Schneider Electric EasyPact CVS100-250 Circuit Breaker
Circuit breaker / Switch-disconnector
DANGER / PELIGRO / 危险 / GEFAHR / PERICOLO / ОПАСНОСТЬ
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. Refer to NFPA 70E, CSA Z462, or local equivalents.
- This equipment must only be installed and serviced by qualified electrical personnel.
- Turn off all power supplying this equipment before working on or inside it. Lock the switchgear in the isolated position.
- Always use a properly rated voltage sensing device to confirm power is off.
- Install safety barriers and display a danger sign.
- Replace all devices, doors, and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
Product Identification
Model Series: EasyPact CVS100-250
Document Identifier: S1A19928-07
Manufacturing Date Code: The product's manufacture date is coded PP-YYYY-Www-D, where:
- PP: Plant code
- YYYY: Year of manufacture
- Www: Week of manufacture
- D: Weekday of manufacture (Monday = 1)
Example: 7Q-2014-W19-3 indicates a product manufactured at plant 7Q on Wednesday, May 7, 2014.
Installation and Connections
General Notes
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. Schneider Electric assumes no responsibility for consequences arising from the use of this material.
Mounting Hardware and Torque Specifications
For terminal connections, the following screw sizes and torque values are applicable:
- For 100 A (3P/4P): Use M6 x 20 screws (6 for 3P, 8 for 4P). Torque: 1.2 N.m (10.5 lb-in).
- For 160/250 A (3P/4P): Use M8 x 20 screws (6 for 3P, 8 for 4P). Torque: 1.2 N.m (10.5 lb-in).
- For control circuit terminals: Use M5 x 70 screws (2 for 3P, 4 for 4P). Torque: 5 N.m (44 lb-in).
Cable Connection Details
Ensure proper conductor sizing and connection torque for safe operation.
For 100/160 A Breakers:
- Steel Terminals: For conductors up to 95 mm² (AWG 4/0), use part numbers LV429242 (3P) or LV429243 (4P). For conductors 1.5-4 mm² (AWG 16-12), use specific lugs.
- Cu/Al Conductors: For 1.5-95 mm² (AWG 16-4/0), use part numbers LV429242 (3P) or LV429243 (4P).
- For conductors 1.5-4 mm² (AWG 16-12): Use specific lugs.
- Torque: For 100 A, 10 N.m (88 lb-in). For 160 A, 15 N.m (130 lb-in).
For 100-250 A Breakers:
- Aluminium Terminals:
- For 25-50 mm² (AWG 4-1/0) Cu/Al conductors, torque: 20 N.m (180 lb-in).
- For 70-95 mm² (AWG 2/0-4/0) Cu/Al conductors, torque: 26 N.m (225 lb-in).
- For 120-185 mm² (250-350 kcmil) Cu/Al conductors, torque: 26 N.m (225 lb-in).
- Part Numbers for Lugs: LV429227 (3P, 25-95 mm²), LV429228 (4P, 25-95 mm²), LV429259 (3P, 120-185 mm²), LV429260 (4P, 120-185 mm²).
- Torque: For 100 A, 10 N.m (88 lb-in). For 160-250 A, 15 N.m (130 lb-in).
Note on Dimensions: Terminal hole sizes are Ø22 mm (0.9 in) for 3P and 4P main terminals. Mounting dimensions are provided for reference.
Accessory Installation
Various accessories can be installed, including auxiliary contacts, shunt trip units, and alarm contacts. Refer to the diagrams for specific installation steps and part numbers.
- Auxiliary Contacts: Part numbers include LV429261 (3P), LV429262 (4P) for CVS100, and LV431563 (3P), LV431564 (4P) for CVS160/250. Installation involves clipping them onto the breaker.
- Shunt Trip Units: Part numbers include LV429263 (3P), LV429264 (4P) for CVS160/250. Installation involves mounting them on the side of the breaker.
- Connection Kits: Kits like LV429235 (3P/4P) and LV429236 (3P/4P) are used for connecting accessories. Installation involves attaching parts A and B with M6 x 20 screws, torqued to 5 N.m (44 lb-in).
- Cable Entry Covers: Part numbers LV429515 (3P), LV429516 (4P) for CVS100, and LV429517 (3P), LV429518 (4P) for CVS160/250.
- Terminal Blocks: Part numbers LV429330 (3P), LV429331 (4P).
Diagrammatic Instructions: Detailed visual steps are provided for attaching accessories. These often involve aligning components, pushing them into place until a click is heard [Click sound], and securing them with screws where applicable. Some installations may require a 180-degree rotation of a component.
Torque for Accessory Screws: Specific torque values are provided for accessory mounting screws, e.g., 0.9 N.m (8 lb-in) and 1.2 N.m (10.5 lb-in).
Protection Settings Adjustment
The thermal-magnetic trip units allow adjustment of the overload trip threshold (Ir) and the instantaneous short-circuit trip threshold (Im). The diagrams illustrate the adjustment ranges and time-current curves.
TM100D Trip Unit (for CVS100)
- Current Rating: 70/100A
- Adjustable Overload Trip (Ir): From 70 A to 100 A.
- Instantaneous Short-Circuit Trip (Im): Fixed at 800 A.
- The diagram shows the time-current curve for these settings.
TM125 G Trip Unit (for CVS160/250)
- Current Rating: 88/125A
- Adjustable Overload Trip (Ir): From 88 A to 125 A.
- Instantaneous Short-Circuit Trip (Im): Fixed at 440 A.
- The diagram shows the time-current curve for these settings.
MA 6.3 Trip Unit
- Current Rating: 6.3A
- Adjustable Overload Trip (Ir): From 38 A to 63 A.
- Instantaneous Short-Circuit Trip (Im): Fixed at 6.3 A.
- The diagram shows the time-current curve for these settings.
Note: Ensure settings are appropriate for the protected circuit and load.