User Manual for Petasense models including: VM4P, 2AJW7-VM4P, Vibration Mote Wireless Condition Monitoring Sensor, Vibration Mote, Wireless Condition Monitoring Sensor, Condition Monitoring Sensor, Monitoring Sensor, Sensor

Copy of Mote User Manual

User Manual

Petasense Inc VM4P 2AJW7-VM4P 2AJW7VM4P vm4p


File Info : application/pdf, 21 Pages, 3.69MB

PDF preview unavailable. Download the PDF instead.

GetApplicationAttachment.html?id=7676675
FCC ID : 2AJW7-VM4P

Mote Model 3 User Manual

Revision History
Version 1.0

Date May 1, 2024

Notes Pre-Release

Contributor Harsha Mokkarala

1

Mote Model 3 User Manual

Table of Contents

Revision History

2

Data Sheet

4

How to Install Vibration Motes

7

How to Remove Petasense Motes

13

Blink Up - How to Connect Vibration Motes to WiFi

15

2

Mote Model 3 User Manual

Data Sheet
Accelerometer Frequency Response Frequency Response Accuracy Measurement Range Transverse Sensitivity AD Conversion Sensitivity Sampling Rate Resolution

Model 4 Tri-axial MEMS 2 to 6,000 Hz (+/- 3 dB) At X Hz: X% At Y Hz: Y% +/- 2g to +/- 16g TBD 16 Bit 0.061 mg/LSB 26.7 kHz

TEMPERATURE SENSOR Measurement Range

-40°C to 80°C (-40°F to 185°F) (+/- 5% accuracy)

MAGNETIC SENSOR Digital Output Magnetic Field Sampling Rate

i2C Full scale adjustable from +/- 4 gauss to +/- 16 gauss Up to 1 KHz

PHYSICAL

Dimensions

Height: 90mm

3

Mote Model 3 User Manual

S-ring diameter: 38.7 mm (1.52 inches)

Weight

Mounting (recommend epoxy Epoxy: Steel-enforced two-part epoxy

or stud)

Stud: 6.35 mm (¼ inch) 28 UNF

Materials

Cover: UV Stabilized, Flame Retardant Polycarbonate Base, Mount and S-ring: SS316

ENVIRONMENTAL Operating Temperature Range Storage Temperature Shock Resistance Certifications

-40°C to 80°C (-40°F to 185°F)
< 85°C (185°F) without battery 2 meter fall, 16 g continuous vibration Class I Div 2 (ABCD), IP67, NEMA 4, FCC, CE, RoHS compliant

POWER Source Battery Life

2x CR123A (CR17345) 3V Lithium
1-2 years with 8 measurements per day ~20% reduced battery life if operating below -10°C (15°F)

CONNECTIVITY Wireless Protocol
Antenna Processor

WiFi (2.4 GHz, 802.11 b/g/n) Bluetooth (Pro models only)
WiFi/Bluetooth Antenna | 5 dBi max gain
Dual Core 32-Bit Processor

ACCESSIBILITY

User Interface

Web: Internet browser access Mobile: iOS application available in App Store

4

Mote Model 3 User Manual
Security

TLS 1.2 with AES encryption

5

Mote Model 3 User Manual
How to Install Vibration Motes
Overview Mounting Petasense Motes is simple and does not require any special skills. Each Mote takes about 5-10 minutes to mount. Start monitoring the health of your industrial machines in four simple steps: Step 1. Power up the Mote Step 2. Prepare the machine surface Step 3. Mix the epoxy Step 4. Mount the Mote
What you will need:  Petasense Motes  CR123A 3V Batteries (Duracell recommended for longer battery life)  Handheld rotary tool with sanding attachment (Dremel recommended)  2-part steel-enforced epoxy (JB Weld SteelStik recommended) - Safety Datasheet  X-Acto knife  Rubber gloves (for mixing epoxy)  Soap Water (1:4 soap to water mixture)  Shop towels  Protective glasses  Protective gloves  Dust Mask  Silicone/Lithium Grease
6

Mote Model 3 User Manual
Mote Components: These instructions will reference specific components of the Mote as follows:
7

Mote Model 3 User Manual
Before Getting Started 0.1 Confirm that your WiFi network has coverage in the machine areas. If possible, perform a brief site survey with a mobile device. 0.2 Prepare the appropriately sized pieces of 2-part steel-enforced epoxy. Each Mote requires a 2.5 ­ 3-gram piece of epoxy. Each tube of JB-Weld SteelStik will contain enough epoxy for approximately 20 Motes. 0.3 Document the allocation of your Motes very carefully. Keep a record of the serial numbers of your Motes and which machines they are mounted on. This attention to detail is essential for any successful asset monitoring program. Note: Before handling Petasense Motes, be sure to wash your hands to avoid getting dirt or other particles inside the device.
Now, let's get started. Step 1. Power up the Mote 1.1 Remove the Mote cover and insert a new CR123A battery. The Mote will blink a series of yellow and red LEDs, ending with a slow, blinking green LED, indicating that the Mote has successfully connected to WiFi. If the Mote only blinks yellow and/or red, you will need to configure the Mote with the appropriate WiFi credentials before continuing. (See "How to Connect Vibration Motes to WiFi") 1.2 Once the Mote has connected to WiFi, replace the cover, place the device on the mount, place the S-ring over the top of the device and thoroughly tighten the S-ring clockwise at the base. *If using Model 2, please see further instructions below.*
8

Mote Model 3 User Manual
Step 2. Prepare the machine surface 2.1 Identify a mounting location close to where the bearing is located on the machine. The ideal mounting location will be a rigid, flat surface. Avoid mounting on sheet metal covers, fins or other flimsy surfaces that are prone to rattle.
2.2 Use the rotary tool to strip the paint from the mounting location on the machine. 2.3 Apply Soap Water to a shop towel and wipe off any dirt or particles from the sanded mounting location.
9

Mote Model 3 User Manual
10

Mote Model 3 User Manual
Step 3. Mix the epoxy 3.1 Wearing rubber gloves, knead one piece of 2-part steel-enforced epoxy thoroughly in your hand until the color is uniform. Ensure that the epoxy is in good condition (firm and slightly moist, not too hard or crumbly). Once the epoxy is mixed, you will need to apply it to the Mote quickly or it will start to harden.
3.2 Roll epoxy into a 2-3 inch strip, then form a ring on the bottom of the Mote mount.
11

Mote Model 3 User Manual
Step 4. Mount the Mote 4.1 Place the Mote on the mounting location with the Petasense logo facing the closest machine shaft. Press down firmly for 15-20 seconds.
Note: It is important that the Mote is mounted with the Petasense logo facing the direction of the machine's shaft for orientation purposes 4.2 Visually check that the epoxy is only bonding to the base of the Mote, not touching the knurled S-ring above the mount. If it is touching the S-ring, use the X-Acto knife to push the edges of the epoxy down toward the machine surface, so that the S-ring can be removed in the future for battery changes. Mounting Complete!
12

Mote Model 3 User Manual
13

Mote Model 3 User Manual
How to Remove Petasense Motes
Overview: Petasense Motes will need to be removed and reinstalled from time to time as your equipment will require maintenance or replacement. There are a few options when it comes to removing your Motes safely and efficiently. Option 1: Temporary removal of the Petasense Motes for equipment repairs/maintenance: If your equipment will be removed temporarily and reinstalled with the same configuration, Petasense Motes may also be removed and stored without going through the whole installation process. Step 1: With safety gloves on, secure the Mote with one hand and remove the S-Ring by turning counter-clockwise with your other hand. Once removed, please store the Mote and S-Ring together until re-mounting. The Mount can remain on the machine component for re-mounting later.
14

Mote Model 3 User Manual
Step 2: Remove the CR123a Battery for storage or discard/recycle properly if spent. Step 3: After the equipment is reinstalled, re-insert a CR123a Battery and verify it has taken a reading with the Petasense Mobile App. Step 4: Remount the Mote by placing in the correct orientation on the mount and then fastening the S-Ring tightly (clockwise).
Option 2: Permanent removal of Petasense Motes and Mounts In the case your equipment will be replaced with new components, you can safely remove the Mote and recover the Mount. Step 1: Follow the steps above to remove the Petasense Mote from the mount. Step 2: With a chisel and rubber hammer you can gently chip away the SteelStik Epoxy easily and recover the Mount. A Flathead Screwdriver can also be used in place of a chisel.
15

Mote Model 3 User Manual
Step 3: Clean the Mount by chipping away any leftover epoxy residue with the Chisel/Rubber Hammer. A Handheld Grinder can also be used to clean the Mount.
16

Mote Model 3 User Manual
Blink Up - How to Connect Vibration Motes to WiFi
How to Connect Vibration Motes to WiFi
Connecting Vibration Motes to your WiFi network is a quick and simple process, which utilizes a technology called Blink Up. This is a method of using your mobile device to optically communicate WiFi login credentials to a Vibration Mote. * Note: If your WiFi network was provided by Petasense, your Vibration Motes should already be configured to the wireless network when you receive them.
Summary 1. Log in to the Petasense App 2. Configure your WiFi credentials 3. Power up the Vibration Mote 4. Initiate Blink Up 5. Confirm a successful WiFi connection
What you will need  Petasense Vibration Mote 17

Mote Model 3 User Manual
 iOS mobile device  3V CR123a batteries  WiFi network access (see network requirements)
Pro Tip: Perform Blink Up in a low-light area Indoors, away from any windows or ambient lights, best results in a shaded area (e.g. underneath a desk)
Step 1: Log in to the Petasense App
1-1. Install the Petasense App Using your iOS mobile device, install the Petasense App from the App Store.
1-2. Login using your email and password If you have not set up a personal Petasense Login, contact your Petasense Account Admin to gain access.
Step 2: Configure your WiFi credentials
2-1. Navigate to Blink Up On the main dashboard page, select More from the bottom-right corner of the screen. Then select Blink Up.
2-2. Enter your WiFi Credentials Select Configure WiFi and enter the SSID and password of your WiFi network. Then select Next.
Step 3: Power up the Vibration Mote
3-1. Access the battery compartment of the Mote Unscrew the steel S-ring and slide it over the top of the Mote. Remove the Mote from the steel mount and carefully pull off the plastic cover.
3-2. Insert the battery Insert one 3V CR123a battery into the battery compartment.
18

Mote Model 3 User Manual
3-3. Confirm a successful power-up On the opposite side of the battery compartment, you will notice a flashing red LED on the top-right corner of the Mote, indicating that the Mote was successfully powered up and ready to receive WiFi credentials. If no light appears; remove the battery, wait 15 seconds and reinsert the battery.
Step 4: Initiate Blink Up
4-1. Select Start on your mobile device After selecting Start, there will be a 3-second countdown on-screen before Blink-Up starts. You will need to quickly perform the next step before the countdown ends.
4-2. Place the Mote (LED side) on the screen of your mobile device With your mobile device on a table or in your palm, place the Mote on top with the blinking red LED facing the screen. If the Blink Up sequence starts before you place the Mote on the screen, wait until the sequence is over, select the back arrow and try again.
4-3. Confirm a successful Blink Up As soon as the Blink Up sequence is over, pick up the Mote and check the LED. You should immediately see a flashing green LED, indicating that the Mote successfully received your WiFi credentials.
Step 5: Confirm a successful WiFi connection
5-1. Confirm a recent measurement on the Petasense App To confirm that the mote has taken a measurement select the Sensors option at the bottom of your screen. Then select the Sort option at the top left of the screen. From there select Serial Number - Ascending/Descending. Find the serial number of the mote you are attempting to connect and verify that a measurement has been taken by checking the Last Measurement option.
5-2. Reassemble the Mote
19

Mote Model 3 User Manual
Once you have confirmed the connection, you may remove the battery until it is time to install the Mote on a machine. Then replace the plastic cap and place the Mote on the steel mount. Lastly, place the steel S-ring over the top of the Mote and tighten clockwise at the base.
Success! Your Vibration Mote is now connected to WiFi!
Federal Communication Commission (FCC) Radiation Exposure Statement When using the product, maintain a distance of 20cm from the body to ensure compliance with RF exposure requirements. This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: The manufacturer is not responsible for any radio or TV interference caused by unauthorized modifications or changes to this equipment. Such modifications or changes could void the user's authority to operate the equipment. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. -Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. -Consult the dealer or an experienced radio/TV technician for help. FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
20



References

Skia/PDF m126 Google Docs Renderer