MT8090/8092XE Series Installation Instruction

Installation and Startup Guide

This document covers the installation of MT8090/8092XE Series HMI. For detailed specifications and operation, please refer to the Brochure and EasyBuilder Pro User Manual.

Install Environment:

NEMA RatingMT8090/8092XE Series HMI is NEMA 4 rated.
Electrical EnvironmentMT8090/8092XE Series has been tested to conform to European CE requirements. The circuitry is designed to resist the effects of electrical noise, but this does not guarantee noise immunity in severe cases. Proper wire routing and grounding will ensure proper operation.
Environmental Considerations
  • Ensure displays are installed correctly and operating limits are followed. Avoid environments with severe mechanical vibration or shocks.
  • The HMI product is certified in accordance with ATEX zone 2/22 categories 3 G/D. The unit must be installed in an additional enclosure ensuring a minimal protection level for 3G/D equipment. The enclosure must be certified and should not be opened when an explosive atmosphere is present.
  • Do not install the unit where acid gas, such as SO2, exists.
  • This device should be mounted in the vertical position and used on a flat surface enclosure.
  • Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in Pollution Degree 2 Environment.
  • Relative Humidity: 10% ~ 90% (non-condensing).

Unpacking the Unit

Unpack and check the delivery. If damage is found, notify the supplier.

NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it fall may cause damage.

Included items:

  • Installation Instruction, 2-sided A4 *1
  • Human Machine Interface *1
  • Power Connector *1
  • Brackets & Screws *1 pack
  • Fuse 1.25A/250V 5*20mm *1

The packing box can be transformed into an HMI stand. Follow these steps:

  1. Remove the center of the box cover along the perforated line.
  2. Pull the two inner flaps.
  3. Press down along the perforated line inside the box.
  4. Complete the stand as shown in the diagram. [Diagram showing box transformation into a stand]

Installation Instructions

Secure the operator panel in position using all fastening holes and the provided brackets and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (To achieve a waterproof effect and prevent panel deformation.)

Panel cutout dimensions:

TypeA(mm)B(mm)
MT8090XE250192
MT8092XE250192

[Diagram showing panel mounting with brackets and screws]

[Diagram showing grounding connection FG 24VDC]

Power Connections

NOTE:

  1. Connect the positive DC line to the '+' terminal and the DC ground to the '-' terminal.
  2. When downloading projects using a USB cable, do not connect the HMI with the PLC and PC simultaneously, as electric potential difference may result in damage to the HMI or PC.

System Settings

MT8092XE:

When the HMI is powered up and displays an image, press the system setting button in the lower-right corner of the screen. (Default System Password: 111111)

Navigate to the Network tab to choose automatic DHCP IP acquisition or to designate your own IP address. MT8092XE has two 10/100/1000 Base-T Ethernet ports. The default IP addresses are: LAN 1: DHCP, LAN 2: 192.168.100.1

[Screenshot of System Settings Network tab for MT8092XE]

MT8090XE:

When the HMI is powered up and displays an image, press the system setting button. (Default System Password: 111111)

Connect the HMI to your network using an RJ-45 cable. [Diagram showing RJ-45 connection]

Navigate to the Network tab to choose automatic DHCP IP acquisition or to designate your own IP address.

[Screenshot of System Settings Network tab for MT8090XE]

EasyBuilder Pro Software Settings

Launch EasyBuilder Pro software, select your project file, and press the F7 shortcut key to open the download dialog box.

Select Ethernet > IP tab > Enter your HMI IP > Click Download to transfer the project file to the HMI. Using a screensaver and backlight saver is recommended to prevent image persistence caused by displaying the same image for extended periods.

(Refer to the EasyBuilder Pro User Manual for detailed software operation.)

Communication Connections

NOTE:

  1. COM2 and COM3 [RS485] 2W support MPI 187.5K; use one at a time.
  2. Only Tx & Rx (no RTS/CTS) can be used for COM1 RS-232 when COM3 RS-232 is also used.

Communication Port Pinouts:

  • Con.B: COM1/3 [RS232] 9 Pin, Male, D-sub
  • Con.A: COM2/3 [RS485] / CAN Bus 9 Pin, Female, D-sub
PIN#COM1 [RS232]COM3 [RS232] (MT8092XE only)PIN#COM2 [RS485] 2WCOM2 [RS485] 4WCOM3 [RS485]CAN Bus
1Data-1Rx-
2RxDRxD2Data+Rx+
3TxDTxD3Tx-
44Tx+
5GNDGND5GNDGNDGND
66Data-CAN_L
7RTSTxD7CAN_H
8CTSRxD8
99Data+

*CAN Bus is not applicable for MT8090XE1 model.

Calibration Mode

To enter touch screen calibration mode, press and hold anywhere on the screen for more than 2 seconds when the HMI starts.

Battery Replacement

Battery replacement must be performed by qualified personnel only. Exercise caution when handling lithium batteries. For more information on battery replacement and disposal, please refer to: http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf

CAUTION

NOTE: Ensure all local and national electrical standards are met during installation. Contact local authorities to determine applicable codes.

PowerThe unit can be powered by DC power only, with a voltage range of 24±20% Volts DC, compatible with most controller DC systems. The power conditioning circuitry is accomplished by a switching power supply. Peak starting current can be as high as 2A.
Fusing RequirementsIf the display does not power on within 5 seconds, remove power. An internal fuse prevents damage if the DC power polarity is incorrect. Check wiring for proper connections and attempt to power up again.
High VoltageAn internal fuse prevents damage for overcurrent conditions, but it is not guaranteed. DC voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency StopA hard-wired EMERGENCY STOP should be fitted in any system using the HMI to comply with ICS Safety Recommendations.
Supply Voltage ConditionDo not power the unit and inductive DC loads, or input circuitry to the controller, with the same power supply. Note: The 24 VDC output from some controllers may not have sufficient current to power the unit.
Wire Routing
  • Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
  • Use twisted pair cables for power and signal wires, conforming to impedance matching.
  • If wiring is exposed to lightning or surges, use appropriate surge suppression devices.
  • Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
  • Add a resistor and capacitor in parallel between the ungrounded DC power supply and the frame ground to provide a path for static and high-frequency dissipation. Typical values are 1M Ohm and 4700pF.

DANGER

Hardware ConsiderationsSystem designers should be aware that controller system devices can fail, creating unsafe conditions. Electrical interference in an operator interface can lead to equipment startup, potentially causing property damage and/or personal injury. If using programmable control systems requiring an operator, be aware of this potential safety hazard and take appropriate precautions. While specific design steps vary by application, the following precautions generally apply to the installation of solid-state programmable control devices and conform to NEMA ICS 3-304 Control Standards.
Programming ConsiderationsTo comply with ICS Safety Recommendations, incorporate checks within the controller program to ensure all writable registers controlling critical plant or machinery have limit checks. Implement an out-of-limit safe shutdown procedure to ensure personnel safety.

Limited Warranty

This product is warranted against defects in design and manufacture. Weintek will, at its discretion, repair or replace proven defective products. This warranty does not cover products that:

  • Are outside the warranty period (12 months from the manufacturing date of the HMI products).
  • Suffer damage from Force Majeure, accident, negligence, improper installation, or misuse.
  • Have been repaired or disassembled by unauthorized technicians.
  • Have had their identification markings removed or damaged.

PDF preview unavailable. Download the PDF instead.

GME8090X2 MT8090 8091 8092XE1 Installation Microsoft Word 2010

Related Documents

Preview Weintek MT8091XE 9.7" TFT HMI Touchscreen Panel
Detailed specifications and features of the Weintek MT8091XE, a 9.7-inch TFT LCD HMI touchscreen panel with fanless cooling, USB host, RS-485 and CAN bus communication, and NEMA4/IP65 front panel protection.
Preview Weintek cMT1106X Series HMI Installation Guide
Comprehensive installation instructions for the Weintek cMT1106X Series HMI, covering setup, wiring, system settings, and safety precautions.
Preview cMT-FHDX Series HMI Installation and Startup Guide
Comprehensive guide for installing and starting up the cMT-FHDX Series HMI, covering environment, unpacking, installation, power connections, system settings, software configuration, communication, DIP switch settings, battery replacement, and warranty information.
Preview Weintek MT8051iE Series HMI Installation Guide
Comprehensive installation and startup guide for the Weintek MT8051iE Series Human Machine Interface (HMI). Covers environmental requirements, unpacking, physical installation, power connections, system settings, software configuration, communication protocols, calibration procedures, battery replacement, safety precautions, and limited warranty information.
Preview Weintek EasyAccess2.0: Remote HMI Management and Startup Guide
This user manual provides comprehensive guidance on Weintek's EasyAccess2.0 software, enabling secure remote access, monitoring, and management of industrial HMIs and PLCs. It covers domain creation, HMI activation, user management, and pass-through functionalities.
Preview WEINTEK EasyBuilder Pro Quick Start Guide: HMI Project Creation and Download
A comprehensive quick start guide for WEINTEK's EasyBuilder Pro software. Learn to create HMI projects, configure PLC devices, simulate, manage IP addresses, and download projects to WEINTEK HMIs.
Preview EasyBuilder Pro: Window Operations Guide
Learn how to create, set, and delete windows in EasyBuilder Pro, including different window types, transparency settings, and editing tips for efficient project development.
Preview EasyBuilder Pro: 文字標籤庫與多國語言使用指南
本指南詳述 WEINTEK EasyBuilder Pro 軟體中文字標籤庫的建立與管理,以及如何實現多國語言顯示。內容涵蓋文字標籤的創建、語言與字型設定、匯入匯出功能,以及快速新增文字標籤的方法,旨在協助使用者有效管理和顯示多語言內容。