cause minor to severe burning. Failure to follow this Caution could result in property damage or personal injury. Do not touch top of compressor.

CAUTION
CONTAINS REFRIGERANT!
Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening system.
CAUTION
GROUNDING REQUIRED!
Failure to inspect or use proper service tools may result in equipment damage or personal injury. Reconnect all grounding devices. All parts of this product that are capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
WARNING
SERVICE VALVES!
Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and/or property damage. Extreme caution should be exercised when opening the Suction and Liquid Line Service Valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. No torque is required.
WARNING
BRAZING REQUIRED ­ IF USING MECHANICAL CONNECTIONS, ENSURE LEAK TEST IS NEGATIVE!
Failure to inspect lines or use proper service tools may result in equipment damage or personal injury. If using existing refrigerant lines make certain that all joints are brazed, not soldered.

WARNING
HIGH LEAKAGE CURRENT!
Failure to follow this Warning could result in property damage, severe personal injury, or death. Earth connection essential before connecting electrical supply.

©2023 Trane

18-BC89D1-1M-EN

WARNING

SAFETY SECTION -- OUTDOOR

400 VOLTS ELECTRICAL HAZARD
Failure to follow this warning coul d result in personal injury or death.
WAIT TWO (2) MINUTES after disconnecting power prior to touching electrical components as they may hold a dangerous charge of 400VDC, then verify DC Voltage is less than 42 VDC at inverter test points labeled +VDC and -VDC before servicing board.

+VDC

-VDC

CAUTION - HOT SURFACE
+ VDC and - VDC

Approved Combinations for Variable Speed Units
· TCONT850, TZONE950, or TZON1050 · TAM9 · TAM8C · TEM8 · S9V2 Furnace w/Relay Panel · XC80 Furnace · XC95m Furnace · Approved System Accessories
Note: See AHRI directory for approved indoor and outdoor model combinations. Only Trane / American Standard coils and air handlers are approved for use with variable speed outdoor units.

Table 1. Operating Range
Cooling Heating

55° F to 120° F -10° F to 66° F

Important: Use caution when cleaning outdoor coil to ensure no water enters the electrical control compartment. When cleaning coil from inside the compressor compartment, take special care not to spray water towards the top rows of the coil near the control panel. Water may enter the control compartment and drive damaging the electronics. Disconnect all electric power, including remote disconnects before servicing.
Scan to see an overview video about the IVSC Board

18-BC89D1-1M-EN

3

Table of Contents
Unit Location Considerations . . . . . . . . . . . . . . . 5 Suggested Locations. . . . . . . . . . . . . . . . . . . . . . 6 Coastal Considerations . . . . . . . . . . . . . . . . 7
Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Setting Up the Unit . . . . . . . . . . . . . . . . . . . . . . . 8
Refrigerant Line Considerations . . . . . . . . . . . . 9 Refrigerant Line Brazing . . . . . . . . . . . . . . . . . . . 12 Refrigerant Line Leak Check . . . . . . . . . . . . . . . 14
Refrigerant Line and Indoor Coil Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Service Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Electrical -- Low Voltage Communicating . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Electrical ­ High Voltage . . . . . . . . . . . . . . . . . . . 17

Integrated Variable Speed Control Board LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
LED'S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Charge Adjustment . . . . . . . . . . . . . . . 20
Subcool Charging Correction Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Refrigerant Charging Chart . . . . . . . . . . . . . . . 21
Charging the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 23
Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only) . . . . . . . . . . 24
Communicating Display Assembly (CDA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Defrost Control (Heat Pump only). . . . . . . . . . 26
Checkout Procedures . . . . . . . . . . . . . . . . . . . . . . 27

4

18-BC89D1-1M-EN

Unit Location Considerations

Table 2. Unit Dimensions and Weight

Models

H x D x W (in)

4TWV0024A

46 x 30 x 33

4TWV0036A

48 x 34 x 37

4TWV0048A

48 x 34 x 37

4TWV0060A

52 x 34 x 37

4TTV0024A

46 x 30 x 33

4TTV0036B

48 x 34 x 37

4TTV0048A

48 x 34 x 37

4TTV0060A

52 x 34 x 37

4TTV0061A

52 x 34 x 37

* Weight values are estimated (uncrated).

Weight * (lb) 206 243 255 265 207 239 259 265 303

· When mounting the outdoor unit on a roof, be sure the roof will support the unit's weight.
· Properly selected isolation is recommended to alleviate sound or vibration transmission to the building structure.

Table 3. Refrigerant Line and Service Valve Connection Sizes

Model
4TWV0024A 4TWV0036A 4TWV0048A 4TWV0060A 4TTV0024A 4TTV0036B 4TTV0048A 4TTV0060A 4TTV0061A

Rated Line Sizes

Vapor Line 5/8 (a) 3/4 (a) 7/8 (a) 7/8 (a) 5/8 (a) 3/4 (a) 7/8 (a) 1 -- 1/8 (b)

Liquid Line 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

1 -- 1/8 (b)

3/8

Service Valve Connection Sizes

Vapor Line Liquid Line Connection Connection

3/4

3/8

3/4

3/8

7/8

3/8

7/8

3/8

3/4

3/8

3/4

3/8

7/8

3/8

7/8

3/8

7/8

3/8

H W
D

Standard Line Set 150' Max Line Length

50' Max Line Lift

100' Max Line Length

Refer to (a), (b), and (c) footnotes for specific model details

50 Max Line Lift

100' Max Line Length

(a) The max length of refrigerant lines from outdoor to indoor unit MUST NOT exceed 150 feet. The max vertical change MUST NOT exceed 50 feet. (b) The max length of refrigerant lines from outdoor to indoor unit MUST NOT exceed 80 feet. The max vertical change MUST NOT exceed 25 feet.

18-BC89D1-1M-EN

5

Unit Location Considerations

Table 4. Alternate Refrigerant Line and Service Valve Connection Sizes

Model
4TWV0024A 4TWV0036A 4TWV0048A 4TWV0060A

Alternate Line Sizes

Vapor Line
3/4" (a)

Liquid Line 5/16"

5/8" (a) 3/4" (a) 3/4" (a) 7/8" (a)

5/16" 3/8" 3/8" 3/8"

Service Valve Connection Sizes

Vapor Line Connection

Liquid Line Connection

3/4"

3/8"

3/4" 7/8" 7/8" 7/8"

3/8" 3/8" 3/8" 3/8"

Model
4TTV0024A 4TTV0036B 4TTV0048A 4TTV0060A

Alternate Line Sizes

Vapor Line 3/4" (a) 5/8" (a) 3/4" (a) 3/4" (a) 7/8" (a)

Liquid Line
5/16" 5/16" 3/8" 3/8" 3/8"

Service Valve Connection Sizes

Vapor Line Connection

Liquid Line Connection

3/4" 3/4" 7/8" 7/8" 7/8"

3/8" 3/8" 3/8" 3/8" 3/8"

4TTV0061A

3/4" (a) 7/8" (a)

3/8" 3/8"

7/8" 7/8"

3/8" 3/8"

(a) The max length of refrigerant lines from outdoor to indoor unit MUST NOT exceed 150 feet. The max vertical change MUST NOT exceed 50 feet.

Suggested Locations
Table 5. Suggested Locations for Best Reliability
· Ensure the top discharge area is unrestricted for at least 5 feet above the unit.
· Provide at least 3 feet clearance in front of the control box (access panels) and any other side requiring service.
· Do not locate close to bedrooms as operational sounds may be objectionable.
· Avoid locations near windows and similar areas where condensation and freezing defrost vapor can annoy a customer.
· Position the outdoor unit a minimum of 12" from any wall or surrounding shrubbery to ensure adequate airflow.
· Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water or icicles from falling directly on the unit.

Avoid Install Near Bedrooms
Min. 12" to Shrubbery

Min 5' Unrestricted
Min 3' Unrestricted
Access Panel

· Position the outdoor unit a minimum of 12" from any wall or surrounding shrubbery to ensure adequate airflow.
· Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water or icicles from falling directly on the unit.

Min. 12" to Shrubbery

Min. 12" to Wall

6

18-BC89D1-1M-EN

Unit Location Considerations

Table 6. Cold Climate Considerations (Heat Pump Only)

Note: It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below-freezing temperatures occur.
· Units should be elevated 3­12 inches above the pad or rooftop, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base pan are not obstructed, preventing drainage of defrost water.
· If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.

Min. 12"
Snow Barrier

Snow Legs
3-12" Elevation Pad

Coastal Considerations

If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.

18-BC89D1-1M-EN

7

Unit Preparation
1. Check for damage and report promptly to the carrier any damage found to the unit.
2. To remove the unit from the pallet, remove tabs by cutting with a sharp tool.
Setting Up the Unit
Table 7. Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following: · The pad should be at least 1" larger than the unit on all sides. · The pad must be separate from any structure. · The pad must be level. · The pad should be high enough above grade to allow for drainage. · The pad location must comply with National, State, and Local
codes.

8

18-BC89D1-1M-EN

Refrigerant Line Considerations
Table 8. Factory Charge
The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via subcooling (TXV/EEV).
Table 9. Required Refrigerant Line Length
Determine required line length and lift. You will need this to determine the subcooling charging corrections later in the installation process. Total Line Length = ___________________________Ft. Total Vertical Change (lift) = ____________________Ft.
Line Length

Table 10. Refrigerant Line Insulation

Important: The Vapor Line must always be insulated. DO NOT allow the Liquid Line and Vapor Line to come in direct (metal to metal) contact.

Liquid Line

Note: The gas line must always be insulated. Insulating the liquid line through attic spaces may benefit system performance by minimizing heat gain in the liquid line.

Vapor Line

Insulation

18-BC89D1-1M-EN

9

Refrigerant Line Considerations
Table 11. Reuse Existing Refrigerant Lines
CAUTION
REFRIGERANT!
Failure to inspect or use proper service tools may result in equipment damage or personal injury. If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken. · Ensure that the indoor evaporator coil and refrigerant lines are
the correct size. · Ensure that the refrigerant lines are free of leaks, acid, and oil. Important: For more information, see publication number SS-
APG006­EN

Table 12. Refrigerant Line Routing Precautions
Important: Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements. Important: For buried linesets, see publication number SS-APG006­EN. Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
For Example: · When the refrigerant lines must be fastened to floor joists or other framing in a structure, use isolation type hangers. · Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings. · Where the refrigerant lines run though a wall, sill or enclosed ceiling- they should be insulated, isolated and serviceable if any braze
connections are present. · Isolate the lines from all duct work. · Minimize the number of 90° turns.
Table 13. Isolation From Joist/Rafter

8 Feet Maximum

Joist/Rafter

Isolator

Side View

8 Feet Maximum

Line Set

Secure Vapor Line from joists using isolators every 8 ft. Secure Liquid Line directly to insulated Vapor Line using tape, wire, or other appropriate method every 8 ft.

10

18-BC89D1-1M-EN

Table 14. Isolation In Wall Spaces

Refrigerant Line Considerations

8 Feet Maximum

Wall Isolator

Side View

8 Feet Maximum

Line Set

Secure Vapor Line from joists using isolators every 8 ft. Secure Liquid Line directly to insulated Vapor Line using tape, wire, or other appropriate method every 8 ft.

Table 15. Isolation Through Wall
Wall

Sealant Insulation Vapor Line

Duct Work Isolator

Line Set DO NOT hang line sets from duct work

18-BC89D1-1M-EN

11

Refrigerant Line Brazing
Table 16. Braze the Refrigerant Lines
1. Remove caps or plugs. Use a deburring tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.
2. Remove the pressure tap cap and valve core from each service valve.
3. Purge the refrigerant lines and indoor coil with dry nitrogen.

12

18-BC89D1-1M-EN

Table 16. Braze the Refrigerant Lines (continued)
4. Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
5. Braze the refrigerant lines to the service valves. a. For Units shipped with a field-installed external drier, check liquid line filter drier's directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as illustrated. Braze the filter drier to the Liquid Line.
6. Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
Note: Precautions should be taken to avoid heat damage to base pan during brazing. It is recommended to keep the flame directly off of the base pan.
7. Replace the pressure tap valve cores after the service valves have cooled.

Refrigerant Line Brazing
3-4" from valve

18-BC89D1-1M-EN

13

Refrigerant Line Leak Check
Table 17. Check for Leaks
1. Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.

150 PSIG

2. Check for leaks by using a soapy solution at each brazed location.
Note: Remove nitrogen pressure and repair any leaks before continuing.

Refrigerant Line and Indoor Coil Evacuation
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.
1. Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.

0350
Microns
ON OFF

2. Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
3. When evacuation is complete, blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.

1 MIN.

14

18-BC89D1-1M-EN

Service Valves

Table 18. Open the Gas Service Valve

Important: Leak check and evacuation must be completed before opening the service valves.
Note: Do not vent refrigerant gases into the atmosphere.

Cap

1. Remove valve stem cap.
2. Using a wrench, turn valve stem 1/4 turn counterclockwise to the fully open position.
3. Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/4 turn.

Unit Side of Valve

1/4 Turn Only Counterclockwise for Full Open Position
Valve Stem

Pressure Tap Port Gas Line Connection

Table 19. Open the Liquid Service Valve

Cap
WARNING

SERVICE VALVES!

Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and/or property damage.
Extreme caution should be exercised when opening the Suction and Liquid Line Service Valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. No torque is required.

Unit Side of Service Valve

Important: Leak check and evacuation must be completed before opening the service valves.
4. Remove service valve cap.
5. Fully insert 3/16" hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns).
6. Replace the valve cap to prevent leaks. Tighten finger tight plus an additional 1/4 turn.

Service Port

3/16" Hex Wrench
Rolled Edge to Captivate Stem
Hex Headed Valve System

18-BC89D1-1M-EN

15

Electrical -- Low Voltage Communicating

Table 20. Low Voltage Maximum Wire Length
Table 20, p. 16 defines the size and combined total maximum length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat. Note: The use of color coded low voltage wire is recommended to simplify
connections between the outdoor unit, the control, and the indoor unit. Note: The maximum total cable length for the entire comfort control
communicating system is 500 ft. 18 AWG.

CONTROL WIRING

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

500 Ft. Combined

Table 21. Low Voltage Hook-up Diagrams

Figure 1. Fully Communicating System
Communicating Outdoor Unit

Communicating Communicating Comfort Control Indoor Unit

Note 4

D

Brown

R

Red

B

Blue

Field wiring

R

BK

D

D - Note 3

Y1

Y2 Note 1

G

&

W1 Note 2 W2

W3

B

B - Blue

O

Brown

Neatly bundle all low voltage wires as shown.

Blue

Red Note 5

Only used for Load Shed (Cap off if not used)

1. In communicating mode, unused terminals are non-functional. Do not use. 2. Terminals present will vary by indoor model. 3. "D" is the data line. Installer to select a wire color. 4. If a 3rd party condensate overflow switch is installed, it should be wired in series with R to the thermostat or connected to the External
Switch terminals on the AFC. See External Switch wiring section in the air handler Installer's Guide. 5. Wire present only on Variable Speed Outdoor Units.
Note: Anti-oxidizing grease is supplied in the documentation package for use when making low voltage field wiring connections at the outdoor unit. Apply grease to field wiring before installing wire caps to protect these connections from corrosion.

16

18-BC89D1-1M-EN

Electrical ­ High Voltage
Table 22. High Voltage Power Supply
WARNING
LIVE ELECTRICAL COMPONENTS!
Failure to follow this Warning could result in property damage, severe personal injury, or death. Follow all electrical safety precautions when exposed to live electrical components. It may be necessary to work with live electrical components during installation, testing, servicing, and troubleshooting of this product.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the control box cover and in the Service Facts document included with the unit.
Table 23. High Voltage Disconnect Switch
WARNING
HIGH LEAKAGE CURRENT!
Failure to follow this Warning could result in property damage, severe personal injury, or death. Earth connection essential before connecting electrical supply.
Install a separate disconnect switch at the outdoor unit.
For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem within the structure.
Table 24. High Voltage Disconnect Switch
Ground the outdoor unit per national, state, and local code requirements.

18-BC89D1-1M-EN

17

Integrated Variable Speed Control Board LED Indicators

J2
J10
J5 J3
J9 J8 J20

High

FAN

Voltage to Condensor

Fan Motor PSC

(not used)

PWM

EXT.ODT

LSOV

EEV T4

CDA
T3 COCOMMMM

PERSONALITY MODULE

STSATTAUTUSS
LOAD SHED

HPCO

T1 T2 9
18 CHARGE SOLENOID (N/A Phase I)

1 J1 10

DATA

DRB

The Status (Green) and COMM (Amber) LEDs are located in the upper right region of the Control Board.
Fault messages are displayed on the CANda

ALUMINUM COVER PLATE

J6 J4
MONITOR TOOL

Table 25. LED'S in clii mode

LED
STATUS (GREEN)

RATE SLOW MEDIUM FAST SOLID ON INTERMITTENT

Note: The STATUS Light is not illuminated in Link mode.

Table 26. LED'S in clii and Link modes

LED
COMM (AMBER)

RATE SLOW FAST

LED'S
LED
STATUS (GREEN)
COMM (AMBER)

RATE SLOW MEDIUM FAST SOLID ON INTERMITTENT SLOW FAST

18

DESCRIPTION 1 TIME PER SECOND 2 TIMES PER SECOND 5 TIMES PER SECOND
1 FLASH EVERY 4 SECONDS
DESCRIPTION 1 TIME PER DEVICE 5 TIME PER SECOND
DESCRIPTION 1 TIME PER SECOND 2 TIMES PER SECOND 5 TIMES PER SECOND
1 FLASH EVERY 4 SECONDS 1 TIME PER DEVICE 5 TIME PER SECOND

INDICATION STANDBY/IDLE CALL FOR CAPACITY POWER UP DELAY
TEST MODE HARD LOCKOUT
INDICATION DEVICE COUNT LOSS OF COMMUNICATION
INDICATION STANDBY/IDLE CALL FOR CAPACITY POWER UP DELAY
TEST MODE HARD LOCKOUT DEVICE COUNT LOSS OF COMMUNICATION
18-BC89D1-1M-EN

Start Up
1. Ensure you have completed the following sections. "Refrigerant Line Brazing," p. 12 through "Electrical ­ High Voltage," p. 17. 2. Set System Thermostat to OFF.

3. Turn on disconnect(s) to apply power to the indoor and outdoor units.
4. Wait 3 hours before starting the unit if the outdoor ambient temperature is below 85° F.
5. Run the system using the "Charging Mode-Cooling" test mode found in the 850/950/1050 comfort control. This is the only approved method for setting the system charge level by subcooling.
Follow the on-screen prompts. Important: ENSURE INDOOR BLOWER IS CONFIGURED FOR 400
CFM/TON

ON OFF
3 HRS

18-BC89D1-1M-EN

19

System Charge Adjustment
Table 27. Temperature Measurements
Check the outdoor temperatures. Subcooling using "Charging Mode-Cooling" is the only recommended method of charging between 55 ° F and 120° F ambient outdoor temperature.
For best results the indoor temperature should be kept between 70° F to 80° F.

120° F 55° F
80° F 70° F

Table 28. Subcooling Charging Corrections
Determine the final subcooling value using total Line Length and Lift measured in "Required Refrigerant Line Length" and the "Subcooling Charging Corrections Charts."

Subcooling Charging Correction Worksheet

Total Line Length (ft)

________________________

Total Vertical Charge (lift) ________________________ (Values from -- Required Refrigerant Line Length)

Design Subcooling Value ________________________ (from nameplate or Service Facts)

Final Subcooling Value ________________________

Note: The only mode approved for setting or validating system charge is using Charging Mode-Cooling. Charging Mode-Cooling is a variable speed test mode found in the 850/950/1050 and UX360 comfort control Technician Menu's. Test modes can also be accessed using the Diagnostic Mobile App on Link systems. Outdoor Temperature must be between 55°F and 120°F with Indoor Temperature kept between 70°F and 80°F.
Important: VARIABLE SPEED OUTDOOR UNITS REQUIRE THE INDOOR UNIT BE CONFIGURED FOR 400 CFM/TON IN clii MODE.

20

18-BC89D1-1M-EN

Subcool Charging Correction Charts

REFRIGERANT LINE LIFT (FEET)

Figure 2. Subcool Charging Corrections -- 2.0 Ton

2.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

50

Add 1° Add 2°

40

Add 1°

30

25

Use Design Subcooling

15

10

0
20 30 40 50 60 70 80 90 100 110 120 130 140 150 TOTAL REFRIGERANT LINE LENGTH (FEET)

Important: VARIABLE SPEED OUTDOOR UNITS REQUIRE THE INDOOR UNIT BE CONFIGURED FOR 400 CFM/TON IN clii MODE ONLY.
Note: System will auto configure airflow in Link mode.

REFRIGERANT LINE LIFT (FEET)

REFRIGERANT LINE LIFT (FEET)

Figure 3. Subcool Charging Corrections -- 3.0 Ton

3.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

50

Add 1°

Add 2°

40

Add 1°

30

25

Use Design Subcooling

15

10

0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 TOTAL REFRIGERANT LINE LENGTH (FEET)

Figure 4. Subcool Charging Corrections -- 4.0 Ton

4.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

50

Add 1°

Add 2°

40

Add 1°

30

1°

25

Use Design Subcooling

1°

15

1°

10

0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 TOTAL REFRIGERANT LINE LENGTH (FEET)

Figure 5. Subcool Charging Corrections --5.0 Ton

5.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

REFRIGERANT LINE LIFT (FEET)

50

1°

Add 4°

40

Add 1°

Add

2°

30

Use Design Subcooling

25

Add 1°

15 AC: 1-1/8" Vapor Line Limit 10

Add 1°

0

1°

20 30 40 50 60 70 80 90 100 110 120 130 140 150

TOTAL REFRIGERANT LINE LENGTH (FEET)

NOTE: 150 ft. length is approved ONLY with 7/8" vapor lines.

Refrigerant Charging Chart
R-410A REFRIGERANT CHARGING CHART

LIQUID TEMP

(°F)

8

DESIGN SUBCOOLING (°F)

9

10

11

12

13

14

LIQUID GAGE PRESSURE (PSI)

55

179

182

185

188

191

195

198

60

195

198

201

204

208

211

215

65

211

215

218

222

225

229

232

18-BC89D1-1M-EN

21

Subcool Charging Correction Charts

R-410A REFRIGERANT CHARGING CHART

70

229

232

236

240

243

75

247

251

255

259

263

80

267

271

275

279

283

85

287

291

296

300

304

90

309

313

318

322

327

95

331

336

341

346

351

100

355

360

365

370

376

105

381

386

391

396

402

110

407

413

418

424

429

115

435

441

446

452

458

120

464

470

476

482

488

125

495

501

507

514

520

247

251

267

271

287

291

309

313

331

336

355

360

381

386

407

413

435

441

464

470

495

501

527

533

22

18-BC89D1-1M-EN

Charging the Unit

Important: ENSURE INDOOR BLOWER IS CONFIGURED FOR 400 CFM/TON
Table 29. Proper Gage Pressure
Using the Standard R-410A Subcool Charging Chart, adjust refrigerant level to attain proper gage pressure. Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
1. Connect gauges to refrigerant bottle and unit as illustrated. 2. Purge all hoses. 3. Open bottle. 4. Stop adding refrigerant when liquid line temperature and Liquid
Gage Pressure match the charging chart. Note: Recover refrigerant if the Liquid Gage Pressure is higher than the
chart value.
Table 30. Stabilize the system
5. Wait 20 minutes for the system condition to stabilize between adjustments.
Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system is properly charged.
6. Remove gauges. 7. Replace service port caps to prevent leaks. Tighten finger tight
plus an additional 1/6 turn.
Table 31. Verify Performance
8. Refer to System Pressure Curves in the Service Facts document to verify typical performance.

SUCTION PRESSURE (PSIG)

DISCHARGE PRESSURE (PSIG)

20 MIN.

PRESSURE CURVE SAMPLE

Cooling @ 1450 SCFM

Heating @ 1350 SCFM

550 INDOOR ENTERING WET BULB CURVES
500 TOP TO BOTTOM 71, 67, 63 AND 59 DEG F.
450

400

350 (4)

(3)

300

250

(1) 200

40

60

80

100

(2) 120

500 INDOOR ENTERING DRY BULB CURVES
450 TOP TO BOTTOM 80, 70, AND 60 DEG F.
400

350

300

250

200

-5

5

15 25 35 45 55 65

OUTDOOR TEMPERATURE (Degree F)

170 INDOOR ENTERING 165 WET BULB CURVES
TOP TO BOTTOM 160 71, 67, 63 AND 59 DEG F.
155

150

145 (5) 140

(3)

135

130

125

120

115

(1)

110

40

60

80

100

(2) 120

140 INDOOR ENTERING 130 DRY BULB CURVES
TOP TO BOTTOM 120 80, 70, AND 60 DEG F.
110

100

90

80

70

60

50

40

30

-5

5

15 25 35 45 55 65

Table 32. System Information

9. Record system pressures and temperatures after charging is complete.

Outdoor model number =

________________________

Measured Outdoor Ambient = ________________________°F

Measured Indoor Ambient = ________________________°F

Measured Liquid Line Temp = ________________________°F

Measured Suction Line Temp = ________________________°F

Indoor Wet Bulb =

________________________°F

Liquid Gage Pressure = ________________________ PSIG

Suction Gage Pressure = ________________________ PSIG

18-BC89D1-1M-EN

23

Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)

Table 33. Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
The Subcooling Charging method in cooling is not recommended below 55º F outdoor temperature.
The only recommended method of charging at outdoor temperatures below 55º F is weighing in the charge in heating mode and referencing the refrigerant pressure curves for typical performance.

STEP 1 - Determine additional charge.
Note: The nameplate charge value represents the amount of refrigerant shipped in the outdoor unit and is compatible with 10 feet of AHRI rated refrigerant lines and the smallest AHRI rated coil.
Using the method below, find the charge associated with the additional length of tubing above 10 ft. and record it below.
Calculating Charge Using the Weigh-In Method
1. Measure in feet the distance between the outdoor unit and the indoor unit. (Include the entire length of the line from the service valve to the IDU.) Subtract 10 ft from this entire length and record on line 1.
2. Enter the charge multiplier (0.6 oz/ft). Each linear foot of interconnecting tubing requires the addition of 0.6 oz of refrigerant.
3. Multiply the total length of refrigerant tubing (Line 1) times the value on Step 2. Record the result on Line 3 of the Worksheet.
4. This is the amount of refrigerant to weigh-in prior to opening the service valves.

Weigh-In Method can be used for the initial installation, or anytime a system charge is being replaced. Weigh-In Method can also be used when power is not available to the equipment site or operating conditions (indoor/outdoor temperatures) are not in range to verify with the subcooling charging method.
1. Total Line length (ft) ­10 ft _______________ 2. Charge multiplier x ____0.6 oz______ 3. Step 1 x Step 2 = ______________ 4. Refrigerant (oz) = ______________

STEP 2 - Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made.

20 MIN.

STEP 3 - Check the liquid line temperature and liquid gage pressure to obtain a minimum of 10º subcooling in heating mode. Measured Liquid Line Temp = __________ º F Liquid Gage Pressure = __________ PSIG
STEP 4 - Add charge if a minimum of 10º subcooling is not obtained with the namplate charge plus additional charge previously added.
STEP 5 - Return to site for adjustment. Important: Return in the spring or summer to accurately charge the system in the cooling mode with outdoor ambient above 55º F.

24

18-BC89D1-1M-EN

Communicating Display Assembly (CDA)

SYSTEM STATUS XXXXXXXXXXXXXXXX

NAVIGATION
· To enter and exit Technician Menus, press the Up/Down buttons simultaneously for 5 seconds.
· To return to the Home Screen, press the Up/Down buttons simultaneously for 5 seconds.
· To return to the top level of any menu, press the Left/Right buttons simultaneously for 5 seconds.
· After five minutes of inactivity in the Technician Menu section, the Home Screen will be displayed. Pressing the Enter button for 5 seconds will increase this time to 20 minutes.
TECHNICIAN MENUS

MONITOR MENU

ALERT MENU

ALERT HISTORY MENU

CONFIG MENU

The Monitor Menu

The Alert Menu

displays information displays active alerts.

on System status, Drive

stats and the System

Tachometer.

Scan to see an overview video about the CDA

The Alert History menu displays alerts stored over time. Note that clearing Alert History will also clear Active Alerts.

The Configuration Menu is where System parameters and options are set and reported.
1. External shut down (Load Shed)
2. Min. Airflow 3. Blower on/off delays 4. Custom Airflow 5. PFC (Power Factor
Correction)

CONTROL MENU
The Control Menu contains a selection of unit function tests that are used to verify operation.
1. FRC DFT (Forced Defrost) 2. EEV Test 3. Evacuation 4. Drive Diagnostic Test 5. OD Fan Test

Note: See the Service Facts found in the control box of the outdoor unit for more information.

18-BC89D1-1M-EN

25

Defrost Control (Heat Pump only)

Demand Defrost
The demand defrost control measures heat pump outdoor ambient temperature with a sensor located outside the outdoor coil. A second sensor located on the outdoor coil is used to measure the coil temperature. The difference between the ambient and the colder coil temperature is the difference or delta-T measurement. This delta-T measurement is representative of the operating state and relative capacity of the heat pump system. By measuring the change in delta-T, we can determine the need for defrost. The coil sensor also serves to sense outdoor coil temperature for termination of the defrost cycle.

Fault Identification
A fault condition is indicated by the CDA connected to the control board inside the heat pump control box.

Defrost Enabled
Demand Defrost is enabled with the following inputs to the Integrated Variable Speed Control (IVSC):
· Outdoor ambient temperature sensor (ODS-B) reporting an outdoor temperature at or below 52° F.
· Coil temperature sensor (CBS) reporting a coil temperature at or below 35° F.
· Heat/Cool Demand (HCD) from the communicating comfort control for at least two minutes or more.

Defrost Initiation
The calculated temperature difference between the outdoor temperature sensor and the coil temperature sensor is called Delta T. Defrost can occur once the current Delta T exceeds the Delta T initiate value. . This adaptive logic assures a complete defrost for a range of outdoor temperatures.

DEFROST TERMINATION PROFILES
65ºF
HIGH TERMINATION TEMP 60ºF

55ºF

MEDIUM TERMINATION TEMP

TERMINATION TEMPERATURE

50ºF FACTORY TERMINATION TEMP
45ºF

40ºF
35ºF
30ºF -40ºF

-20ºF

0ºF

20ºF

AMBIENT TEMPERATURE

SOFTWARE 1.0/2.0

SOFTWARE 3.0 AND LATER

40ºF

60ºF

CDA Navigation to Forced Defrost Figure 6. CANda Mini Menu

CONFIG MENU

CONTROL MENU

MONITOR MENU

FRC DFT
PRESS ENTER

TEST IN PROGRESS
CTS <value>
TEST COMPLETE

NOTES: Forced Defrost
1. System must be running with demand from the thermostat.
2. FRC DFT TEST can be initiated in heat mode only.
3. Press ENTER to begin forced defrost.
4. Execute Forced Defrost following Forced Defrost (Defrost terminates on Coil Temperature or maximum time override of 15 minutes).
5. When test begins, TEST IN PROGRESS displays on line 1 and Coil Temperature value on line 2.
Note: Home Screen, under System Status will display DEFROST.
6. When test is complete, TEST COMPLETE displays for 10 seconds.
7. If there is a defrost fault condition, test terminates and sends alert to the alert menu.
8. For more information, refer to the Alert Code Tables in Service Facts and Technical Service Manual (Pub. No. 34­4301­01) documents.
Note: Screens will update as the test proceeds.

26

18-BC89D1-1M-EN

Checkout Procedures

The final phase of the installation is the system Checkout Procedures. The following list represents the most common items covered in a Checkout Procedure. Confirm all requirements in this document have been met.

 All wiring connections are tight and properly secured.
 Voltage and running current are within limits.
 All refrigerant lines (internal and external to equipment) are isolated, secure, and not in direct contact with each other or structure.
 All braze connections have been checked for leaks. A vacuum of 350 microns provides confirmation that the refrigeration system is leak free and dry.
 Final unit inspection to confirm factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other or any component when unit runs.
 Ductwork is sealed and insulated.
 All drain lines are clear with joints properly sealed. Pour water into drain pan to confirm proper drainage. Provide enough water to ensure drain trap is primed.

 Supply registers and return grilles are open, unobstructed, and air filter is installed.
 Indoor blower and outdoor fan are operating smoothly and without obstruction.
 Indoor blower motor set on correct speed setting to deliver required CFM. "Blower and fan set screws are tight."
 Cover panels are in place and properly tightened.
 For gas heating systems, manifold pressure has been checked and all gas line connections are tight and leak free.
 For gas heating systems, flue gas is properly vented.
 System functions safely and properly in all modes.
 Owner has been instructed on use of system and given manual.

18-BC89D1-1M-EN

27

Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane. com or tranetechnologies.com.

The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory. org.

Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

18-BC89D1-1M-EN 19 Jul 2023 Supersedes 18-BC89D1-1L-EN (April 2020)

©2023 Trane



References

PDFlib PDI 9.2.0 (C /Win64)