FSD901-U2/ FSD901-R2/ FSD901-U3/FSD901-R3 Floor Repeater Display Product Manual

Overview
Characteristic
A6V10333726_c_en_-2020-02-05

The floor repeater display is an indication and operation unit in a fire detection system

with the following functions:

Indication of events

Operation

l Alarm

l Scrolling through lists

l Trouble

l Reset

l Supervisory

l Acknowledge

l Status

l Unsilence

l Silence

The display on the floor repeater terminal is synchronized with the fire control panel and displays the same event texts.

l Small floor repeater operating, and display panels applied in FC2005/FC901 fire detection system
l Large backlight LCD display(160X64) l Communication with controller via RS485 (individual addressing) l Additional 24 VDC power supply necessary l In total, up to 8 FSD can be connected to a fire control panel l Access control by key l Flat, elegant housing
Smart Infrastructure
firealarmresources.com

Function Application

l Display of alarms, troubles, supervisory and status event l Same message layout as the fire control panel l With the navigation keys an indicated list in the display can be scrolled through l The internal buzzer can be switched off manually by pressing button "Acknowledge" l Reset events displayed on the FSD l Silence and unsilence

User Level
A6V10333726_c_en_--

Fig.1 Front view
No. Name 1. LCD 2. Alarm 3. Four-way button 4. Power 5. Trouble 6. Ground Fault 7. Silenced 8. Supervisory 9. Audibles on 10. <Reset> 11. <Acknowledge> 12. <Unsilence > 13. <Silence > 14. Lock

Function Display of alarms, troubles, supervisory and status Light up in case of fire For menu navigation Light up when power supply is normal Light up in case of trouble event Light up in case of ground fault event All activated silenceable devices are silenced Light up in case of supervisory event Light up when NAC or silenceable device is activated Clear all events Acknowledges unacknowledged events All silenced devices are activated again Silence all activated silenceable devices Set user access level by key

FSD floor repeater display control access right through lock on door. There are two user levels for access right:

User level

Lock key position

L0

L1

The operation items for L0/L1 are listed as below:

Items

L0

L1

View real time events





Acknowledge

-



Reset

-



Silence

-



Unsilence

-



Lamp test

-



2
firealarmresources.com

Operation

Task View real time events
Lamp test
Acknowledge or reset events Unsilence devices Silence devices
Address and Baud Rate

Operation 1. Press "" / "" to navigate a real time event. 2. Press "" to return to first event. Press both "Silence" and "Unsilence" button for 5s to do lamp test. Press "Acknowledge" or "RESET".
Press "Unsilence", all silenced devices are activated again. Press "Silence", silence all activated silenceable devices.

8-digit Dip-switch S1 is used for setting the FSD901 address and Baud Rate Setting. The first 1-4 digits is for setting the FSD901 address 1-8, the 7-8 digits is for setting RS485 communication baud rate. The 5 and 6 digits are reserved for future use.

DIP switch

DIP switch

Address

1

2

3

4

Baud Rate

7

8

1

On Off Off Off

9600 bps

Off Off

2

Off On Off Off

19200 bps On Off

3

On On Off Off

38400 bps Off On

4

Off Off On Off

115200 bps On On

5

On Off On Off

6

Off On On Off

7

On On On Off

8

Off Off Off On

FC2005 and FC901 can only support 19200 bps, other options reserve for future usage.

EOL Resistor

Installation

2-digit Dip-switch S20 is used for setting EOL resistor of RS485.

1 and 2

OnInternal EOL resistor is connected

1 and 2

OffInternal EOL resistor is disconnected

For RS485 Class A, loop mode, no EOL resistor is needed.

For RS485 Class B, stub mode, internal EOL resistor of the repeater display at the end

of RS485 must be connected.

Fig 2 Dimension (mm) 3

Note:
·
·

Fig 3 Connection
Point G is not used for any connection. Power in from the non-resettable auxiliary power output on panel.

firealarmresources.com

A6V10333726_c_en_--

Fig 4

Fig 5

1. Insert the loop line and external power wire through the floor repeater display.

2. Mark the position for the 4 installation holes on flat wall (Fig. 2), drill the holes, put expansion bolts in and insert the

screws leaving a small gap for hanging the display.

3. Hang the floor repeater display over those screws through installation holes.

4. Open the front panel (Fig. 4/5), tighten the screws and make sure the display is fixed firmly.

5. Connect cables to terminals referring to the connection diagram (Fig. 3). Correctly set the internal 120 EOL

resistor referring to the section "EOL Resistor".

6. Close the front panel.

FSD connects to separate power supply, which needs to be UL Listed for Fire Safety Use and Power

Limited.

Dimension (mm)

Technical data

Operating voltage Operating current (quiescent) Activation current Operating temperature Humidity Communication protocol Connection terminals Color Operating location

24 VDC nominal / 19...28 VDC 60 mA 70 mA
0...+49 °C 93% rel. UFP (RS485-BUS) 14-18 AWG Black / Red Indoor / dry

Details for ordering

Type FSD901-U2 FSD901-R2 FSD901-U3 FSD901-R3

Material No. S54433-C102-A4 S54433-C102-A3 S54433-C102-A1 S54433-C102-A2

Part No. 100935670 101061934 101061935 100935673

Designation Desigo system display (black) Desigo system display (red) Cerberus system display (bl) Cerberus system display (red)

Weight 1.5 kg 1.5 kg 1.5 kg 1.5 kg

Issued by

Siemens Industry, Inc.

Smart Infrastructure

8 Fernwood Road

Florham Park, NJ 08932

Tel. +1 973-593-2600

www.sbt.siemens.com/FIS

Doc No.

A6V10333726_c_en_--

© Siemens Industry, Inc., 2019
Technical specifications and availability subject to change without notice

100935693