SCHNEIDER ELECTRIC APC BACK-UPS PRO BGM1500B (01)
User Manual Back-UPSTM Pro Gaming UPS BGM1500 / BGM1500B
Important Safety Instructions
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage. SAVE THESE INSTRUCTIONS - This section contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · This UPS is intended for indoor use only. · Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust
or humidity. · Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. · Connect the UPS power cable directly to a wall outlet. Failure to follow these instructions will result in death or serious injury.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE · Replace the battery at least every 5 years or at the end of its service life, whichever is earlier. · Replace the battery immediately when the UPS indicates battery replacement is necessary. · Replace batteries with the same number and type of batteries as originally installed in the
equipment. · Replace the battery immediately when the UPS indicates a battery over-temperature condition, or
when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced. Failure to follow these instructions can result in minor or moderate injury and equipment damage.
Inventory
USB Data Port Cable
https://manual-hub.com/

Connect the Battery
The UPS is shipped with the battery disconnected.

 Lay the UPS with the battery door facing up. The arrows point to the locking tabs of the battery compartment.

 Press the tabs downwards and pull the battery door away from the unit to access the battery modules.

 Using the handles on both sides of the battery, lift the battery 30 degrees upward to expose the battery connector. Connect the red wire as shown above.

 Push the battery into the unit

 Align the side rails on the cover with the rails on the UPS and slide the cover till it locks in position.
Install PowerChute TM Personal Edition Software
Use PowerChute Personal Edition software to configure the UPS settings. During a power outage, PowerChute will save any open files on your computer and shut it down. When power is restored, it will restart the computer.
Note: PowerChute is only compatible with a Windows operating system. If you are using Mac OSX, use the native shutdown feature to protect your system. See the documentation provided with your computer.
Installation Use the USB Data Port Cable supplied with the Back-UPS to connect the data port on the Back-UPS to the USB port on your computer. Download PowerChuteTM Personal Edition Software from www.apc.com/pcpe. Select the appropriate operating system and follow directions to download the software.

2

Back-UPS Pro Gaming UPS 1500 VA

https://manual-hub.com/

Connect the Equipment
Battery Backup and Surge Protected outlets
When the Back-UPS is receiving input power, the Battery Backup with Surge Protection outlets will supply power to connected equipment. During a power outage or other AC problems, the Battery Backup outlets receive power for a limited time from the Back-UPS. Connect Gaming PC, Console, router and Monitor to these outlets so you could stay on line during power outage.
Connect equipment such as External Hard Drive, Television or other peripherals that do not need battery backup power to the Surge Protection Only outlets. These outlets provide full-time protection from surges even if the Back-UPS is turned off.

 USB and Serial Data Port
 Ground Screw
 Building Wiring Fault Indicator
 Coaxial Ports with Surge Protection

To use PowerChute Personal Edition, connect the supplied USB communication cable.
Connect the ground lead from an additional surge suppression device such as a stand-alone data line surge protector.
If this illuminated, there is a problem with the wiring in the building. Contact an electrician immediately and do not use the Back-UPS.
Connect a cable modem or other equipment with coaxial jacks.

 Circuit breaker Reset Button

Use to reset the system after an overload condition has tripped the circuit breaker interrupt current flow.

 Surge Protected Outlets
 In/Out Ethernet Surge Protected Ports
 Battery Backup Outlets with Surge Protection
 Rear LEDs

These outlets provide full-time protection from surges, even if the Back-UPS is off. Connect equipment such as printers and scanners that do not require battery backup protection. Use an Ethernet cable to connect a cable modem to the in port, and connect a computer to the OUT port.
During a power outage or other AC problems, the Battery Backup receive power for a limited time from the Back-UPS. Connect critical equipment such as Gaming PC, Console, Router or other gaming gear into these outlets. The Rear LEDs provide 12-color ambient lights to help you add/remove loads from outlets.

Back-UPS Pro Gaming UPS 1500 VA

3

https://manual-hub.com/

Operation
Top Bezel Buttons and Display Interface Use the four buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.
Front panel
 INFORMATION button
 POWER ON/OFF button
 MUTE button
 Display interface
 LED button
 USB charging ports: The 3 USB ports provide a total of 15W of DC power, and will provide power even when the UPS is on battery.
Reactor Circle: Provides 12-color ambient lights.

On Line: The Back-UPS is supplying conditioned Utility power to connected equipment
Load Capacity: The approximate load capacity percentage is indicated by the number of load bar sections illuminated. Each bar represents approx 20% of load capacity.
Battery Capacity: The battery charge level is indicated by the number of bar sections illuminated. When all five bar sections are illuminated, it indicates that the battery is fully charged. When only one bar section is illuminated, it indicates the battery charge is nearing depletion.
Low Battery: When the battery charge is completely depleted and the UPS is nearing shutdown, the indicator will flash accompanied by a continuous beep.
Replace Battery: The battery is nearing the end of its useful life and should be replaced immediately.
On Battery: The UPS is supplying battery power to the connected equipment. The UPS will emit an audible beep once in every 10 seconds.
System Error Detected: A system error has been detected. The system error number will be displayed on the display interface. Refer "Detected System Errors" on page 7, for details.
Overload: The connected equipment is drawing more power than the rated capacity of the UPS.

4

Back-UPS Pro Gaming UPS 1500 VA

https://manual-hub.com/

Mute: An illuminated line through the icon indicates that the audible alarm is disabled.
Out: Output voltage, frequency
In: Input voltage, frequency
Automatic Voltage Regulation: When illuminated, the Back-UPS is compensating for low input voltage. When illuminated, the Back-UPS is compensating for high input voltage.
Estimated Runtime: Indicates the remaining runtime (in minutes) in on-battery mode.
Load: The total load in watts (W) or percentage (%) used by the devices indicates the remaining runtime (in minutes) in on-battery mode.
Event: The number of events that shows up on the LCD screen are the number of power disturbances that your UPS has detected. These disturbances can be any of the following: blackout, under/over voltage, total harmonic distortion, surge, spike, etc.

Back-UPS Pro Gaming UPS 1500 VA

5

https://manual-hub.com/

Unit sensitivity

The higher the sensitivity, the more often the Back-UPS switchs to battery power. Adjust the sensitivity of the Back-UPS to control when the UPS will switch over to
battery power;

1. Turn off the Back-UPS while connected to a wall outlet.

2. Press and hold the INFORMATION button for six seconds. The Load capacity icon will flash on and off, indicating that the Back-UPS is in programming
mode.

3. Press INFORMATION button to navigate through the menu options. Stop at selected sensitivity.

Generator Sensitivity

Default

Sensitive Loads

Low sensitivity
78-150 Vac
Gaming UPS will change to battery mode only when input voltage is extremely low or high. Not recommended for computer or gaming console loads.

Medium sensitivity (Default)
88-147 Vac
This is default sensitivity setting and is recommend for Gaming PC and Gaming consoles.

High sensitivity
88-144 Vac
The connected equipment is sensitive to voltage fluctuations.

6

Back-UPS Pro Gaming UPS 1500 VA

https://manual-hub.com/

Alarms and Detected System Errors

Audible Indicators Overload Low battery Overcharge Battery replacement Battery mode Internal error detected

Beep every 0.5 second Beep every 0.5 second Beep every 1.5 seconds Beep every 2 seconds Beep every 30 seconds Continuous beep

Detected System Errors

If the UPS system does not operate correctly, use the table below to resolve the

problem.

F01

Overload fault

Turn the Gaming UPS off. Disconnect non-essential

equipment from the Battery Backup outlets and then

turn Gaming UPS on.

F02

Output short.

Turn the Gaming UPS off. Disconnect all

equipment from the Battery Backup outlets and

then turn Gaming UPS on. Reconnect

equipment one item at a time. If the system

error is detected again, disconnect the last

connected equipment as it is in an inoperable

condition.

F05

Over Charge Voltage

Contact your APC support

F06

Relay Welding

Contact your APC support

F07

Over Temperature or NTC Contact your APC support

disconnected

F08

Fan lock error detected.

Contact your APC support.

F12

Battery mode output high. Contact your APC support

F13

Battery mode output low

Contact your APC support

F28

Low battery voltage

Replace the battery. If the detected error still occurs after battery is replaced, contact APC by Schneider Electric Support"

Back-UPS Pro Gaming UPS 1500 VA

7

https://manual-hub.com/

Function Power On

Button

Timing 2 sec

Description Press and hold the POWER ON/OFF button to turn on UPS.

Power Off

2 sec

Press and hold the POWER ON/OFF button to turn off UPS.

Self-Test mode UPS Information
Sensitivity
Mute
LED Color
Previous LED Color Turn on/off the led lights
Event Reset

6 sec 0.2 sec 6 sec
2 sec

Press and hold the POWER ON/OFF button for 6 seconds (buzzer will beep when 6 seconds pass) to go into Self-Test mode when UPS is in Line mode or AVR mode.
Press the INFORMATION button to display UPS information. The information will cycle from Event counter  Runtime  Load watt  Load VA  Load percentage  Output voltage  Output frequency  Input voltage  LCD off
When the UPS is powered off, press and hold the INFORMATION button, the Load Capacity icon will blink, indicating that the UPS is in programming mode. Use the INFORMATION button to scroll through Low, Medium, and High. Stop at selected sensitivity for 5 seconds. The UPS will beep confirming the selection.
Press and hold the MUTE button to enable or disable the audible alarms.

0.2 sec 2 sec

Click to LED button to select LED Color (There are twelve colors to choose from.). The front and rear LED will be synced in color.
Press and hold the LED button (till a beep is heard after 2 seconds) to select previous LED Color

6 sec 0.2 sec

Press and hold the LED button to turn on/off the LED lights (buzzer will beep when after 6 seconds pass). The status will cycle through: Front and rear LED on  Front LED on, rear LED off  Front LED off, Rear LED on  Front LED and rear LED off
When the Event screen is visible, press and hold INFORMATION button, then press POWER ON/OFF button to clear the detected event counter.

8

Back-UPS Pro Gaming UPS 1500 VA

https://manual-hub.com/

Status Indicators

Unit Status

Description

Standby

When the unit is plugged into the AC outlet but is turned off, LCD will display battery capacity, input voltage and mute icon. LED ring will be in customized
color. In standby mode, the connected equipment will not be protected.

UPS is turning on All LEDs will light up and the colors will slowly cycle among all available colors. The process should take about 10 seconds.

Equipment is plugged in

The Reactor circle will show the load percentage. The Rear LEDs do not change. Rear LEDs will return to idle state after 10 seconds.

Equipment is unplugged

The Reactor circle will show the load percentage. Rear LEDs do not change. Rear LEDs will return to idle state after 10 seconds.

Idle State

This animation occurs after 10s of inactivity. This occurs every time except when UPS has detected a system error. Rear LED doesn't change (keeps custom/default color).
Idle state color is defined by the custom color that user selects (default white).
LED illumination in idle state is always at 60% intensity.

Press a button

The LCD will be lit. The unit will switch to idle state after 10 seconds of inactivity.

Power Outage (unit goes on
battery)

The Reactor circle will light up to show the runtime percentage, and the
displayed percentage will reduce as the runtime reduces. The reactor circle color will be green and blinking if battery life is above 50%, orange and
pulsing when battery life is between 20% and 50%, red and flashing when
battery life is under 20%.

Low Battery

When the unit is on battery and the battery capacity is low (i.e. when the unit continuously beeps) the reactor circles that is still on will turn red and pulsing regardless of the color you have selected. The backlight will match this functionality - but only when lighting is enabled.

Overload

The reactor circle lights up in red. It will remain in this state until the unit is
no longer overloaded.

Dead Battery

The reactor circle lights up in red. It will remain in this state until the battery
is charged or replaced

Building Wiring Fault

The reactor circle lights up in red and pulsing. It will remain in this state
until the building wiring fault is no longer detected

Power Surge

All LEDs light up in your chosen color
Rear LED has same behavior as Reactor circle.

Power Dip

All LEDs light up in your chosen color
Rear LED has same behavior as Reactor circle.

LCD Information

LCD will cycle through different information when INFORMATION button is pressed. The information will be cycle from Event counter  Runtime  Load watt  Load VA  Load percentage  Output voltage  Output frequency  Input voltage  LCD off.
When Runtime is displayed, the Reactor circle color will be green and blinking if battery life is above 50%, orange and pulsing when battery life is between 20% and 50%, red and flashing when battery life is under 20%

When Load percentage is displayed, the LED ring color will be green.

Troubleshooting

Back-UPS Pro Gaming UPS 1500 VA

9

https://manual-hub.com/

Problem
Back-UPS will not switch on.
The Back-UPS does not provide power during a utility power outage.
The Back-UPS is operating on battery power, while connected to utility power.
The Back-UPS does not provide the expected amount of backup time.
The Replace Battery indicator is illuminated. The Overload indicator is illuminated.
The System Error Detected indicator is illuminated, all the front panel indicators are flashing.

Possible Cause
The Back-UPS is not connected to utility power.
The circuit breaker has tripped.
The internal battery is not connected. The input voltage is out of range. Be sure that essential equipment is not plugged into a surge only outlet. Plug is not inserted fully into the wall outlet, the wall outlet is no longer receiving utility power, the circuit breaker has tripped. The Back-UPS is performing an automatic self-test. The input voltage is out of range, the frequency is out of range, or the waveform is distorted. Battery Backup outlets may be fully or improperly loaded. The battery was recently discharged due to a power outage and has not fully recharged. The battery has reached the end of its useful life.
The battery has reached the end of its useful life.
The equipment connected to the Back-UPS is drawing more power than the Back-UPS can provide.
An internal error has been detected.

Corrective Action
Be sure that the Back-UPS is securely connected to a utility outlet. Disconnect non-essential equipment from the Back-UPS. Reset the circuit breaker. Reconnect equipment one item at a time. If the circuit breaker trips again, disconnect the device that caused the circuit breaker to trip. Connect the battery.
Adjust the transfer voltage and sensitivity range. Disconnect equipment from the surge only outlet and re-connect to a Battery Backup outlet. Be sure that the plug is fully inserted into the wall outlet. Be sure that the wall outlet is receiving utility power by checking it with another device. Reset the circuit breaker
No action is necessary.
Adjust the transfer voltage and sensitivity range.
Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to surge outlets.
Charge the battery cartridge for 16 hours.
Replace the battery.
Replace the battery immediately
Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to surge outlets.
Determine the detected system error by matching the detected error number displayed on the LCD with the corresponding detected system error number in "Detected System Errors" table in page 7. Contact SEIT Technical Support

10

Back-UPS Pro Gaming UPS 1500 VA

https://manual-hub.com/

Specifications
VA
Maximum Load Nominal Input Voltage Online Input Voltage Range
Automatic Voltage Regulation
Frequency Range On-battery Waveshape USB charging port Typical Recharge Time Transfer Time Operating Temperature Storage Temperature Unit Dimensions Unit Weight Color Interface On-Battery Runtime International Protection code

Gaming UPS 1500 VA
1500 VA
900 W
120 V 88 - 147 V Boost by +15.7% when input voltage drops below limit Trim by -13.6% when input voltage exceeds limit 60 Hz ± 3 Hz Sinewave Type C*1, Type A*2 (15 W in total) 16 hours 8ms (Typical), 10ms (Max) 32 to 104  (0 ~ 40 ) 23 to 113  (-15 to 40  ) 16.0 ×4.1 ×11.4 in (408 ×105 ×291 mm) 25.3 lb (11.5 kg) Black &White USB Go to: http://www.apc.com/ IP20

Replacement Battery
The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Contact APC support for battery replacement parts. Battery replacement parts for BGM1500 and BGM1500B is APCRBC163. Delaying the replacement of batteries may corrode the batteries in the cartridge. Recycle spent battery cartridges.

Warranty
The standard warranty is three (3) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

Back-UPS Pro Gaming UPS 1500 VA

11

https://manual-hub.com/

APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric web site, www.apc.com.
Select models are ENERGY STAR® qualified. For more information on your specific model visit the APC by Schneider Electric web site, www.apc.com.
Select models are compliant with California (CEC) Battery Charger regulations. For more information on your specific model visit the APC by Schneider Electric web site, www.apc.com.
FCC Radio Frequency Class B Warning
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
· Reorient or relocate the receiving antenna. · Increase the separation between the equipment and receiver. · Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected. · Consult the dealer or an experienced radio/TV technician for help

© 2020 APC by Schneider Electric. APC, the APC logo, PowerChute

and Back-UPS are owned by Schneider Electric Industries S.A.S.

or their affiliated companies. All other trademarks are property of EN 990-6266

their respective owners

09/2020